Plan Review Notes
Plan Review Notes For Permit 05110263
Permit Number 05110263
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-14 00:00:00************ UNSAT 2ND REVIEW *********
  
 HILTON GARDENS INN
  
 ** PLEASE KNOW, PLANS TO DATE HAVE STILL
 NOT BEEN SUBMITTED FOR PERMIT FOR
 BUILDING AND PLANS ARE ONLY SUBMITTED
 FOR "PLAN REVIEW".
  
 ** PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEW WHICH ARE IN NEED OF BEING
 ADDRESSED AND SOME NEW NOTES FOR ITEMS
 CHANGED AND/OR NOW SUBMITTED FOR REVIEW>
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
 1A) NOTE: NO, PLEASE SEE NO INFORMATION
 WAS SUBMITTED AND NO CHANGES OR
 ADJUSTMENTS COULD BE LOCATED ON PLANS
 FOR COMPLIANCE TO THE 2004 FBC CHAPTER
 13. 13-413.1ABC.1.1,13-415.1.ABC.1.1,
 13-415.1.ABC.1.2,13-415.1.ABC.1.4 ETC.
 PLEAS KNOW, IN THE RESPONSE PACKAGE FROM
 DESIGN PROFESSIONALNO RESPONSE WAS
 INDICATED.
  
 ** PREVIOUS NOTE**
 PLEASE SEE 2004 FCB CHAPTER 13
 HOTELS, ROOM OCCUPANCY CONTROLS FOR AND
 OTHER CONTROL FOR COMMON AREAS.
  
  
  
 1)NOTE: NO, PLEASE SEE THESE COULD NOT
 BE LOCATED ON PLANS FOR ADDED CODES AND
 RESPONSE LETTER DOES NOT RESPONSED TO
 THIS NOTE.
  
 ** PREVIOUS NOTE**
 PLEASE BE SURE PLANS REFERENCE
 CURRENT CODES IN EFFECT.
 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002
 NFPA-72 ETC
  
 2)NOTE:OK, HOWEVER PLEASE SEE
 ARCHITECTURAL PLANS DO NOT CORRELATE
 WITH DOOR SWINGS AND PLEASE ALSO SEE
 POSSIBLE CONFLICT WIHT THE SWING OF
 OTHER DOOR ON PLANS. PLEASE SEE IF ONE
 DOOR IS BEING OPENED AND THE SINGLE DOOR
 FROM MAIN ELECTRICAL ROOM ALSO OPENS
 THESE WILL INTERSECT IN THE CENTER OF
 HALL EGRESS AREA. PLEASE SEE DOOR
 HINGE/SWING SIDE MAY NEED TO BE REVERSED
 TO AVOIDE THIS INTERFERENCE.
  
 ** PREVVIOUS NOTE **
 PLEASE SEE MAIN ELECTRICAL ROOM
 DOORS WILL BE REQUIRED TO OPEN OUTWARD
 AND SHALL HAVE PANIC HARDWARE.
 110.26
  
 3)NOTE:OK, HOWEVER SEE NEW NOTES FOR
 CORRELATION OF FIXTURES ETC.
  
 ** PREVIOUS NOTE**
 PLEASE BE SURE ALL ELECTRICAL RMS,
 ELEVATOR EQUIPMENT RMS CONTAIN A
 BATTERY BACK UP LIGHT OF SOME SORT.
 LS101 7.8,7.9, 700.16
  
 4)NOTE: OK.
  
  
 5)NOTE: OK.
  
 6)NOTE:NO, PLEASE SEE SOME AREAS/ITEMS
 ON PLANS ARE REDLINED WHERE FIXTURES AND
 EQUIPMENT IS NOT CIRCUITED. PLEASE ALSO
 PLEASE SEE GUEST ROOMS DO NOT INDICATE
 THE CIRCUITING. PLEASE SEE RESPONSE LTR
 MENTIONS THESE WERE ALL DONE, HOWEVER
 PLEASE SEE PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE ALL OTHER CIRCUITING,
 GUEST RMS ETC. 215.5
  
 7)NOTE: OK.
  
 8)NOTE: OK.
  
