Plan Review Notes
Plan Review Notes For Permit 05110263
Permit Number 05110263
Review Stop P
Sequence Number 2
Notes
Date Text
2006-04-29 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WPB CITY CODE/ORDINENCES
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS WILL REMAIN THE SAME.
  
 2. ALL ARCHITECTURAL SHEETS SHALL SHOW
 THE DATE THAT THE SEAL WAS AFFIXED TO
 THE PLANS. FAC 61G1-16.003 &
 61G1-16.004(5) AND FS 481.219 &
 481.2055. MANY SHEETS HAVE NO DATE ON
 THE SEAL AND THE CERTIFICATE OF
 AUTHORIZATION NUMBER SHALL BE IN THE
 TITLE BLOCK OF EACH SHEET.
 ***NO RESPONSE: ID SHEETS HAVE PREPARED
 BY THE ARCHITECT HAVE NO DATE ON THE
 SEAL AND NO SHEETS HAVE THE CERTIFICATE
 OF AUTHORIZATION NUMBER ON EACH SHEET.
  
 3. POOL PLAN: SEPARATE PERMIT/PLANS
 REQUIRED FOR THE POOL. MINIMUM 2 SETS OF
 PLANS SHALL BE REVIEWED AND STAMPED BY
 THE PBC HEALTH DEPT. PRIOR TO SUBMITTING
 TO THE CITY WPB FOR REVIEW.
 ***NO RESPONSE: THIS WAS INFORMATIONAL.
  
 5. SHT A.01 ROUTE PLANS TO DBPR,
 DIVISION OF HOTEL & RESTURANT FOR REVIEW
 PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF
 PLANS SHALL BE REVIEWED, STAMPED AND TWO
 SHEET "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW.
 SECTION 102.2.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 7. SHT A.01 INDICATES ROOM TYPES K4, K5,
 K6, K7, KING HI, KING, KS, K2, K3, KING
 2, KING 3, KING 8, QQ, QQ HI, BUT ONLY
 K4, K7, KS, KE, KING 2, OFFER
 ACCESSIBLITY. PLEASE INDICATE HOW THIS
 COMPLYS WITH SECTION 11-9.1.4 CLASSES OF
 SLEEPING ACCOMMODATIONS.
 ***NO RESPONSE, NOT ADDRESSED.
  
 8. SHT A.01 PLAN KEY NOTES: UNABLE TO
 LOCATE KEY PLAN NUMBERS 7 AND 10. PLEASE
 SHOW NUMBERS ON FLOOR PLAN. SECTION
 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 9. SHT A.01 ADA ROOMS MATRIX INDICATES
 ROOM 121 AS HAVING A SHOWER. TABLE
 INDICATING NUMBER OF ACCESSIBLE ROOMS
 INDICATE 4 ARE REQUIRED WITH ONE ROOM
 WITH A ROLL IN SHOWER REQUIRED. PLEASE
 INDICATE IF ROOM 121 IS ONE OF THE FOUR
 REQUIRED ACCESSIBLE ROOMS. SECTION
 11-9.1.2.
 ***NO RESPONSE, NOT ADDRESSED.
  
 10. SHT A.01 ADA ROOMS MATRIX INDICATES
 5 ROOMS FOR THE HEARING IMPAIRED ROOMS.
 ONE ROOM (226) IS NOT SHOWN ON THE FLOOR
 PLAN. (4 OTHER ROOMS SHOWN AS HEARING
 IMPAIRED ACCOMODATIONS). PLEASE CLARIFY.
 SECTION 11-9.1.3.
 ***NO RESPONSE, NOT ADDRESSED.
  
 11. SHT A.01 1 ROOM SHALL COMPLY WITH
 SECTION 11-9.2.3 PLEASE INDICATE THE
 ROOM NUMBER THAT SHALL COMPLY WITH THIS
 REQUIREMENT.
 ***NO RESPONSE, NOT ADDRESSED.
  
 12. SHT A.05 SUBMIT A DETAIL FOR
 SCUPPERS. ALL DOWNSPOUTS ARE NOT SHOWN
 ON THE ELEVATIONS. PLEASE CLARIFY.
 SECTION 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 13. SHT A.17 BREAK SINK TO COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL.
 ***NO RESPONSE, NOT ADDRESSED.
  
 14. SHT A.17 PLAN KEY NOTES: SHOW THE
 LOCATIONS OF NUMBER 2 & 10. SECTION
 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 15. SHT A.32 SHOW CENTER OF FIXTURE OFF
 THE WALL AT 18" FOR THE WATER CLOSET.
 (FIG. 28). SHOW THE FLUSH CONTROLS AS
 REQUIRED IN SECTION 11-4.16.5.
 ***NO RESPONSE, NOT ADDRESSED.
  
 16. SHT A.33A LAV CLEARANCE TO BE 29"
 PER 11-4.19.2. (27" SHOWN). - SHOW THE
 FAUCET REQUIREMENT PER SECTION 11-4.19.5
 - SHOW CONTROL REQUIREMENTS FOR TUB &
 SHOWERS PER 11-4.20.5 (FIG. 11-34) AND
 11-4.21.5 (FIG. 11-37).
 ***NO RESPONSE, NOT ADDRESSED.
  
 17. SHT A.34 PUBLIC TOILETS PROVIDE A
 DETAIL SHOWING COMPLIANCE WITH 11-4.16,
 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SECTION 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
  
 18. SHT P-1 NOTE INDICATES 24 GAUGE
 GALVINIZED PAN ABOVE THE ELECTRICAL
 EQUIPMENT ROOM WITH A 1" DRAIN TO FLOOR
 DRAIN. PER PLUMBING NOTES ON SHT P-12,
 NO WATER, SANITARY, OR DRAINAGE PIPING
 PERMITTED IN ELECTRICAL OR ELEVATOR
 EQUIPMENT ROOMS. (ALSO SEE NEC SECTION
 110.26(F)A.D. - IF SOMEHOW APPROVED, AN
 EXPLANATION WILL BE REQUIRED TO EXPLAIN
 HOW A 1" DRAIN LINE WILL BE ABLE TO
 DRAIN THE 4" SOIL STACK #13, 1" HOT
 WATER & 1-1/4" COLD WATER IF THESE LINES
 HAPPEN TO FAIL. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT PLAN STILL SHOWS
 A 1" DRAIN FROM METAL PAN, AND STILL
 SHOWS STACK 13 9TYPE A) SOIL STACK IN
 THE MAIN ELECTRIC ROOM.
  
 19. SUBMIT A KITCHEN FIXTURE I.D. SHEET
 INDICATING THE LOCATION AND I.D. NUMBER
 FOR EACH FIXTURE. INDICATE ALL SANT.,
 GREASE, GAS, AND WATER SUPPLY PIPE SIZE
 FOR EACH FIXTURE/APPLIANCE. SECTION
 106.3.5.1.3.
 ***RESPONSE NOTED, BUT NO KITCHEN
 FIXTURE ID SHEET SUBMITTED. (SEE SHT
 A-19 FOR ALL KITCHEN FIXTURES).
  
 21. SHT P-4 BATH GROUP "E" ITEM D
 INDIRECT WASTE FROM THE ICE MACHINE NOT
 APPROVED AS SHOWN. SEE ICE MACHINE
 DETAIL SHEET P-14 FOR CORRECT
 INSTALLATION OF THE INDIRECT WASTE.
 SECTIONS 802.3 & 802.3.2. PLEASE CHANGE
 DETAIL ON BATH GROUP "E"
 ***RESONSE NOTED, BUT NO CHANGED NOTED
 ON PLANS
  
 22. SHT P-5 3" RPZV BACKFLOW REQUIRED
 DOWNSTREAM OF THE METERS. SECTIONS 603.1
 FOOTNOTE D, AND608.13.2. - ALSO MAKE
 CHANGE TO WATER ISOMETRIC DIAGRAM ON
 SHEET P-8.
 ***RESPONSE NOTED, BUT DOUBLE CHECK
 VALVES ARE NOT APPROVED. 3" RPCV
 BACKFLOW REQUIRED.
  
 23. SHT P-6 ALL WATER RISER DIAGRAMS,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 CHANGE NOTE 3 OF THE WATER ISOMETRIC
 RISERS NOTES TO REFLECT THIS. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT WATER HAMMER
 ARRESTORS ARE STILL SHOWN IN THE CEILING
 FOR THE SHOWERS AND TUBS.
  
 24. SHT P-7 STACK TYPE "A1" NOTE
 INDICATES A SHOWER FOR THE BATHROOM
 GROUPS, BUT A TUB IS SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE FLOOR PLAN AND
 NOTE. - STACK TYPE "C" A TUB ON THE BATH
 GROUP, BUT ISOMETRIC SHOWS SHOWERS.
 PLEASE CORRELATE. - STACK TYPE "E" SHOWS
 A SAFEWASTE FOR THE INDIRECT WASTE FOR
 THE ICE MAKER. SHEET P-14 SHOWS THE
 CORRECT INDIRECT WASTE ON THE ICE MAKER
 DETAIL. PLEASE CHANGE RISER ISOMETRIC TO
 REFLECT THE ICE MAKER DETAIL FOR
 INDIRECT WASTE. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT STACK A1 NOT
 CHANGED, STACK C SHOULD SHOW 1 TUB & 1
 SHOWER AND FLOOR PLAN ONLY SHOWN ONE
 LAV, AND STACK E REQUIRES A FLOOR SINK,
 NOT A FLOOR DRAIN.
  
 25. SHT P-8 BACKFLOW PROTECTION IS
 REQUIRED FOR SUPPLY LINE TO THE
 FOUNTAIN. PLEASE INDICATE METHOD OF
 BACKFLOW PROTECTION. SECTION 608.
 ***RESPONSE NOTED, BUT DOUBLE CHECK
 VALVES ARE NOT APPROVED.
  
 27. SHT P-13 WATER HEATER DETAIL STATES
 "SEE PROJECT DOCUMENTS AND SPECIFICTION
 FOR ADDITIONAL INFORMATION AND WORK
 REQUIRED FOR A CODE APPROVED AND
 ARCHITECT ACCEPTED INSTALLATION". ALSO
 STATESIN PIPING ARRANGEMENT AT WATER
 HEATERS (E) "REFER TO MANUFACTURE
 RECOMMENDATIONS AND CODE REQUIREMENTS
 FOR INSTALLATIONS AND LOCATIONS OF
 INTAKE AND EXHAUST VENT TERMINALS".
 THESE HAVE NOT BEEN SUBMITTED. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT NO SPECIFICATIONS
 HAVE BEEN LOCATED.
  
 29. SHT P-14 NOTES REFER TO PROJECT
 SPECIFICATIONS THAT WERE NOT SUBMITTED.
 PLEASE SUBMIT ALL REFERENCED
 SPECIFICATIONS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT NO SPECIFICATION
 HAVE BEEN LOCATED.
  
 30. SHT P-14 ICE MACHINE DETAIL.
 SEPARATE DRAIN LINES REQUIRED FOR THE
 ICE CUBER AND THE ICE BIN.
 ***RESPONSE NOTED, BUT DETAIL HAS NOT
 BEEN CHANGED.
  
 31. SHT P-15 GREASE WASTE ISOMETRIC
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 NO LINE TO THE CAN WASH IS SHOWN. P-5
 BEHIND THE ELECTRICAL ROOM IS SHOWN AS A
 FLOOR SINK ON THE FLOOR PLAN AND AS A
 FLOOR DRAIN ON THE RISER DIAGRAM.
 (SHOULD BE A FLOOR SINK ON BOTH) SECTION
 106.1.1. - UNDER GREASE WASTE DIAGRAM
 THE NOTESTATES "SEE KITCHEN DOCUMENTS,
 SPECIFICATIONS, AND DATA SHEETS FOR
 ADDITIONAL INFORMATION AND REQUIREMENTS
 OF PLUMBING WORK ETC.". THESE WERE NOT
 SUBMITTED.
 ***RESPONSE NOTED, BUT NO CHANGES ARE
 SHOWN AND COMMENT HAS NOT BEEN
 ADDRESSED.
  
 32. P-15 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLAN APPROVAL:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT THERE ARE SOME
 CUT SECTIONS THAT DO NOT SHOW THE LENGTH
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES,-
 SPECIFICATIONS NOT SUBMITTED. INDICATE
 IF PIPING WILL BE SCREW PIPE OR WELDED
 PIPE.
 ***RESPONSE NOTED, BUT NO INFORMATION
 FOUND.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC.
 402.4(2). NATURAL GAS SPECIFY .5 PSI OR
 2 PSI.
 ***RESPONSE NOTED, BUT DELIVERY PRESSURE
 HAS NOT BEEN ADDRESSED.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. BYPASS
 PIPING SHALL BE CONNECTED DOWNSTREAM OF
 THE EMERGENCY HOOD SHUT OFF VALVE.
 ***NO RESPONSE, NOT ADDRESSED. EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" PER
 NFPA-96 SECTION 10.5.1 AND NFPA-1
 SECTION 50.4.7.1. INDICATE ON GAS RISER.
  
 *************NEW COMMENT****************
 1B. SHT P-9 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. NEW FLOOR
 PLAN SHOWS THE LAV CHANGED TO THE
 OPPOSITE WALL BY STACK 1 WHERE AS THE
 RISER DOES NOT REFLECT THIS CHANGE. THE
 BATHROOM AT STACK 2 SHOWS A TUB ON THE
 FLOOR PLAN, BUT A SHOWER ON THE RISER
 DIAGRAM. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 RESUBMIT ONE SET OF ORIGINAL SHEETS FOR
 COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved