| Date |
Text |
| 2006-04-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | NFPA-96 |
| | NFPA-1 |
| | |
| | FROM PLUMBING REVIEW NOTES: |
| | |
| | 32. P-15 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PLAN APPROVAL: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS. |
| | ***RESPONSE NOTED, BUT THERE ARE SOME |
| | CUT SECTIONS THAT DO NOT SHOW THE LENGTH |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES,- |
| | SPECIFICATIONS NOT SUBMITTED. INDICATE |
| | IF PIPING WILL BE SCREW PIPE OR WELDED |
| | PIPE. |
| | ***RESPONSE NOTED, BUT NO INFORMATION |
| | FOUND. |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. |
| | 402.4(2). NATURAL GAS SPECIFY .5 PSI OR |
| | 2 PSI. |
| | ***RESPONSE NOTED, BUT DELIVERY PRESSURE |
| | HAS NOT BEEN ADDRESSED. |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***NO RESPONSE, NOT ADDRESSED. |
| | |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. BYPASS |
| | PIPING SHALL BE CONNECTED DOWNSTREAM OF |
| | THE EMERGENCY HOOD SHUT OFF VALVE. |
| | ***NO RESPONSE, NOT ADDRESSED. EMERGENCY |
| | HOOD SHUT DOWN SHUT OFF VALVE SHALL BE |
| | INSTALLED BETWEEN 42" AND 48" PER |
| | NFPA-96 SECTION 10.5.1 AND NFPA-1 |
| | SECTION 50.4.7.1. INDICATE ON GAS RISER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | RESUBMIT ONE SET OF ORIGINAL SHEETS FOR |
| | COMPARISON. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |