| Date |
Text |
| 2006-05-03 00:00:00 | DENIED: |
| | RESPONSE TO COMMENT #1 FROM REVIEW DATED |
| | 1-24-06 INDICATES THE OUTDOOR SHAFT WAS |
| | ELIMINATED.RTU #1 SUPPLY AIR FOR THE |
| | COMMON AREA OF FLOORS ONE THROUGH 4. |
| | THIS DUCT SHALL BE BE IN A RATED CHASE |
| | IN ACCORDANCE WITH 2004 FMC 607.6. |
| | |
| | COMMENT #3:RESPONSE INDICATES SUB-DUCT |
| | DETAIL IS NO LONGER ON PLAN SHEET M-11 |
| | BUT IS NOW ON PLAN SHEET M-9, THIS IS |
| | INCORRECT.PLAN SHEET M-9 IS THE FIRE |
| | SUPPRESSION FOR THE GREASE HOOD. |
| | SUB-DUCT IS DETAILED ON PLAN SHEET M-11. |
| | |
| | COMMENT #5:REPONSE INDICATES CHILLED |
| | WATER SYSTEM HAS BEEN ELIMINATED.PLAN |
| | SHEETS M-15, M-16 & DETAIL ON PLAN SHEET |
| | M-14, STILL INDICATE A CHILLED WATER |
| | SYSTEM.PLEASE REMOVE DETAILS AND PLANS |
| | THAT DO NOT PERTAIN TO THIS JOB. |
| | |
| | |
| | NEW COMMENTS: |
| | 1.PLAN SHEET M-1 RETURN AIR FROM THE |
| | MAIN ELECTRICAL ROOM IS MISSING A FIRE |
| | DAMPER/ACCESS DOOR.PLEASE CLARIFY. |
| | |
| | 2.PLEASE CLARIFY PLAN SHEET M-6 & M-8. |
| | PLAN SHEET M-6 APPEARS TO REPLACE M-8. |
| | PLEASE REMOVE ALL PAGES THAT ARE NOT |
| | PERTINENT. |
| | |
| | 3.PLAN SHEET M-6 THE FRESH AIR |
| | CALCULATION INDICATES FRESH PROVIDED |
| | FROM AHU-1 & BY VTAC UNITS.PLEASE |
| | INDICATE WHERE THE VTAC UNITS ARE |
| | LOCATED.PLEASE NOTE THE VTAC UNITS ARE |
| | NOT INDICATED ON THE EQUIPMENT SCHEDULE |
| | OR ON THE PLAN.PLEASE CLARIFY HOW |
| | AHU-1 IS ABLE TO PROVIDE OUTSIDE AIR |
| | WHEN THERE IS NO OUTSIDE AIR DUCTED INTO |
| | AHU-1.IT APPREARS THAT AHU-3, 4, 5 & |
| | POSSIBLY AHU-2 HAVE OUTSIDE AIR PROVIDED |
| | VIA RTU-1.AHU-1, 6, & 7 DO NOT APPEAR |
| | TO HAVE FRESH AIR INTRODUCED INTO THE |
| | SYSTEM. |
| | |
| | ADDITIONAL PERMITS REQUIRED FOR HOOD, |
| | FIRE SUPPRESSION & WALK-IN COOLERS. |
| | HOOD & SUPPRESSION PLANS SUBMITTED WITH |
| | BUILDING PERMIT.PLEASE PROVIDE |
| | MANUFACTURE SUBMITTAL DATA FOR THE |
| | WALK-IN COOLER WITH MECHANICAL PERMIT |
| | APPLICATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |
| | |
| | **************REVIEW IN PROGRESS******* |