| 2006-05-05 00:00:00 | ******DENIED****** |
| | |
| | PLEASE BE ADVISED THAT RESPONSES HAVE |
| | BEEN PROVIDED, HOWEVER SOME ADDITIONS, |
| | DELETIONS OR CHANGES ARE NOT ILLUSTRATED |
| | ON THE PLANS. |
| | |
| | 1) COMMENT 5- RESPONSE STATES THAT A 2ND |
| | FIRE HYDRANT IS SHOWN ON FP-16. ONLY (8) |
| | FP SHEETS HAVE BEEN SUBMITTED. |
| | |
| | 2) COMMENT 7- RESPONSE REFERS TO A.20, |
| | HOWEVER NO SUCH NOTE WAS FOUND. |
| | |
| | 3) COMMENT 11- CERTIFICATION OR APPROVED |
| | COPY OF CERTIFICATE SHALL BE AVAILABLE |
| | PRIOR TO OR AT THE TIME OF THE FIRE |
| | ALARM FINAL. |
| | |
| | 4) COMMENT 13- PLEASE PROVIDE NOTE TO |
| | DRAWINGS. |
| | |
| | 5) COMMENT 15- PLEASE ADD ADDRESS NOTE |
| | TO ELEVATIONS. |
| | |
| | 6) COMMENT 18- PLEASE NOTE THAT |
| | INCORRECT CHAPTER IS STILL REFERENCED ON |
| | A.20. PLEASE MAKE CORRECTION. |
| | |
| | 7) COMMENT 20- PLEASE PROVIDE NOTE TO |
| | PLANS. NO SUCH NOTE WAS FOUND ON A.25. |
| | |
| | 8) COMMENT 24- RESPONSE INDICATES THAT |
| | THE FIRE DEPARTMENT CONNECTION |
| | ARRANGEMENT ON DCDA WAS ELEIMINATED. |
| | THIS ARRANGEMENT IS STILL BEING SHOWN ON |
| | FP-6. |
| | |
| | 9) COMMENT 27- PLEASE BE AWARE THAT FIRE |
| | SPRINKLER COVERAGE SHALL BE IN |
| | ACCORDANCE WITH NFPA 13. IF SUCH AN |
| | EXCEPTION EXISTS, PLEASE PROVIDE WITH |
| | RESPONSE INDICATING THAT SECTION. |
| | |
| | 10) COMMENT 33- PLEASE NOTE THAT A |
| | DIMENSION OF 13'-6" WAS NOT FOUND ON |
| | A.24. |
| | |
| | |
| | PLEASE BE SURE WHEN RESUBMITTING, TO |
| | REFLECT ANY CHANGES TO PLANS THAT |
| | CORRULATE WITH APPROPRIATE RESPONSE. |
| | THIS WILL ASSIST IN EXPEDITING THIS |
| | PROCESS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |