| 2006-04-14 00:00:00 | ************ UNSAT 2ND REVIEW ********* |
| | |
| | HILTON GARDENS INN |
| | |
| | ** PLEASE KNOW, PLANS TO DATE HAVE STILL |
| | NOT BEEN SUBMITTED FOR PERMIT FOR |
| | BUILDING AND PLANS ARE ONLY SUBMITTED |
| | FOR "PLAN REVIEW". |
| | |
| | ** PLEASE SEE MANY NOTES FROM PREVIOUS |
| | REVIEW WHICH ARE IN NEED OF BEING |
| | ADDRESSED AND SOME NEW NOTES FOR ITEMS |
| | CHANGED AND/OR NOW SUBMITTED FOR REVIEW> |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | |
| | 1A) NOTE: NO, PLEASE SEE NO INFORMATION |
| | WAS SUBMITTED AND NO CHANGES OR |
| | ADJUSTMENTS COULD BE LOCATED ON PLANS |
| | FOR COMPLIANCE TO THE 2004 FBC CHAPTER |
| | 13. 13-413.1ABC.1.1,13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2,13-415.1.ABC.1.4 ETC. |
| | PLEAS KNOW, IN THE RESPONSE PACKAGE FROM |
| | DESIGN PROFESSIONALNO RESPONSE WAS |
| | INDICATED. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE 2004 FCB CHAPTER 13 |
| | HOTELS, ROOM OCCUPANCY CONTROLS FOR AND |
| | OTHER CONTROL FOR COMMON AREAS. |
| | |
| | |
| | |
| | 1)NOTE: NO, PLEASE SEE THESE COULD NOT |
| | BE LOCATED ON PLANS FOR ADDED CODES AND |
| | RESPONSE LETTER DOES NOT RESPONSED TO |
| | THIS NOTE. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE BE SURE PLANS REFERENCE |
| | CURRENT CODES IN EFFECT. |
| | 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002 |
| | NFPA-72 ETC |
| | |
| | 2)NOTE:OK, HOWEVER PLEASE SEE |
| | ARCHITECTURAL PLANS DO NOT CORRELATE |
| | WITH DOOR SWINGS AND PLEASE ALSO SEE |
| | POSSIBLE CONFLICT WIHT THE SWING OF |
| | OTHER DOOR ON PLANS. PLEASE SEE IF ONE |
| | DOOR IS BEING OPENED AND THE SINGLE DOOR |
| | FROM MAIN ELECTRICAL ROOM ALSO OPENS |
| | THESE WILL INTERSECT IN THE CENTER OF |
| | HALL EGRESS AREA. PLEASE SEE DOOR |
| | HINGE/SWING SIDE MAY NEED TO BE REVERSED |
| | TO AVOIDE THIS INTERFERENCE. |
| | |
| | ** PREVVIOUS NOTE ** |
| | PLEASE SEE MAIN ELECTRICAL ROOM |
| | DOORS WILL BE REQUIRED TO OPEN OUTWARD |
| | AND SHALL HAVE PANIC HARDWARE. |
| | 110.26 |
| | |
| | 3)NOTE:OK, HOWEVER SEE NEW NOTES FOR |
| | CORRELATION OF FIXTURES ETC. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE BE SURE ALL ELECTRICAL RMS, |
| | ELEVATOR EQUIPMENT RMS CONTAIN A |
| | BATTERY BACK UP LIGHT OF SOME SORT. |
| | LS101 7.8,7.9, 700.16 |
| | |
| | 4)NOTE: OK. |
| | |
| | |
| | 5)NOTE: OK. |
| | |
| | 6)NOTE:NO, PLEASE SEE SOME AREAS/ITEMS |
| | ON PLANS ARE REDLINED WHERE FIXTURES AND |
| | EQUIPMENT IS NOT CIRCUITED. PLEASE ALSO |
| | PLEASE SEE GUEST ROOMS DO NOT INDICATE |
| | THE CIRCUITING. PLEASE SEE RESPONSE LTR |
| | MENTIONS THESE WERE ALL DONE, HOWEVER |
| | PLEASE SEE PLANS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE COMPLETE ALL OTHER CIRCUITING, |
| | GUEST RMS ETC. 215.5 |
| | |
| | 7)NOTE: OK. |
| | |
| | 8)NOTE: OK. |
| | |
| | 9)NOTE:OK, HOWEVER PLEASE SEE |
| | DESCREPANCIES IN THE PHOTO-METRICS, AND |
| | FIXTURE TYPES. PLEASE SEE THE |
| | PHOTO-METRICS SEEM TO BE REVERSED, THE |
| | LEVEL OF LIGHTING UNDER NORMAL LIGHTING |
