| 2006-04-13 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05110263 |
| | ADD: LOT# 7 CENTERPARK WEST |
| | CONT: "PLAN REVIEW" HILTON |
| | JOHN COSTAS |
| | TEL: (561)523-3699 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | ***IMPORTANT*** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | NOTE NOC WILL BE NULL & VOID 90 DAYS |
| | AFTER RECORDING AT THE CLERK OF THE |
| | COURTS OFFICE IF WORK HAS NOT STARTED. |
| | FL S S 713.13(2). |
| | |
| | 2) 2ND REQUEST FOR THIS INFORMATION, |
| | RESPONCE INDICATED A PERMIT 06011019 |
| | SUPPLIED THIS INFORMATION. THIS PERMIT |
| | IS A SITE PREP PERMIT. |
| | A FOUNDATION PERMIT WAS APPLIED FOR |
| | UNDER 06011052. |
| | BOTH THE S0.1 & S1.1 HAVE NOTES |
| | ABOUT THE SOILS AND FOUNDATION BUT THE |
| | ENGINEER DOESN'T STATE WHAT THE SAFE |
| | MINIMUM DESIGN FOR THE FOUNDATION WAS |
| | DESIGNED TO? |
| | THIS IS A STAND ALONE PERMIT |
| | REQUESTING (3) SIGNED/SEALED SOILS |
| | REPORTS AS PER, |
| | FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 3) COMMENT# 3 FROM THE PREVIOUS REVIEW, |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 4)COMPLIED. |
| | |
| | 5)COMPLIED, HAROLD PISKURA, HAS THE |
| | NECESSARY DOCUMENTS. |
| | |
| | 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS |
| | FOR THE BUILDING WHICH ARE REQUIRED TO |
| | BE SIGNED AND SEALED BY THE ARCHITECT OR |
| | ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR |
| | ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | THIS STATEMENT IS FOUND ON THE |
| | STRUCTURAL SHEETS BUT NOT THE |
| | ARCHITECTURAL SHEETS. |
| | |
| | 7A)COMPLIED. |
| | |
| | 7B)2ND REQUEST, A SITE PLAN WAS |
| | SUBMITTED ONLY, THIS REQUEST IS MADE AS |
| | REQUEST (7D) TO DETERMINE LOT LINE, AND |
| | TABLE 503, TABLE 601 ISSUES, PLANS DO |
| | NOT PROVIDE MINIMUM BLDG TYPE! |
| | PROVIDE A COPY OF THE NEW PLAT, SHEET |
| | SP.01 APPEARS TO HAVE BEEN SUBDIVIDED |
| | WITH ADDITIONAL BUILDINGS TO BE ON THE |
| | SAME LOT. |
| | |
| | 7C)NOTE, TO BE COMPLETED AT TIME OF |
| | PERMIT APPLICATION. PLEASE FILL OUT AN |
| | ACTUAL APPLICATION SHEET PROVIDING THE |
| | PROPERTY |
| | CONTROL NUMBER FOR ADDRESSING. |
| | |
| | 7D)2ND REQUEST,SAME AS ISSUES AS 7B, |
| | PROVIDE A SURVEY OF THE SITE. |
| | |
| | 8) 2ND REQUEST,ADDITIONAL INFORMATION |
| | REQUIRED FOR |
| | RECORD KEEPING PURPOSES 106.1.2*: |
| | 8)A) FLOOD ZONE |
| | 8)B) FLOOD ELEVATION (IF A ZONE) |
| | 8)C) LOMAR (IF A ZONE) |
| | 8)D) COMPLIED |
| | 8)E) COMPLIED |
| | 8)F)COMPLIED |
| | 8)G)COMPLIED |
| | 8)H)COMPLIED |
| | 8)I) COMPLIED |
| | 8)J) COMPLIED |
| | 8)K) COMPLIED |
| | |
| | 9)THIS COMMENT WILL STAY UNTIL A |
| | CONTRACTOR IS SIGNED ON AND ACKNOWLEDGES |
| | STATEMENT. |
| | 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 10) WILL REMAIN UNTIL ALL PERTINENT |
| | INFORMATION REQUIRED FOR PERMIT HAS BEEN |
| | REVIEWED, |
| | SINCE THISWILL BE A THRESHOLD |
| | PROJECT (3) SETS OF ALL INFORMATION |
| | SUBMITTED WILL BE REQUIRED. |
| | |
| | 11)2ND REQUEST, 1609.1.4 PROTECTION OF |
| | OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | |
| | 12)2ND REQUEST, NONE OF THE PRODUCT |
| | APPROVALS SUBMITTED HAVE FLORIDA |
| | COVERSHEETS, |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 13) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS MISSING FL COVERSHEET |
| | SHEET |
| | B) EXTERIOR DOORS, SOLID MISSING FL |
| | COVER SHEET |
| | C) EXTERIOR DOORS GLAZED NOT SUBMITED |
| | D) EXTERIOR DOORS BYPASS, EXTERIOR AUTO |
| | SLIDERS, USUALLY TRANSOM NOT INCLUDED |
| | E) MULLIONS- NOT SUBMITTED- HORIZONTAL |
| | TO SEPERATE THE AUTO SLIDERS FROM FIXED |
| | STOREFRONT |
| | F) LOUVERS NOT SUBMITTED |
| | G) TRUSS ANCHORS NOT SUBMITTED |
| | H1) ROOF ASSEMBLIES, FLAT ROOF: |
| | ) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | |
| | ROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED.HIGHLIGHT THE ACTUALL |
| | SUBSYSTEM AND ANY OPTIONS AS FASTENER |
| | TYPES! |
| | |
| | _X THIS MAY BE THE SITUATION SINCE NO |
| | SYSTEM WAS HIGHLIGHTED,__ THE SYSTEM |
| | PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ___ . |
| | |
| | ___ THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | H2) ROOF TILE OR SHINGLES NOT SUBMITTED |
| | I) PREMANUFACTURED A/C STANDS NOT |
| | SUBMITTED |
| | |
| | 14)2ND REQUEST REVERTS BACK TO 13E: |
| | 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 15) 2ND REQUEST REVERTS BACK TO 13E: |
| | 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 16) 2ND REQUEST, SHEET SP. 01 |
| | 16A) INDICATES THAT THE TOTAL REQUIRED |
| | PARKING SPACES OF 118 PARKING SPOTS. |
| | PLANS NOW INDICATE (5) ACCESSIBLE |
| | PARKING STALLS, 5.11-4.6.2 LOCATION. |
| | ACCESSIBLE PARKING SPACES SERVING A |
| | PARTICULAR BUILDING SHALL BE LOCATED ON |
| | THE SHORTEST SAFELY ACCESSIBLE ROUTE OF |
| | TRAVEL FROM ADJACENT PARKING TO AN |
| | ACCESSIBLE ENTRANCE. THE NEW ACCESSIBLE |
| | PARKING SPACE SHALL BE AS CLOSE TO THE |
| | ENTRANCE AS POSSIBLE. |
| | |
| | 16B)2ND REQUEST, THIS SHEET NOR A.01 |
| | INDICATE CLEARLY THE PASSENGER LOADING |
| | ZONE UNDER THE CANOPY PLEASE CLARIFY THE |
| | PASSENGER LOADING ZONE, 11-4.6.6 |
| | PASSENGER LOADING ZONES. |
| | PASSENGER LOADING ZONES SHALL PROVIDE AN |
| | ACCESS AISLE AT LEAST 60 INCHES (1525 |
| | MM) WIDE AND 20 FEET (6096 MM) LONG |
| | ADJACENT AND PARALLEL TO THE VEHICLE |
| | PULL-UP SPACE (SEE FIGURE 11-10 ). IF |
| | THERE ARE CURBS BETWEEN THE ACCESS AISLE |
| | AND THE VEHICLE PULL-UP SPACE, THEN A |
| | CURB RAMP COMPLYING WITH SECTION 11-4.7 |
| | SHALL BE PROVIDED. VEHICLE STANDING |
| | SPACES AND ACCESS AISLES SHALL BE LEVEL |
| | WITH SURFACE SLOPES NOT EXCEEDING 1:50 |
| | (2 PERCENT) IN ALL DIRECTIONS. |
| | |
| | 17) COMPLIED. |
| | |
| | 18)NOTE, REQUIREMENT FOR C. O. |
| | SHEET SP.03, NOTE: POOL, |
| | SEE DEPARTMENT OF HEALTH FOR REGULATIONS |
| | FOR POOL SAFETY FENCE, RULE 64E-9. |
| | |
| | 19)SHEET A.01: |
| | |
| | 19A)2ND REQUEST, |
| | NEITHER A.01 OR A 4.17 PROVIDE WALL |
| | DETAILS INDICATING A 1 HR WALL RATING. |
| | THE DOOR 48A DOES NOT INDICATE ANY FIRE |
| | RATING ON A.25 OF THE DOOR SCHEDULE. |
| | LAUNDRY CHUTE TERMINATION ROOM & |
| | DOOR 48ATO MEET THE REQUIREMENTS OF , |
| | 707.13.4 TERMINATION ROOM. |
| | REFUSE AND LAUNDRY CHUTES SHALL |
| | DISCHARGE INTO AN ENCLOSED ROOM |
| | COMPLETELY SEPARATED FROM THE REMAINDER |
| | OF THE BUILDING BY CONSTRUCTION THAT HAS |
| | A FIRE-RESISTANCE RATING OF NOT LESS |
| | THAN 1 HOUR AND OPENINGS INTO THE |
| | TERMINATION ROOM SHALL BE PROTECTED BY |
| | OPENING PROTECTIVES HAVING A FIRE |
| | PROTECTION RATING OF NOT LESS THAN ? |
| | HOUR AND SHALL BE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF |
| | SMOKE. REFUSE CHUTES SHALL NOT TERMINATE |
| | IN AN INCINERATOR ROOM. REFUSE AND |
| | LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH |
| | CHUTES NEED ONLY COMPLY WITH TABLE |
| | 302.1.1 . |
| | |
| | 19B)2ND REQUEST, A.02-.04 PLANS ARE |
| | TOTALLY MISSING AN ACCESS ROOM FOR THE |
| | LAUNDRY CHUTE. |
| | 707.13.3 REFUSE AND LAUNDRY CHUTE |
| | ACCESS ROOMS. |
| | ACCESS OPENINGS FOR REFUSE AND LAUNDRY |
| | CHUTES SHALL BE LOCATED IN ROOMS OR |
| | COMPARTMENTS COMPLETELY ENCLOSED BY |
| | CONSTRUCTION THAT HAS A FIRE-RESISTANCE |
| | RATING OF NOT LESS THAN 1 HOUR AND |
| | OPENINGS INTO THE ACCESS ROOMS SHALL BE |
| | PROTECTED BY OPENING PROTECTIVES HAVING |
| | A FIRE PROTECTION RATING OF NOT LESS |
| | THAN ? HOUR AND SHALL BE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF |
| | SMOKE. |
| | |
| | 19C)2ND REQUEST, |
| | PROVIDE A 2 HR SHAFT TO SURROUND |
| | THE LAUNDRY CHUTE, 707.4 FIRE-RESISTANCE |
| | RATING. SHAFT ENCLOSURES SHALL HAVE A |
| | FIRE-RESISTANCE RATING OF NOT LESS THAN |
