| Date |
Text |
| 2006-02-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | WPB CITY CODE/ORDINENCES |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. INDICATE ON PLANS THAT THE DESIGN IS |
| | PER FBC-2004. |
| | 2. ALL ARCHITECTURAL SHEETS SHALL SHOW |
| | THE DATE THAT THE SEAL WAS AFFIXED TO |
| | THE PLANS. FAC 61G1-16.003 & |
| | 61G1-16.004(5) AND FS 481.219 & |
| | 481.2055. MANY SHEETS HAVE NO DATE ON |
| | THE SEAL AND THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER SHALL BE IN THE |
| | TITLE BLOCK OF EACH SHEET. |
| | 3. POOL PLAN: SEPARATE PERMIT/PLANS |
| | REQUIRED FOR THE POOL. MINIMUM 2 SETS OF |
| | PLANS SHALL BE REVIEWED AND STAMPED BY |
| | THE PBC HEALTH DEPT. PRIOR TO SUBMITTING |
| | TO THE CITY WPB FOR REVIEW. |
| | 4. SHT A.01 GREASE INTECEPTOR SHALL BE |
| | SIZED BY LYNN MASSON, ENVIRONMENTAL |
| | COMPLIANCE. PLEASE CONTACT HER AT (561) |
| | 822-2271, OR FAX (561) 822-2279, OR |
| | E-MAIL HER AT [email protected]. SUBMIT A |
| | COPY OF HER REQUIREMENTS/DETERMINATION |
| | WITH PLANS WHEN RESUBMITTING. WASTE ORD. |
| | 90-124(7)(B). |
| | 5. SHT A.01 ROUTE PLANS TO DBPR, |
| | DIVISION OF HOTEL & RESTURANT FOR REVIEW |
| | PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF |
| | PLANS SHALL BE REVIEWED, STAMPED AND TWO |
| | SHEET "WORKSHEETS" SHALL BE ATTACHED TO |
| | EACH SET OF PLANS SUBMITTED FOR REVIEW. |
| | SECTION 102.2.1. |
| | 6. SHT A.01 SHOW THE TURNING AREA IN THE |
| | TOILET ROOMS 32 & 33, NOT IN THE |
| | ACCESSIBLE STALL. SECTION 11-4.22.3 |
| | 7. SHT A.01 INDICATES ROOM TYPES K4, K5, |
| | K6, K7, KING HI, KING, KS, K2, K3, KING |
| | 2, KING 3, KING 8, QQ, QQ HI, BUT ONLY |
| | K4, K7, KS, KE, KING 2, OFFER |
| | ACCESSIBLITY. PLEASE INDICATE HOW THIS |
| | COMPLYS WITH SECTION 11-9.1.4 CLASSES OF |
| | SLEEPING ACCOMMODATIONS. |
| | 8. SHT A.01 PLAN KEY NOTES: UNABLE TO |
| | LOCATE KEY PLAN NUMBERS 7 AND 10. PLEASE |
| | SHOW NUMBERS ON PLAN. SECTION 106.1.1. |
| | 9. SHT A.01 ADA ROOMS MATRIX INDICATES |
| | ROOM 121 AS HAVING A SHOWER. TABLE |
| | INDICATING NUMBER OF ACCESSIBLE ROOMS |
| | INDICATE 4 ARE REQUIRED WITH ONE ROOM |
| | WITH A ROLL IN SHOWER REQUIRED. PLEASE |
| | INDICATE IF ROOM 121 IS ONE OF THE FOUR |
| | REQUIRED ACCESSIBLE ROOMS. SECTION |
| | 11-9.1.2. |
| | 10. SHT A.01 ADA ROOMS MATRIX INDICATES |
| | 5 ROOMS FOR THE HEARING IMPAIRED ROOMS. |
| | ONE ROOM (226) IS NOT SHOWN ON THE FLOOR |
| | PLAN. (4 OTHER ROOMS SHOWN AS HEARING |
| | IMPAIRED ACCOMODATIONS). PLEASE CLARIFY. |
| | SECTION 11-9.1.3. |
| | 11. SHT A.01 1 ROOM SHALL COMPLY WITH |
| | SECTION 11-9.2.3 PLEASE INDICATE THE |
| | ROOM NUMBER THAT SHALL COMPLY WITH THIS |
| | REQUIREMENT. |
| | 12. SHT A.05 SUBMIT A DETAIL FOR |
| | SCUPPERS. ALL DOWNSPOUTS ARE NOT SHOWN |
| | ON THE ELEVATIONS. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | 13. SHT A.17 BREAK SINK TO COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | SUBMIT A DETAIL. |
| | 14. SHT A.17 PLAN KEY NOTES: SHOW THE |
| | LOCATIONS OF NUMBER 2 & 10. SECTION |
| | 106.1.1. |
| | 15. SHT A.32 SHOW CENTER OF FIXTURE OFF |
| | THE WALL AT 18" FOR THE WATER CLOSET. |
| | (FIG. 28). SHOW THE FLUSH CONTROLS AS |
| | REQUIRED IN SECTION 11-4.16.5. |
| | 16. SHT A.33A LAV CLEARANCE TO BE 29" |
| | PER 11-4.19.2. (27" SHOWN). - SHOW THE |
| | FAUCET REQUIREMENT PER SECTION 11-4.19.5 |
| | - SHOW CONTROL REQUIREMENTS FOR TUB & |
| | SHOWERS PER 11-4.20.5 (FIG. 11-34) AND |
| | 11-4.21.5 (FIG. 11-37). |
| | 17. SHT A.34 PUBLIC TOILETS PROVIDE A |
| | DETAIL SHOWING COMPLIANCE WITH 11-4.16, |
| | 11-4.18, 11-4.19, & 11-4.22 AND ALL |
| | SUBSECTIONS. SECTION 106.1.1. |
| | 18. SHT P-1 NOTE INDICATES 24 GAUGE |
| | GALVINIZED PAN ABOVE THE ELECTRICAL |
| | EQUIPMENT ROOM WITH A 1" DRAIN TO FLOOR |
| | DRAIN. PER PLUMBING NOTES ON SHT P-12, |
| | NO WATER, SANITARY, OR DRAINAGE PIPING |
| | PERMITTED IN ELECTRICAL OR ELEVATOR |
| | EQUIPMENT ROOMS. (ALSO SEE NEC SECTION |
| | 110.26(F)A.D. - IF SOMEHOW APPROVED, AN |
| | EXPLANATION WILL BE REQUIRED TO EXPLAIN |
| | HOW A 1" DRAIN LINE WILL BE ABLE TO |
| | DRAIN THE 4" SOIL STACK #13, 1" HOT |
| | WATER & 1-1/4" COLD WATER IF THESE LINES |
| | HAPPEN TO FAIL. SECTION 106.1.1. |
| | 19. SUBMIT A KITCHEN FIXTURE I.D. SHEET |
| | INDICATING THE LOCATION AND I.D. NUMBER |
| | FOR EACH FIXTURE. INDICATE ALL SANT., |
| | GREASE, GAS, AND WATER SUPPLY PIPE SIZE |
| | FOR EACH FIXTURE/APPLIANCE. SECTION |
| | 106.3.5.1.3. |
| | 20. SHT P-1 DISHWASHER SHALL DRAIN INTO |
| | THE SANITARY SYSTEM, NOT THE GREASE |
| | SYSTEM PER CITY CODE 90-124(7)(B). |
| | 21. SHT P-4 BATH GROUP "E" ITEM D |
| | INDIRECT WASTE FROM THE ICE MACHINE NOT |
| | APPROVED AS SHOWN. SEE ICE MACHINE |
| | DETAIL SHEET P-14 FOR CORRECT |
| | INSTALLATION OF THE INDIRECT WASTE. |
| | SECTIONS 802.3 & 802.3.2. PLEASE CHANGE |
| | DETAIL ON BATH GROUP "E" |
| | 22. SHT P-5 3" RPZV BACKFLOW REQUIRED |
| | DOWNSTREAM OF THE METERS. SECTIONS 603.1 |
| | FOOTNOTE D, AND608.13.2. - ALSO MAKE |
| | CHANGE TO WATER ISOMETRIC DIAGRAM ON |
| | SHEET P-8. |
| | 23. SHT P-6 ALL WATER RISER DIAGRAMS, |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. |
| | CHANGE NOTE 3 OF THE WATER ISOMETRIC |
| | RISERS NOTES TO REFLECT THIS. SECTION |
| | 106.1.1. |
| | 24. SHT P-7 STACK TYPE "A1" NOTE |
| | INDICATES A SHOWER FOR THE BATHROOM |
| | GROUPS, BUT A TUB IS SHOWN ON THE FLOOR |
| | PLAN. PLEASE CORRELATE FLOOR PLAN AND |
| | NOTE. - STACK TYPE "C" A TUB ON THE BATH |
| | GROUP, BUT ISOMETRIC SHOWS SHOWERS. |
| | PLEASE CORRELATE. - STACK TYPE "E" SHOWS |
| | A SAFEWASTE FOR THE INDIRECT WASTE FOR |
| | THE ICE MAKER. SHEET P-14 SHOWS THE |
| | CORRECT INDIRECT WASTE ON THE ICE MAKER |
| | DETAIL. PLEASE CHANGE RISER ISOMETRIC TO |
| | REFLECT THE ICE MAKER DETAIL FOR |
| | INDIRECT WASTE. SECTION 106.1.1. |
| | 25. SHT P-8 BACKFLOW PROTECTION IS |
| | REQUIRED FOR SUPPLY LINE TO THE |
| | FOUNTAIN. PLEASE INDICATE METHOD OF |
| | BACKFLOW PROTECTION. SECTION 608. |
| | 26. SHT P-10 INDICATE THE PIPE SIZE AND |
| | SQUARE FOOTAGE BEING DRAINED DOWNSTREAM |
| | OF STORM RISER L-5. - PIPING DOWNSTREAM |
| | OF STORM RISER L-2 IS INDICATED AS BEING |
| | 2% SLOPE. THIS IS NOT REQUIRED AS THE |
| | RAINFALL RATE IS 4.5 INCHES PER HR. IF |
| | THE PIPE IS TO BE 2% THEN THE ENTIRE RUN |
| | FROM L-8 TO THE OUTSIDE OF THE BLDG |
| | SHALL BE 2% PER SECTION 704.1. - PER |
| | TABLE 1106.3THE MAXIMUM SQUARE FOOTAGE |
| | FOR 4" PIPE @ 4.5 PER INCH RANIFALL RATE |
| | IS 1600SF. L-10 & L-11 ADD UP TO 1646SF. |
| | 5" HORIZONTAL PIPING REQUIRED. PLEASE |
| | CLARIFY. |
| | 27. SHT P-13 WATER HEATER DETAIL STATES |
| | "SEE PROJECT DOCUMENTS AND SPECIFICTION |
| | FOR ADDITIONAL INFORMATION AND WORK |
| | REQUIRED FOR A CODE APPROVED AND |
| | ARCHITECT ACCEPTED INSTALLATION". ALSO |
| | STATESIN PIPING ARRANGEMENT AT WATER |
| | HEATERS (E) "REFER TO MANUFACTURE |
| | RECOMMENDATIONS AND CODE REQUIREMENTS |
| | FOR INSTALLATIONS AND LOCATIONS OF |
| | INTAKE AND EXHAUST VENT TERMINALS". |
| | THESE HAVE NOT BEEN SUBMITTED. SECTION |
| | 106.1.1. |
| | 28. SHT P-14 STORM ISOMETRIC DIAGRAM |
| | DOES NOT REFLECT THE PIPING SHOWING ON |
| | SHEET P-10. THE RISER TO L-10 & L-11 IS |
| | SHOWN AS 5" ON SHT P-10, BUT NO PIPE |
| | SIZE IS SHOWN ON RISER. - INDICATE THE |
| | PIPE SIZE AND SQUARE FOOTAGE DOWNSTREAM |
| | OF RISER L-5. - 2% SLOPE SHOWN |
| | DOWNSTREAM OF RISER L-2. (SEE COMMENT |
| | 26) SECTION 106.1.1 AND TABLE 1106.3. |
| | 29. SHT P-14 NOTES REFER TO PROJECT |
| | SPECIFICATIONS THAT WERE NOT SUBMITTED. |
| | PLEASE SUBMIT ALL REFERENCED |
| | SPECIFICATIONS. SECTION 106.1.1. |
| | 30. SHT P-14 ICE MACHINE DETAIL. |
| | SEPARATE DRAIN LINES REQUIRED FOR THE |
| | ICE CUBER AND THE ICE BIN. |
| | 31. SHT P-15 GREASE WASTE ISOMETRIC |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| | NO LINE TO THE CAN WASH IS SHOWN. P-5 |
| | BEHIND THE ELECTRICAL ROOM IS SHOWN AS A |
| | FLOOR SINK ON THE FLOOR PLAN AND AS A |
| | FLOOR DRAIN ON THE RISER DIAGRAM. |
| | (SHOULD BE A FLOOR SINK ON BOTH) SECTION |
| | 106.1.1. - UNDER GREASE WASTE DIAGRAM |
| | THE NOTESTATES "SEE KITCHEN DOCUMENTS, |
| | SPECIFICATIONS, AND DATA SHEETS FOR |
| | ADDITIONAL INFORMATION AND REQUIREMENTS |
| | OF PLUMBING WORK ETC.". THESE WERE NOT |
| | SUBMITTED. |
| | 32. P-15 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PLAN APPROVAL: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES,- |
| | SPECIFICATIONS NOT SUBMITTED. INDICATE |
| | IF PIPING WILL BE SCREW PIPE OR WELDED |
| | PIPE. |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. |
| | 402.4(2). NATURAL GAS SPECIFY .5 PSI OR |
| | 2 PSI. |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. BYPASS |
| | PIPING SHALL BE CONNECTED DOWNSTREAM OF |
| | THE EMERGENCY HOOD SHUT OFF VALVE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | RESUBMIT ONE SET OF ORIGINAL SHEETS FOR |
| | COMPARISON. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |