| 2006-01-24 00:00:00 | DENIED:********PLAN CHECK ONLY******* |
| | |
| | 1.PLAN SHEET M-2 DETAIL OF THE FAN |
| | COIL UNITS INDICATE A FIRE DAMPER AT THE |
| | FLOOR PENETRATIONS.PER 2004 FMC |
| | 607.6.1,FIRE DAMPERS ARE PERMITTED THE |
| | FLOOR CEILING PENETRATIONS WHEN |
| | CONNECTING NOT MORE THAN TWO STORIES.A |
| | SHAFT ENCLOSURE WILL BE REQUIRED FOR THE |
| | OUTSIDE AIR DUCT THAT PENETRATES 3 FIRE |
| | RATED FLOOR/CEILING & 1 CEILING ROOF |
| | ASSEMBLY. |
| | |
| | 2.PLAN SHEET M-2 TERMINATION OF GREASE |
| | DUCT.PER 2004 FMC 506.3.12.3, EXHAUST |
| | OUTLETS SHALL BE LOCATED NOT LESS THAN |
| | 10 FT HORIZONTALLY FROM PARTS OF THE |
| | SAME OR CONTIGUOUS BUILDINGS.THE |
| | EXCEPTION TO THE 10 FT CLEARANCE IS, 5FT |
| | PROVIDED THAT THE EXHAUST DISCHARAGES |
| | AWAY FROM SUCH LOCATIONS. |
| | |
| | 3.PLEASE CLARIFY IF THE TOILET EXHAUST |
| | WILL BE IN A SUB-DUCT AS INDICATED ON |
| | PLAN SHEET M-11. |
| | |
| | 4.PLAN SHEET M-2 PLEASE CLARIFY THE |
| | FLUE THAT TERMINATES ON THE ROOFAT THE |
| | SECOND FLOOR.PLEASE PROVIDE DETAIL. |
| | |
| | 5.PLEASE INDICATE PIPING MATERIAL & |
| | METHOD OF JOING THE PIPE (WELD, |
| | VICTALIC, THREADED, ETC).PLEASE NOTE, |
| | UNDER GROUND PIPING TO BE PRESSURE |
| | TESTED AND INSPECTED PRIOR TO COVERING |
| | IN ACCORDANCE WITH 2004 FMC 1208. |
| | |
| | 6.PLEASE PROVIDE SUBMITTAL DATA FOR |
| | ALL COMPONENTS OF THE SYSTEM. |
| | |
| | 8.ADDITIONAL PERMITS REQUIRED FOR THE |
| | HOOD, FIRE SUPPRESSION AND WALK-IN |
| | COOLER/FREEZER.PLEASE PROVIDE |
| | MANUFACTURER SUBMITTAL WITH PERMIT |
| | APPLICATION. |
| | |
| | 9.PLEASE INDICATE CLEARANCE TO |
| | COMBUSTIBLES AS REQUIRED IN 2004 FMC |
| | 506.3.6. |
| | |