 9)NOTE:OK, HOWEVER PLEASE SEE
 DESCREPANCIES IN THE PHOTO-METRICS, AND
 FIXTURE TYPES. PLEASE SEE THE
 PHOTO-METRICS SEEM TO BE REVERSED, THE
 LEVEL OF LIGHTING UNDER NORMAL LIGHTING
 CONDITION IS LOWER THAN UNDER EMERGENCY?
 PLEASE SEE PERHAPS EACH SUDY WAS
 REVERSED IN LABLEING?
 PLEASE ALSO CORRELATE STAIR AREAS AND
 FIXTURE TYOE WITH FIXTURES LISTED ON
 FIXTURE SCHEDULE. PLEASE SEE FIXTURE
 SCHEDULE AND ORIGINAL PLANS FOR LIGHTING
 ON EACH FLR INDICATES A FIXTURE "H".THIS
 FIXTURE IS SHOWN AS WALL MOUNTED AND
 MENTIONED AS CEILING MOUNTED ON
 SCHEDULE?
 PLEASE CORRELATE.
  
 ** PREVIOUS NOTE**
 PLEASE SUBMIT COMPLETE PHOTOMETRICS FOR
 ALL COMMON AREAS, AND STAIR TOWERS.
 PLEASE SEE 2003 NFPA-1017.8.1.3 WHICH
 REQUIRES A MIN OF 1 FT CANDLEAND A MIN
 OF 10FT CANDLES ON THE WALKING SURFACE
 UNDER NORMAL POWER. PLEASE SEE7.9.2.1
 WHICH REQUIRES A MIN OF 1FT CANDLE OF
 LIGHTING ON ALL WALKING SURFACES UNDER
 EMERGENCY CONDITIONS.
  
 10)NOTE: NO, PLEASE SEE RESPONSE LTR
 MENTIONS TO SEE ARCHITECTURAL PLANS,
 HOWEVER NONE OF THE A-SHEETS CONTAIN THE
 INFORMATION NEED AND REQUESTED.
  
 ** PREVIOUS REVIEW **
 PLEASE SEE PHOTOMETRICS SHOWN
 FOR POOL AREA SHALL BE SUBMITTED TO PALM
 BEACH COUNTY HEATH DEPARTMENT FOR ANY
 AFTER DUSK SWIMMMING.
 IF THERE IS NOT GOING TO BE ANY SWIMMING
 FROM DUSK TO DAWN, PLEASE PROVIDE A NOTE
 ON PLAN FOR REQUIRED SIGNAGE TO BE PLACE
 AT AND IN POOL AREA.
 ** PLEASE KNOW, THE SWIMMING POOL ITSELF
 WILL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT.
  
 11)NOTE:NO, SAME NOTE. SEE CIRCUITING
 NOTE.
 RESPONSE LTR MENTIONS TO SEE ROOM TYOE
 ADDED?? THIS DOES NOT CORRELATE FOR THE
 COMMENT WHICH WAS MADE.
  
 ** PREVIOUS NOTE **
 PLEASE CLARIFY NOTE ON PLANS FOR THE
 REQUIREMENTS OF GUEST BATH GFI.
 THIS CAN NOT BE VERIFIED AT THIS TIME
 DUE TO MISSING CIRCUITING.
  
 12)NOTE: OK.
  
 13)NOTE: NO, PLEASE SEE LTTR MENTIONS NO
 PROTECTION PER OWNER? PLEASE SEE
 PREVIOUS NOTE:::
  
 ** PREVIOUS NOTE**
 PLEASE PROVIDE A NOTE ON THE ROOOFTOP
 PLAN WHICH SHOULD NOTE/MENTION:
 ANY PROPOSED LIGHTNING PROTECTION SYSTEM
 SHALL MEET NFPA-780, OR WORDS TO THAT
 AFFECT.
 IT IS NOTED THAT NO SYSTEM IS SHOWN AT
 THIS TIME, AND ANY FUTURE WOULD BE UNDER
 A SEPARATE PERMIT, HOWEVER A NOTE IS
 REQUIRED AT THIS TIME.
  
 14)NOTE: OK.
  
 15)NOTE: OK.
  
 16)NOTE: OK.
  
 17)NOTE:OK, HOWEVER PLEASE SEE WHAT
 APPEARS TO BE A MISPRINT FOR 3RD FLR
 PANEL "3R3" WHICH READS "2R3"
  
 ** PREVIOUS NOTE**
 PLEASE SEE RISER AND MSB SHOWS ALL 1H1,
 2H2, 3H3 ETC AS 1H, 2H, 3H ETC ON PANEL
 SCHEDULES FOR THESE.
 PLEASE CORRELATE THE IDENTIFICATION OF
 THESE.
 215.5
  
 18)NOTE: NO, PLEASE SEE RESPONSE
 MENTIONS "800A CHILLER HAS BEEN
 ELIMINATED" ETC, PLEASE KNOW, THIS
 RESPONSE WAS NOT FOR COMMENT MADE?
 PLEASE SEE RISER AND NEW LOAD
 CALCULATIONS NOW SUBMITTED. PLEASE SEE
 NOTE #2 ON RISER WAS ADDRESSED IN FEEDER
 SCHEDULE, HOWEVER SAME SHEET STILL
 MENTIONS CONDUITRS, AND CONDUCTORS NOT
 RATED FOR THE 3000A MAIN BEING ISTALLED.
 PLEASE SEEREDLINED PLANS.
  
 **PREVIOUS NOTE **
 PLEASE SEE 240.4C, WHICH REQUIRES THE
 CONDUCTOR FEEDING DEVICES RATED OVER
 800A'S TO MEET OR EXCEED RAITNG OF SUCH
 DEVICE.
 PLEASE SEE MSB OS SHOWN AS A 3000A MAIN
 , HOWEVER CONDUCTORS ARE ONLY RATED FOR
 2100 A'S?
 5-SETS OF 600MCM, RATED @420A'S EACH.(75
 DEGREE COL).
 110.14, 215.5,215.3
 PLEASE ADJUST ON MORE THAN ONE SHEET,
 SEE 13,14.
  
 19)NOTE: OK, CHILLER REMOVED, HOWEVER
 PLEASE SEE PLANS NOW INDICATE NEW CU'S
 LOCATED ON SITE WITHOUT SERVICE RECEPTS
 210.63 AND PLEASE SEE MECH PLANS
 INDICATE "P-TAC" UNITS AT THE END OF
 THE HALLS FOR EACH FLR, HOWEVER THESE
 ARE NOT SHOWN ON ELECTRICAL PLANS ,
 HOWEVER THEY ARE INDICATED ON PANEL
 SCHEDULES.??
  
 **PREVIOUS NOTE**
 PLEASE ALSO SEE CONDUCTORS FOR MAIN
 FEEDERS TO CHILLER FROM MSB.
 PLEASE SEE MSB SHOWS 3-300 MCM, HOWEVER
 PLEASE SEE CALCUALTIONS FOR CHILLER
 WHICH INDICATE 2-600'S.
 PLEASE CORRELARE. 215.5
  
 20)NOTE: NO, PLEASE SEE RESPONSE LTR
 MENTIONS TO SEE REVISED DETAIL, HOWEVER
 DETAIL WAS NOT REVISED AND SHOW THE
 SAME.
  
 ** PREVIOUS **
 PLEASE SEE RISER INDICATES "BLDG STEEL"
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM, WHICHIS OK AND IS REQUIRED IF
 "BLDG STEEL" IS PRESENT.
 PLEASE ALSO INCLUDE THE REQUIRED "FOOTER
 STEEL" IN DETAIL.
 250.50
  
 21)NOTE: NO?? RESPONSE MENTIONS
 "INFORMATION TO FOLLOW" , WHAT IS MEANT
 BY THIS??????
 PLEASE KNOW, THIS INFORMATION IS NEEDED
 AND REQUIRED ATTHIS TIME AND SHALL BE
 ON PLANS BEFORE PERMITTING.
  
 ** PREVIOUS NOTE**
 PLEASE KNOW, THE REQUIRED WIND LOAD
 CALCULATIONS FOR LT POLES WITH FIXTURES
 ON THEM ARE REQUIRED AT THIS TIME.
 PLEASE KNOW, THESE WILL BE REVIEWED BY A
 STRUCTUAL PLANS REVIEWER.
 IF THIS INFORMATION IS NOT SUBMITTED AT
 THIS TIME, ALL SITE LIGHTING WOULD BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT,
 WITH SEPARATE PLANS AND FEES.
  
  
 ** PLEASE KNOW, ONE SET OF PLANS ARE
 BEING RETAINED FOR FILE AND RECORD OF
 PLAN REVIEWS FOR REPEAT COMMENTS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE SEE ONE SET OF ELECTRICAL
 PLANS HAVE MANY OF THE ABOVE ITMES
 REDLINED IN LOCATIONS FOR NOTES.
 IE,FLR ELEC RMS, RECEPTS ETC.
  
 **BEFORE RESUBMITTING PLANS, PLEASE
 REMOVE ALL OLD/VOIDED ELECTRICAL PAGES
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
 19)NOTE: PLEAS
2006-04-13 00:00:00IN ELEC FOR REVIEW.