2006-06-30 00:00:00ALL COMMENTS ADDRESSED:
 RESPONSE TO COMMENTS DATED 5/3/06
  
 COMMENT #1 - INDICATES SUPPLY DUCT SHALL
 BE IN A RATED CHASE.OK
  
 COMMENT #3 - SUBDUCT DETAIL ON PLAN
 SHEET M-10
  
 COMMENT #5 - RESPONSE INDICATES PLAN
 SHEETS M-15 & M-16 (CHILLED WATER
 PIPING) WERE REMOVED.PLANS ARE STILL
 IN FOR RE-SUBMITTAL.PLEASE REMOVE.
  
 NEW COMMENTS
 COMMENT #1 - OK
 COMMENT #2 - PLANS STILL IN SUBMITTAL
 THAT ARE NOT PERTINENT.
 COMMENT #3 - OK
  
 PLEASE NOTE, BTU'S USED FOR COMBUSTION
 AIR CALUCALTIONS ARE NOT CORRECT.PLAN
 SHOWS 165,000 BTU'S PER DRYER AND THE
 MANUFACTURE SUBMITTAL DATA INDICATE
 215,000 BTU'S.