| 2005-12-19 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND |
| | RENOVATION TO COMPLY WITH NFPA 241. |
| | |
| | 2. SUITABLE ROADS ARE TO BE PROVIDED |
| | DURING CONSTRUCTION FOR FIRE AND |
| | PARAMEDICAL EQUIPMENT. |
| | |
| | 3. EXIT STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 4. THE AUTOMATIC SLIDING DOOR SHALL |
| | COMPLY WITH POWERED OPERATED DOOR |
| | REQUIREMENTS PER THE LIFE SAFETY CODE, |
| | 2003 EDITION. |
| | |
| | 5. THE SITE PLAN APPEARS TO ONLY DISPLAY |
| | ONE FIRE HYDRANT. IF THIS HYDRANT IS |
| | USED TO CONNECT TO THE FIRE DEPARTMENT |
| | SPRINKLER CONNECTION NO OTHERS ARE |
| | AVAILABLE FOR USE. |
| | |
| | 6. FIRE HOSE VALVES SHALL BE PRESENT |
| | WITHIN THE STAIRWELLS WHERE A TWO HOUR |
| | RATED FIRE PROTECTION IS PROVIDED NOT |
| | OUTSIDE THE STAIRWELLS AS SHOWN. |
| | PORTABLE FIRE EXTINGUISHER CABINETS CAN |
| | REMAIN OUTSIDE THE STAIRWELLS BUT THE |
| | STANDPIPE CONNECTIONS SHOULD BE LOCATED |
| | IN THE STAIRWELLS. |
| | |
| | 7. PLEASE PROVIDE PRESCRIPTIVE |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 8. ELEVATOR WARNING SIGNS WILL BE |
| | REQUIRED IN THE ELEVATOR LOBBIES. |
| | |
| | 9. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR ANY HOOD, DUCT, AND FIRE SUPPRESSION |
| | SYSTEMS PLANNED. |
| | |
| | 10. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER SYSTEM INSTALLATION. |
| | |
| | 11. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM |
| | SHALL BE MONITORED BY A LICENSED UL |
| | LISTED CENTRAL STATION APPROVED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 12. WILL THE PROPOSED FIREPLACE BE |
| | OPERATIONAL OR IS IT DECORATIVE. |
| | |
| | 13. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR ALL WALLS AND |
| | CEILINGS. |
| | |
| | 14. NO SOFFITS SHALL INTERFERE WITH THE |
| | OPERATION OF ANY FIRE SPRINKLER HEADS. |
| | |
| | 15. BUILDING ADDRESS IS REQUIRED ON |
| | PROPER ELEVATION. A MINIMUM OF AT LEAST |
| | 6" HIGH NUMBERS ARE REQUIRED. |
| | |
| | 16. GAS DRYERS ARE TO BE INSTALLED IN |
| | ACCORDANCE WITH RECOGNIZED NFPA |
| | STANDARDS AND RECOGNIZED SAFETY |
| | STANDARDS. |
| | |
| | 17. ALL COOLERS AND FREEZERS SHALL HAVE |
| | FIRE SPRINKLER PROTECTION. |
| | |
| | 18. STAIR SECTION 1, ON PAGE A.20 |
| | REFERENCES CHAPTER 5. IT SHOULD READ |
| | CHAPTER 7. |
| | |
| | 19. ON PAGE A.22 NOTES INDICATE A TWO |
| | HOUR RATING BUT NO UL NUMBER IS |
| | PROVIDED. UL NUMBERS LOCATED ON A.27. |
| | |
| | 20. PLEASE INDICATE ON THE PLANS THAT |
| | ALL FIRE RATED DOORS SHALL BE EQUIPPED |
| | WITH SELF-CLOSING DEVICES AND SHALL |
| | POSITIVELY LATCH WHEN CLOSED. |
| | |
| | 21. HOW WILL CARD READERS INTERFACE WITH |
| | EXITING REQUIREMENTS. |
| | |
| | 22. ALL SMOKE DETECTORS SHALL BE LOCATED |
| | A MINIMUM OF AT LEAST THREE FEET FROM |
| | AIR CONDITIONING DIFFUSERS. PLEASE |
| | PROVIDE NOTE ON PLANS. |
| | |
| | 23. PLEASE INDICATE WHAT REQUIRED |
| | INFORMATION WILL BE PLACED WITHIN THE |
| | HOTEL ROOMS ON THE INTERIOR SIDE DOORS. |
| | |
| | 24. FP-1 APPEARS TO ILLUSTRATE TWO FIRE |
| | HYDRANTS BUT NO CALL-OUTS ARE PROVIDED. |
| | PLEASE REVISE. |
| | |
| | 25. FP-1 SEEMS TO SUGGEST TWO FIRE |
| | DEPARTMENT CONENCTIONS. DUE TO THE SIZE |
| | AND OCCUPANCY TYPE, ONLY ONE FDC IS |
| | REQUIRED. |
| | |
| | 26. FIRE LINE BACKFLOW DEVICE SHALL BE |
| | EQUIPPED WITH FLOW SWITCHES, CHAINS AND |
| | LOCKS. |
| | |
| | 27. NO FIRE SPRINKLER HEADS SHOWN IN |
| | MAIN ELECTRICAL ROOM. |
| | |
| | 28. RISER # 2 ON PAGE FP-6 APPEARS TO |
| | DISPLAY CONTROL VALVES BEHIND THE FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | 29. PLEASE EXPLAIN FOUR INCH UNDERGROUND |
| | FIRE LINE. TYPICALLY, THE MINIMUM SHALL |
| | BE AT LEAST 6" UNLESS HYDRAULIC |
| | CALCULATIONS SUGGEST SOMETHING |
| | OTHERWISE. |
| | |
| | 30. PLANS MENTION EXHAUST DUCT WRAP. |
| | PLEASE PROVIDE PRODUCT APPROVALS |
| | REGARDING THE DUCT WRAP STATED IN THE |
| | PLANS. |
| | |
| | 31. DIFFERENT SHEETS SEEM TO SUGGEST |
| | DIFFERENT NUMBERS OF FIRE HYDRANTS. |
| | PLEASE REVISE ALL SHEETS AND ENSURE THAT |
| | THE CORRECT NUMBER OF FIRE HYDRANTS ARE |
| | SHOWN. |
| | |
| | 32. FLOOR PLANS SHALL ILLUSTRATE ALL |
| | RATED WALLS AND LOCATIONS OF RATED |
| | SHAFTS. RATED WALLS IN COMMON AND |
| | BETWEEN GUEST ROOMS SHALL BE SHOWN. |
| | |
| | 33. PLEASE PROVIDE HEIGHT OF PORTA |
| | CACHERE FROM FINISHED ELEVATION. |
| | |
| | 34. TACTILE SIGNAGE REQUIRED AT EXIT |
| | DOORS. |
| | |