Plan Review Notes
Plan Review Notes For Permit 05110263
Permit Number 05110263
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-12-19 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 3. EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 4. THE AUTOMATIC SLIDING DOOR SHALL
 COMPLY WITH POWERED OPERATED DOOR
 REQUIREMENTS PER THE LIFE SAFETY CODE,
 2003 EDITION.
  
 5. THE SITE PLAN APPEARS TO ONLY DISPLAY
 ONE FIRE HYDRANT. IF THIS HYDRANT IS
 USED TO CONNECT TO THE FIRE DEPARTMENT
 SPRINKLER CONNECTION NO OTHERS ARE
 AVAILABLE FOR USE.
  
 6. FIRE HOSE VALVES SHALL BE PRESENT
 WITHIN THE STAIRWELLS WHERE A TWO HOUR
 RATED FIRE PROTECTION IS PROVIDED NOT
 OUTSIDE THE STAIRWELLS AS SHOWN.
 PORTABLE FIRE EXTINGUISHER CABINETS CAN
 REMAIN OUTSIDE THE STAIRWELLS BUT THE
 STANDPIPE CONNECTIONS SHOULD BE LOCATED
 IN THE STAIRWELLS.
  
 7. PLEASE PROVIDE PRESCRIPTIVE
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 8. ELEVATOR WARNING SIGNS WILL BE
 REQUIRED IN THE ELEVATOR LOBBIES.
  
 9. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD, DUCT, AND FIRE SUPPRESSION
 SYSTEMS PLANNED.
  
 10. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
  
 11. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM
 SHALL BE MONITORED BY A LICENSED UL
 LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 12. WILL THE PROPOSED FIREPLACE BE
 OPERATIONAL OR IS IT DECORATIVE.
  
 13. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR ALL WALLS AND
 CEILINGS.
  
 14. NO SOFFITS SHALL INTERFERE WITH THE
 OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 15. BUILDING ADDRESS IS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 16. GAS DRYERS ARE TO BE INSTALLED IN
 ACCORDANCE WITH RECOGNIZED NFPA
 STANDARDS AND RECOGNIZED SAFETY
 STANDARDS.
  
 17. ALL COOLERS AND FREEZERS SHALL HAVE
 FIRE SPRINKLER PROTECTION.
  
 18. STAIR SECTION 1, ON PAGE A.20
 REFERENCES CHAPTER 5. IT SHOULD READ
 CHAPTER 7.
  
 19. ON PAGE A.22 NOTES INDICATE A TWO
 HOUR RATING BUT NO UL NUMBER IS
 PROVIDED. UL NUMBERS LOCATED ON A.27.
  
 20. PLEASE INDICATE ON THE PLANS THAT
 ALL FIRE RATED DOORS SHALL BE EQUIPPED
 WITH SELF-CLOSING DEVICES AND SHALL
 POSITIVELY LATCH WHEN CLOSED.
  
 21. HOW WILL CARD READERS INTERFACE WITH
 EXITING REQUIREMENTS.
  
 22. ALL SMOKE DETECTORS SHALL BE LOCATED
 A MINIMUM OF AT LEAST THREE FEET FROM
 AIR CONDITIONING DIFFUSERS. PLEASE
 PROVIDE NOTE ON PLANS.
  
 23. PLEASE INDICATE WHAT REQUIRED
 INFORMATION WILL BE PLACED WITHIN THE
 HOTEL ROOMS ON THE INTERIOR SIDE DOORS.
  
 24. FP-1 APPEARS TO ILLUSTRATE TWO FIRE
 HYDRANTS BUT NO CALL-OUTS ARE PROVIDED.
 PLEASE REVISE.
  
 25. FP-1 SEEMS TO SUGGEST TWO FIRE
 DEPARTMENT CONENCTIONS. DUE TO THE SIZE
 AND OCCUPANCY TYPE, ONLY ONE FDC IS
 REQUIRED.
  
 26. FIRE LINE BACKFLOW DEVICE SHALL BE
 EQUIPPED WITH FLOW SWITCHES, CHAINS AND
 LOCKS.
  
 27. NO FIRE SPRINKLER HEADS SHOWN IN
 MAIN ELECTRICAL ROOM.
  
 28. RISER # 2 ON PAGE FP-6 APPEARS TO
 DISPLAY CONTROL VALVES BEHIND THE FIRE
 DEPARTMENT CONNECTION.
  
 29. PLEASE EXPLAIN FOUR INCH UNDERGROUND
 FIRE LINE. TYPICALLY, THE MINIMUM SHALL
 BE AT LEAST 6" UNLESS HYDRAULIC
 CALCULATIONS SUGGEST SOMETHING
 OTHERWISE.
  
 30. PLANS MENTION EXHAUST DUCT WRAP.
 PLEASE PROVIDE PRODUCT APPROVALS
 REGARDING THE DUCT WRAP STATED IN THE
 PLANS.
  
 31. DIFFERENT SHEETS SEEM TO SUGGEST
 DIFFERENT NUMBERS OF FIRE HYDRANTS.
 PLEASE REVISE ALL SHEETS AND ENSURE THAT
 THE CORRECT NUMBER OF FIRE HYDRANTS ARE
 SHOWN.
  
 32. FLOOR PLANS SHALL ILLUSTRATE ALL
 RATED WALLS AND LOCATIONS OF RATED
 SHAFTS. RATED WALLS IN COMMON AND
 BETWEEN GUEST ROOMS SHALL BE SHOWN.
  
 33. PLEASE PROVIDE HEIGHT OF PORTA
 CACHERE FROM FINISHED ELEVATION.
  
 34. TACTILE SIGNAGE REQUIRED AT EXIT
 DOORS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709