| | CONDITION IS LOWER THAN UNDER EMERGENCY? |
| | PLEASE SEE PERHAPS EACH SUDY WAS |
| | REVERSED IN LABLEING? |
| | PLEASE ALSO CORRELATE STAIR AREAS AND |
| | FIXTURE TYOE WITH FIXTURES LISTED ON |
| | FIXTURE SCHEDULE. PLEASE SEE FIXTURE |
| | SCHEDULE AND ORIGINAL PLANS FOR LIGHTING |
| | ON EACH FLR INDICATES A FIXTURE "H".THIS |
| | FIXTURE IS SHOWN AS WALL MOUNTED AND |
| | MENTIONED AS CEILING MOUNTED ON |
| | SCHEDULE? |
| | PLEASE CORRELATE. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SUBMIT COMPLETE PHOTOMETRICS FOR |
| | ALL COMMON AREAS, AND STAIR TOWERS. |
| | PLEASE SEE 2003 NFPA-1017.8.1.3 WHICH |
| | REQUIRES A MIN OF 1 FT CANDLEAND A MIN |
| | OF 10FT CANDLES ON THE WALKING SURFACE |
| | UNDER NORMAL POWER. PLEASE SEE7.9.2.1 |
| | WHICH REQUIRES A MIN OF 1FT CANDLE OF |
| | LIGHTING ON ALL WALKING SURFACES UNDER |
| | EMERGENCY CONDITIONS. |
| | |
| | 10)NOTE: NO, PLEASE SEE RESPONSE LTR |
| | MENTIONS TO SEE ARCHITECTURAL PLANS, |
| | HOWEVER NONE OF THE A-SHEETS CONTAIN THE |
| | INFORMATION NEED AND REQUESTED. |
| | |
| | ** PREVIOUS REVIEW ** |
| | PLEASE SEE PHOTOMETRICS SHOWN |
| | FOR POOL AREA SHALL BE SUBMITTED TO PALM |
| | BEACH COUNTY HEATH DEPARTMENT FOR ANY |
| | AFTER DUSK SWIMMMING. |
| | IF THERE IS NOT GOING TO BE ANY SWIMMING |
| | FROM DUSK TO DAWN, PLEASE PROVIDE A NOTE |
| | ON PLAN FOR REQUIRED SIGNAGE TO BE PLACE |
| | AT AND IN POOL AREA. |
| | ** PLEASE KNOW, THE SWIMMING POOL ITSELF |
| | WILL BE REQUIRED TO BE UNDER A SEPARATE |
| | PERMIT. |
| | |
| | 11)NOTE:NO, SAME NOTE. SEE CIRCUITING |
| | NOTE. |
| | RESPONSE LTR MENTIONS TO SEE ROOM TYOE |
| | ADDED?? THIS DOES NOT CORRELATE FOR THE |
| | COMMENT WHICH WAS MADE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE CLARIFY NOTE ON PLANS FOR THE |
| | REQUIREMENTS OF GUEST BATH GFI. |
| | THIS CAN NOT BE VERIFIED AT THIS TIME |
| | DUE TO MISSING CIRCUITING. |
| | |
| | 12)NOTE: OK. |
| | |
| | 13)NOTE: NO, PLEASE SEE LTTR MENTIONS NO |
| | PROTECTION PER OWNER? PLEASE SEE |
| | PREVIOUS NOTE::: |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE PROVIDE A NOTE ON THE ROOOFTOP |
| | PLAN WHICH SHOULD NOTE/MENTION: |
| | ANY PROPOSED LIGHTNING PROTECTION SYSTEM |
| | SHALL MEET NFPA-780, OR WORDS TO THAT |
| | AFFECT. |
| | IT IS NOTED THAT NO SYSTEM IS SHOWN AT |
| | THIS TIME, AND ANY FUTURE WOULD BE UNDER |
| | A SEPARATE PERMIT, HOWEVER A NOTE IS |
| | REQUIRED AT THIS TIME. |
| | |
| | 14)NOTE: OK. |
| | |
| | 15)NOTE: OK. |
| | |
| | 16)NOTE: OK. |
| | |
| | 17)NOTE:OK, HOWEVER PLEASE SEE WHAT |
| | APPEARS TO BE A MISPRINT FOR 3RD FLR |
| | PANEL "3R3" WHICH READS "2R3" |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE RISER AND MSB SHOWS ALL 1H1, |
| | 2H2, 3H3 ETC AS 1H, 2H, 3H ETC ON PANEL |
| | SCHEDULES FOR THESE. |
| | PLEASE CORRELATE THE IDENTIFICATION OF |
| | THESE. |
| | 215.5 |
| | |
| | 18)NOTE: NO, PLEASE SEE RESPONSE |
| | MENTIONS "800A CHILLER HAS BEEN |
| | ELIMINATED" ETC, PLEASE KNOW, THIS |
| | RESPONSE WAS NOT FOR COMMENT MADE? |
| | PLEASE SEE RISER AND NEW LOAD |
| | CALCULATIONS NOW SUBMITTED. PLEASE SEE |
| | NOTE #2 ON RISER WAS ADDRESSED IN FEEDER |
| | SCHEDULE, HOWEVER SAME SHEET STILL |
| | MENTIONS CONDUITRS, AND CONDUCTORS NOT |
| | RATED FOR THE 3000A MAIN BEING ISTALLED. |
| | PLEASE SEEREDLINED PLANS. |
| | |
| | **PREVIOUS NOTE ** |
| | PLEASE SEE 240.4C, WHICH REQUIRES THE |
| | CONDUCTOR FEEDING DEVICES RATED OVER |
| | 800A'S TO MEET OR EXCEED RAITNG OF SUCH |
| | DEVICE. |
| | PLEASE SEE MSB OS SHOWN AS A 3000A MAIN |
| | , HOWEVER CONDUCTORS ARE ONLY RATED FOR |
| | 2100 A'S? |
| | 5-SETS OF 600MCM, RATED @420A'S EACH.(75 |
| | DEGREE COL). |
| | 110.14, 215.5,215.3 |
| | PLEASE ADJUST ON MORE THAN ONE SHEET, |
| | SEE 13,14. |
| | |
| | 19)NOTE: OK, CHILLER REMOVED, HOWEVER |
| | PLEASE SEE PLANS NOW INDICATE NEW CU'S |
| | LOCATED ON SITE WITHOUT SERVICE RECEPTS |
| | 210.63 AND PLEASE SEE MECH PLANS |
| | INDICATE "P-TAC" UNITS AT THE END OF |
| | THE HALLS FOR EACH FLR, HOWEVER THESE |
| | ARE NOT SHOWN ON ELECTRICAL PLANS , |
| | HOWEVER THEY ARE INDICATED ON PANEL |
| | SCHEDULES.?? |
| | |
| | **PREVIOUS NOTE** |
| | PLEASE ALSO SEE CONDUCTORS FOR MAIN |
| | FEEDERS TO CHILLER FROM MSB. |
| | PLEASE SEE MSB SHOWS 3-300 MCM, HOWEVER |
| | PLEASE SEE CALCUALTIONS FOR CHILLER |
| | WHICH INDICATE 2-600'S. |
| | PLEASE CORRELARE. 215.5 |
| | |
| | 20)NOTE: NO, PLEASE SEE RESPONSE LTR |
| | MENTIONS TO SEE REVISED DETAIL, HOWEVER |
| | DETAIL WAS NOT REVISED AND SHOW THE |
| | SAME. |
| | |
| | ** PREVIOUS ** |
| | PLEASE SEE RISER INDICATES "BLDG STEEL" |
| | AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM, WHICHIS OK AND IS REQUIRED IF |
| | "BLDG STEEL" IS PRESENT. |
| | PLEASE ALSO INCLUDE THE REQUIRED "FOOTER |
| | STEEL" IN DETAIL. |
| | 250.50 |
| | |
| | 21)NOTE: NO?? RESPONSE MENTIONS |
| | "INFORMATION TO FOLLOW" , WHAT IS MEANT |
| | BY THIS?????? |
| | PLEASE KNOW, THIS INFORMATION IS NEEDED |
| | AND REQUIRED ATTHIS TIME AND SHALL BE |
| | ON PLANS BEFORE PERMITTING. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE KNOW, THE REQUIRED WIND LOAD |
| | CALCULATIONS FOR LT POLES WITH FIXTURES |
| | ON THEM ARE REQUIRED AT THIS TIME. |
| | PLEASE KNOW, THESE WILL BE REVIEWED BY A |
| | STRUCTUAL PLANS REVIEWER. |
| | IF THIS INFORMATION IS NOT SUBMITTED AT |
| | THIS TIME, ALL SITE LIGHTING WOULD BE |
| | REQUIRED TO BE UNDER A SEPARATE PERMIT, |
| | WITH SEPARATE PLANS AND FEES. |
| | |
| | |
| | ** PLEASE KNOW, ONE SET OF PLANS ARE |
| | BEING RETAINED FOR FILE AND RECORD OF |
| | PLAN REVIEWS FOR REPEAT COMMENTS. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE SEE ONE SET OF ELECTRICAL |
| | PLANS HAVE MANY OF THE ABOVE ITMES |
| | REDLINED IN LOCATIONS FOR NOTES. |
| | IE,FLR ELEC RMS, RECEPTS ETC. |
| | |
| | **BEFORE RESUBMITTING PLANS, PLEASE |
| | REMOVE ALL OLD/VOIDED ELECTRICAL PAGES |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | 19)NOTE: PLEAS |
| 2006-04-13 00:00:00 | IN ELEC FOR REVIEW. |