2006-05-03 00:00:00DENIED:
 RESPONSE TO COMMENT #1 FROM REVIEW DATED
 1-24-06 INDICATES THE OUTDOOR SHAFT WAS
 ELIMINATED.RTU #1 SUPPLY AIR FOR THE
 COMMON AREA OF FLOORS ONE THROUGH 4.
 THIS DUCT SHALL BE BE IN A RATED CHASE
 IN ACCORDANCE WITH 2004 FMC 607.6.
  
 COMMENT #3:RESPONSE INDICATES SUB-DUCT
 DETAIL IS NO LONGER ON PLAN SHEET M-11
 BUT IS NOW ON PLAN SHEET M-9, THIS IS
 INCORRECT.PLAN SHEET M-9 IS THE FIRE
 SUPPRESSION FOR THE GREASE HOOD.
 SUB-DUCT IS DETAILED ON PLAN SHEET M-11.
  
 COMMENT #5:REPONSE INDICATES CHILLED
 WATER SYSTEM HAS BEEN ELIMINATED.PLAN
 SHEETS M-15, M-16 & DETAIL ON PLAN SHEET
 M-14, STILL INDICATE A CHILLED WATER
 SYSTEM.PLEASE REMOVE DETAILS AND PLANS
 THAT DO NOT PERTAIN TO THIS JOB.
  
  
 NEW COMMENTS:
 1.PLAN SHEET M-1 RETURN AIR FROM THE
 MAIN ELECTRICAL ROOM IS MISSING A FIRE
 DAMPER/ACCESS DOOR.PLEASE CLARIFY.
  
 2.PLEASE CLARIFY PLAN SHEET M-6 & M-8.
 PLAN SHEET M-6 APPEARS TO REPLACE M-8.
 PLEASE REMOVE ALL PAGES THAT ARE NOT
 PERTINENT.
  
 3.PLAN SHEET M-6 THE FRESH AIR
 CALCULATION INDICATES FRESH PROVIDED
 FROM AHU-1 & BY VTAC UNITS.PLEASE
 INDICATE WHERE THE VTAC UNITS ARE
 LOCATED.PLEASE NOTE THE VTAC UNITS ARE
 NOT INDICATED ON THE EQUIPMENT SCHEDULE
 OR ON THE PLAN.PLEASE CLARIFY HOW
 AHU-1 IS ABLE TO PROVIDE OUTSIDE AIR
 WHEN THERE IS NO OUTSIDE AIR DUCTED INTO
 AHU-1.IT APPREARS THAT AHU-3, 4, 5 &
 POSSIBLY AHU-2 HAVE OUTSIDE AIR PROVIDED
 VIA RTU-1.AHU-1, 6, & 7 DO NOT APPEAR
 TO HAVE FRESH AIR INTRODUCED INTO THE
 SYSTEM.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION & WALK-IN COOLERS.
 HOOD & SUPPRESSION PLANS SUBMITTED WITH
 BUILDING PERMIT.PLEASE PROVIDE
 MANUFACTURE SUBMITTAL DATA FOR THE
 WALK-IN COOLER WITH MECHANICAL PERMIT
 APPLICATION.
  