| Plan Review Notes For Permit 05110263 |
| Permit Number |
05110263 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-06-30 00:00:00 | ALL COMMENTS ADDRESSED: | | | RESPONSE TO COMMENTS DATED 5/3/06 | | | | | | COMMENT #1 - INDICATES SUPPLY DUCT SHALL | | | BE IN A RATED CHASE.OK | | | | | | COMMENT #3 - SUBDUCT DETAIL ON PLAN | | | SHEET M-10 | | | | | | COMMENT #5 - RESPONSE INDICATES PLAN | | | SHEETS M-15 & M-16 (CHILLED WATER | | | PIPING) WERE REMOVED.PLANS ARE STILL | | | IN FOR RE-SUBMITTAL.PLEASE REMOVE. | | | | | | NEW COMMENTS | | | COMMENT #1 - OK | | | COMMENT #2 - PLANS STILL IN SUBMITTAL | | | THAT ARE NOT PERTINENT. | | | COMMENT #3 - OK | | | | | | PLEASE NOTE, BTU'S USED FOR COMBUSTION | | | AIR CALUCALTIONS ARE NOT CORRECT.PLAN | | | SHOWS 165,000 BTU'S PER DRYER AND THE | | | MANUFACTURE SUBMITTAL DATA INDICATE | | | 215,000 BTU'S. |
|