| 2006-01-20 00:00:00 | FAILED: | | | | | | 1. PLEASE SUBMIT A COPY OF MODIFIED | | | SFWMD PERMIT. | | | 2. PLEASE PROVIDE CALCULATION FOR STORM | | | WATER POST DEVELOPMENT. | | | 3. PLEASE STATE AS WHERE RAIN LEADERS | | | BEING CONNECTED. | | | 4. A CLEAN OUT IN ALL SEWER LATERAL IS | | | REQUIRED. | | | PLEASE SHOW THE LOCATIONS FOR BACKFLOWS | | | FOR DOMMESTIC AND FIRE LINE. | | | 5. AN OIL WATER SEPARATOR IN SEWER LINE | | | FOR THIS FACILITY IS REQUIRED. | | | 6. IS THERE A SEPARATE METER FOR THIS | | | FACILITY? | | | 7. DUMPSTER ENCLOSURE SHOULD BE SIZED | | | PER CITY OF WEST PALM BEACH REQUIREMENTS | | | IF TO BE PICKED UP BY THE CITY, 12'-6" | | | BETWEEN THE GATE POSTS, 12'-6" DEEP. | | | 8. ANY INLET IN THE PROPOSED ASPHALT | | | DRIVEWAY? PLEASE VERIFY. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|