| | 2 HOURS WHERE CONNECTING FOUR STORIES OR |
| | MORE AND NOT LESS THAN1 HOUR WHERE |
| | CONNECTING LESS THAN FOUR STORIES. THE |
| | NUMBER OF STORIES CONNECTED BY THE SHAFT |
| | ENCLOSURE SHALL INCLUDE ANY BASEMENTS |
| | BUT NOT ANY MEZZANINES. SHAFT ENCLOSURES |
| | SHALL BE CONSTRUCTED AS FIRE BARRIERS IN |
| | ACCORDANCE WITH SECTION 706 . SHAFT |
| | ENCLOSURES SHALL HAVE A FIRE-RESISTANCE |
| | RATING NOT LESS THAN THE FLOOR ASSEMBLY |
| | PENETRATED, BUT NEED NOT EXCEED 2 HOURS. |
| | |
| | |
| | 19D)2ND REQUEST MISSING FIRE SPRINKLERS |
| | LOCATED 707.13.6 AUTOMATIC FIRE |
| | SPRINKLER SYSTEM. AN APPROVED AUTOMATIC |
| | FIRE SPRINKLER SYSTEM SHALL BE INSTALLED |
| | IN ACCORDANCE WITH SECTION 903.2.10.2 . |
| | 903.2.10.2 RUBBISH AND LINEN CHUTES. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE |
| | INSTALLED AT THE TOP OF RUBBISH AND |
| | LINEN CHUTES AND IN THEIR TERMINAL |
| | ROOMS. CHUTES EXTENDING THROUGH THREE OR |
| | MORE FLOORS SHALL HAVE ADDITIONAL |
| | SPRINKLER HEADS INSTALLED WITHIN SUCH |
| | CHUTES AT ALTERNATE FLOORS. CHUTE |
| | SPRINKLERS SHALL BE ACCESSIBLE FOR |
| | SERVICING. |
| | |
| | 19E)2ND REQUEST, |
| | PROVIDE A LIFE SAFETY PLAN FOR |
| | EXITING. PROVIDE THE LOADS FROM THE |
| | FLOORS ABOVE AS WELL AS THE FIRST FLOOR. |
| | TABLE 1004.1.2/ TABLE 1005.1. |
| | |
| | |
| | 19F)COMPLIES. |
| | |
| | 19G)COMPLIES. |
| | . |
| | |
| | 19H)2ND REQUEST, INDICATE COMPLIANCE |
| | WITH,BREAKFAST AREA, THIS SHEET AND |
| | A.15 TO INDICATE COMPLIANCE WITH: |
| | 11-5.1- 11-5.6. |
| | |
| | 11-5.2 COUNTERS AND BARS. |
| | WHERE FOOD OR DRINK IS SERVED AT |
| | COUNTERS EXCEEDING 34 INCHES (865 MM) IN |
| | HEIGHT FOR CONSUMPTION BY CUSTOMERS |
| | SEATED ON STOOLS OR STANDING AT THE |
| | COUNTER, A PORTION OF THE MAIN COUNTER |
| | WHICH IS 60 INCHES (1525 MM) IN LENGTH |
| | MINIMUM SHALL BE PROVIDED IN COMPLIANCE |
| | WITH SECTION 11-4.32 OR SERVICE SHALL BE |
| | AVAILABLE AT ACCESSIBLE TABLES WITHIN |
| | THE SAME AREA. |
| | |
| | 11-5.3 ACCESS AISLES. |
| | ALL ACCESSIBLE FIXED TABLES SHALL BE |
| | ACCESSIBLE BY MEANS OF AN ACCESS AISLE |
| | AT LEAST 36 INCHES (915 MM) CLEAR |
| | BETWEEN PARALLEL EDGES OF TABLES OR |
| | BETWEEN A WALL AND THE TABLE EDGES. |
| | |
| | 11-5.5 FOOD SERVICE LINES. |
| | FOOD SERVICE LINES SHALL HAVE A MINIMUM |
| | CLEAR WIDTH OF 36 INCHES (915 MM), WITH |
| | A PREFERRED CLEAR WIDTH OF 42 INCHES |
| | (1065 MM) TO ALLOW PASSAGE AROUND A |
| | PERSON USING A WHEELCHAIR. TRAY SLIDES |
| | SHALL BE MOUNTED NO HIGHER THAN 34 |
| | INCHES (865 MM) ABOVE THE FLOOR (SEE |
| | FIGURE 11-53 ). IF SELF-SERVICE SHELVES |
| | ARE PROVIDED, AT LEAST 50 PERCENT OF |
| | EACH TYPE MUST BE WITHIN REACH RANGES |
| | SPECIFIED IN SECTIONS 11-4.2.5 AND |
| | 11-4.2.6 . |
| | |
| | 11-5.6 TABLEWARE AND CONDIMENT AREAS. |
| | SELF-SERVICE SHELVES AND DISPENSING |
| | DEVICES FOR TABLEWARE, DISHWARE, |
| | CONDIMENTS, FOOD AND BEVERAGES SHALL BE |
| | INSTALLED TO COMPLY WITH SECTION 11-4.2 |
| | (SEE FIGURE 11-54 ). |
| | |
| | 19I)2ND REQUEST, PROVIDE WHERE I CAN |
| | FIND THIS INFORMATION? INDICATE |
| | COMPLIANCE WITH: 11-9.3 |
| | VISUAL ALARMS, NOTIFICATION DEVICES AND |
| | TELEPHONES. 11-9.3.1 GENERAL. |
| | IN SLEEPING ROOMS REQUIRED TO COMPLY |
| | WITH THIS SECTION, AUXILIARY VISUAL |
| | ALARMS SHALL BE PROVIDED AND SHALL |
| | COMPLY WITH SECTION 11-4.28.4 . VISUAL |
| | NOTIFICATION DEVICES SHALL ALSO BE |
| | PROVIDED IN UNITS, SLEEPING ROOMS AND |
| | SUITES TO ALERT ROOM OCCUPANTS OF |
| | INCOMING TELEPHONE CALLS AND A DOOR |
| | KNOCK OR BELL. |
| | NOTIFICATION DEVICES SHALL NOT BE |
| | CONNECTED TO AUXILIARY VISUAL ALARM |
| | SIGNAL APPLIANCES. PERMANENTLY INSTALLED |
| | TELEPHONES SHALL HAVE VOLUME CONTROLS |
| | COMPLYING WITH SECTION 11-4.31.5 ; AN |
| | ACCESSIBLE ELECTRICAL OUTLET WITHIN 4 |
| | FEET (1219 MM) OF A TELEPHONE CONNECTION |
| | SHALL BE PROVIDED TO FACILITATE THE USE |
| | OF A TEXT TELEPHONE. |
| | |
| | 20) SHEET A.02- A.04: |
| | |
| | 20A) 2ND REQUEST PLANS INDICATE NEXT TO |
| | THE ELEVATOR A SHAFT BUT NO DETAILS TO |
| | HR CONSTRUCTION, 707.4. |
| | |
| | 20B) REPEAT OF 20A. |
| | |
| | 21)2ND REQUEST.THE PLANS INDICATE A |
| | DETAIL A.15 DETAIL# 5 FOR HANDRAILS, |
| | THE DETAIL IS NOT FOR HANDRAILS OR |
| | EXTENTIONS. THE OTHER ISSUE IS A NOTE |
| | EXTEND STAIR RAIL EAST STAIR ONLY, NO |
| | INFORMATION IS PROVIDED FOR THE BOTTOM |
| | OF HANDRAILS NOR EXTENTIONS. |
| | SHEET A.20 & A.21 BOTH INDICATE |
| | STAIR TOWERS BUT NO DETAIL SHEET |
| | INDICATING THE HANDRAIL GUARD RAIL |
| | COMPLYING WITH 11-4.9.4(2)IF |
| | HANDRAILS ARE NOT CONTINUOUS, THEY SHALL |
| | EXTEND AT LEAST 12 INCHES (305 MM) |
| | BEYOND THE TOP RISER AND AT LEAST 12 |
| | INCHES (305 MM) PLUS THE WIDTH OF ONE |
| | TREAD BEYOND THE BOTTOM RISER. AT THE |
| | TOP, THE EXTENSION SHALL BE PARALLEL |
| | WITH THE FLOOR OR GROUND SURFACE. AT THE |
| | BOTTOM, THE HANDRAIL SHALL CONTINUE TO |
| | SLOPE FOR A DISTANCE OF THE WIDTH OF ONE |
| | TREAD FROM THE BOTTOM RISER; THE |
| | REMAINDER OF THE EXTENSION SHALL BE |
| | HORIZONTAL [SEE FIGURE 11-19 (C) AND |
| | FIGURE 11-19 (D)]. HANDRAIL EXTENSIONS |
| | SHALL COMPLY WITH SECTION 11-4.4 . |
| | DETAILS ON A.15 ARE MISSING. |
| | |
| | 22) SHEET A.23: |
| | |
| | 22A) RESPONCE FIREPLACE DELETED, SEE |
| | A.05 PLAANS INDICATE CHIMNEY. PLEASE |
| | CORRECT. |
| | |
| | 22B)2ND REQUEST. |
| | MISSING SECTIONS ON A.24A DETAILS |
| | 1-4. |
| | NOTE DETAIL 3 IS USED IN THE |
| | CLEARSTORY AS WELL AS COMMEON TRUSS |
| | DETAIL FOR HIP END. CORRECT. |
| | |
| | 22C) COMPLIED. |
| | |
| | 22D) 2ND REQUEST.THIS IS A FOUR STORY |
| | BUILDING, SHOW PRODUCT APPROVAL REPORT |
| | WHERE SHINGLES WILL BE ABLE TO BE USED |
| | WITH A MEAN ROOF HEIGTH OF OVER 40'-0"? |
| | SHEET A.23 @ CLEARSTORY, DARK GREEN |
| | ASPHALT SHINGLES. |
| | |
| | 23) SHEET A.25 DOOR SCHEDULE: |
| | |
| | 23A)2ND REQUEST.INDICATE ON HARDWARE |
| | SCHEDULE. DOOR SCHEDULE DOESN,T INDICATE |
| | ANY HARDWARE FOR FIRE RATED DOORS, |
| | PLEASE SEE SECTION:715.3.3 FOR REQUIRED |
| | HARDWARE INCLUDING CLOSERS AND |
| | ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS |
| | THE BOTTOM OF THE DOOR TESTED IN |
| | ACCORDANCE WITH UL 1784. |
| | |
| | B)NOTE: LOUVERS ARE PROHIBITED IN FIRE |
| | RATED DOORS. THE ELEVATIONS DO NOT |
| | INDICATE THE BOILERE ROOM DOORS ON THE |
| | ELEVATION. WHEN LOOKING AT THE |
| | MECHANICAL PLANS IT APPEARS THAT THERE |
| | MAY NOT BE ENOUGH MAKE UP AIR, FOR THIS |
| | REASON THE COMMENT WAS MADE. |
| | |
| | 24) COMPLIED. |
| | |
| | 25) COMPLIED. |
| | |
| | 26) 2ND REQUEST, PLANS DO NOT PROVIDE |
| | MINIMUM BLDG TYPE! S3.1, A.23 NO DETAILS |
| | INDICATE THE TYPE OF MATERIAL TO BE USED |
| | FOR ROOF SHEATHING. PLANS ALSO DO NOT |
| | PROVIDE THE MINIMUM BUILDING DESIGN |
| | TABLE 503/ 601. |
| | |
| | NEW COMMENTS: |
| | |
| | 27)1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING |
| | ASSEMBLIES SEPARATING DWELLING UNITS |
| | FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND |
| | TRANSMISSION CLASS (STC) OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. PENETRATIONS |
| | OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| | FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| | VENTILATING OR EXHAUST DUCTS SHALL BE |
| | SEALED, LINED, INSULATED OR OTHERWISE |
| | TREATED TO MAINTAIN THE REQUIRED |
| | RATINGS. THIS REQUIREMENT SHALL NOT |
| | APPLY TO DWELLING UNIT ENTRANCE DOORS; |
| | HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 28) 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN |
| | THE STRUCTURE SHALL HAVE AN IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT |
| | LESS THAN 50 (45 IF FIELD TESTED) WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |