Plan Review Notes
Plan Review Notes For Permit 05110263
Permit Number 05110263
Review Stop G
Sequence Number 2
Notes
Date Text
2006-07-05 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 32. P-15 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLAN APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT THERE ARE SOME
 CUT SECTIONS THAT DO NOT SHOW THE
 LENGTH.
 ****RESPONSE NOTED, BUT THERE IS NO
 LENGTHS FOR THE PIPING TO THE POOL/SPA
 HEATERS. THERE ARE 3 WATER HEATERS
 INDICATED, BUT ONLY TWO SHOWN ON THE
 ISOMETRIC RISER DIAGRAM. PLEASE
 CORRELATE THE APPLIANCES WITH THE RISER
 DIAGRAM.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT MANUF.
 SPECIFICATION SHEET ARE REQUIRED FOR ALL
 GAS APPLIANCES.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. BYPASS
 PIPING SHALL BE CONNECTED DOWNSTREAM OF
 THE EMERGENCY HOOD SHUT OFF VALVE.
 ***NO RESPONSE, NOT ADDRESSED. EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" PER
 NFPA-96 SECTION 10.5.1 AND NFPA-1
 SECTION 50.4.7.1. INDICATE ON GAS RISER.
 ****RESPONSE NOTED, BUT NO MANUAL GAS
 SHUT OFF VALVE IS SHOWN ON RISER
 DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]