| 2006-02-01 00:00:00 | *** PLEASE SEE 2004 FBC CHAPETR 13. |
| | HOTELS, ROOM OCCUPANCY CONTROLS FOR |
| | ROOMS AND OTHER CONTROL FOR COMMON AREAS |
| | ETC. |
| 2005-12-27 00:00:00 | *************************************** |
| | ************** UNSAT *************** |
| | |
| | ** HILTON GARDENS ** |
| | |
| | ** PLEASE KNOW, PLANS ONLY SUBMITTED FOR |
| | "PLAN REVIEW ONLY" AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | ** PLEASE SEE BLDG REVIEW COMMENTS AS |
| | THIS PROJECT MAY REQUIRE A THIRD SET OF |
| | PLANS |
| | |
| | |
| | 1)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | CURRENT CODES IN EFFECT. |
| | 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002 |
| | NFPA-72 ETC |
| | |
| | 2)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM |
| | DOORS WILL BE REQUIRED TO OPEN OUTWARD |
| | AND SHALL HAVE PANIC HARDWARE. |
| | 110.26 |
| | |
| | 3)NOTE: PLEASE BE SURE ALL ELECTRICAL |
| | RMS, ELEVATOR EQUIPMENT RMS CONTAIN A |
| | BATTERY BACK UP LIGHT OF SOME SORT. |
| | LS101 7.8,7.9, 700.16 |
| | |
| | 4)NOTE: PLEASE SEE ELECTRICAL RMS ON |
| | EACH FLOOR MAY NOT CONTAIN AREA FOR |
| | "HOUSEKEEPING/STORAGE. |
| | PLEASE SEE SHEETS E-5- E7 WHICH WOULD BE |
| | ACCEPTABLE BY PLACING A WALL BETWEEN |
| | THIS AREA ELECTRICAL ROOM WITH A |
| | SEPARATE ENTRANCE/DOOR. |
| | 110.26, 407.7, 240.24 |
| | |
| | 5)NOTE: PLEASE SEE FIRST FLR CIRCUTING |
| | FOR HALL RECEPTS, SOME SHOWN AND SOME |
| | MISSING. PLEASE COMPLETE. |
| | THERE IS A NOTE ON PLANS, WHICH MENTIONS |
| | HALL RECEPTS TO BE CIRCUITED TO NEAREST |
| | GUEST RM, HOWEVER THIS CIRCUIT NEEDS TO |
| | BE SHOWN. |
| | |
| | 6)NOTE: PLEASE COMPLETE ALL OTHER |
| | CIRCUITING, GUEST RMS ETC. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SEE ELECTRICAL EQUIPMENT |
| | LOCATED ON WALL NEXT TO POOL APEARS TO |
| | BE LOCATED TOO CLOSE WHICH DOES NOT MEET |
| | MIN CLEARENCES PER 680.22 |
| | |
| | 8)NOTE: PLEASE SEE 620.23, 620.24 WHICH |
| | REQUIRES A DEDICATED BRANCH CIRCUIT FOR |
| | RECEPTS AND LTS FOR ELEVATOR EQUIPMENT |
| | RMS AND ANY ELEVATOR PITS. |
| | |
| | 9)NOTE: PLEASE SUBMIT COMPLETE |
| | PHOTOMETRICS FOR ALL COMMON AREAS, AND |
| | STAIR TOWERS. |
| | PLEASE SEE 2003 NFPA-1017.8.1.3 WHICH |
| | REQUIRES A MIN OF 1 FT CANDLEAND A MIN |
| | OF 10FT CANDLES ON THE WALKING SURFACE |
| | UNDER NORMAL POWER. PLEASE SEE7.9.2.1 |
| | WHICH REQUIRES A MIN OF 1FT CANDLE OF |
| | LIGHTING ON ALL WALKING SURFACES UNDER |
| | EMERGENCY CONDITIONS. |
| | |
| | 10)NOTE: PLEASE SEE PHOTOMETRICS SHOWN |
| | FOR POOL AREA SHALL BE SUBMITTED TO PALM |
| | BEACH COUNTY HEATH DEPARTMENT FOR ANY |
| | AFTER DUSK SWIMMMING. |
| | IF THERE IS NOT GOING TO BE ANY SWIMMING |
| | FROM DUSK TO DAWN, PLEASE PROVIDE A NOTE |
| | ON PLAN FOR REQUIRED SIGNAGE TO BE PLACE |
| | AT AND IN POOL AREA. |
| | ** PLEASE KNOW, THE SWIMMING POOL ITSELF |
| | WILL BE REQUIRED TO BE UNDER A SEPARATE |
| | PERMIT. |
| | |
| | 11)NOTE: PLEASE CLARIFY NOTE ON PLANS |
| | FOR THE REQUIREMENTS OF GUEST BATH GFI. |
| | THIS CAN NOT BE VERIFIED AT THIS TIME |
| | DUE TO MISSING CIRCUITING. |
| | |
| | 12)NOTE: PLEASE SEE 210.60 FOR REQUIRED |
| | RECEPT SPACING FOR GUEST RMS OF HOTELS |
| | WHICH REFERENCES 210.52 FOR MIN SPACING. |
| | PLEASE SEE THERE IS AN EXCEPTION TO THE |
| | MIN SPACING AS TO PROVIDE RECEPTS FOR |
| | FURNITURE PLANS, HOWEVER THE NUMBER OF |
| | RECEPTS TO BE PROVIDED SHALL MEET THE |
| | SAME NUMBER OF RECEPTS IF THEEY WERE |
| | INSTALLED PER 210.52 |
| | PLEASE SEE MANY GUEST RM TYPES WHICH ARE |
| | MISSING THE REQUIRED NUMBER. |
| | PLEASE SEE MOSTOF THESE UNTIS ARE |
| | REDLINED ON ONE SET OF PLANS. |
| | KING,2,5 6,7,KING SUITE ETC. PLEASE KNOW |
| | THAT NOT ALL UNITS WERE REDLINED, PLEASE |
| | BE SURE TO GO OVER THE MIN. |
| | PLEASE KNOW THAT A MIN OF TWO RECEPTS |
| | SHALL BE READILY ACCESSIBLE AT ALL |
| | TIMES. |
| | MOST UNITS MEET THIS , HOWEVER A COUPLE |
| | ARE MISSING. |
| | |
| | 13)NOTE: PLEASE PROVIDE A NOTE ON THE |
| | ROOOFTOP PLAN WHICH SHOULD NOTE/MENTION: |
| | ANY PROPOSED LIGHTNING PROTECTION SYSTEM |
| | SHALL MEET NFPA-780, OR WORDS TO THAT |
| | AFFECT. |
| | IT IS NOTED THAT NO SYSTEM IS SHOWN AT |
| | THIS TIME, AND ANY FUTURE WOULD BE UNDER |
| | A SEPARATE PERMIT, HOWEVER A NOTE IS |
| | REQUIRED AT THIS TIME. |
| | |
| | 14)NOTE:PLEASE SEE PANEL "K" IS SHOWN |
| | LISTING A 125A OCP TO FEED TO PANEL |
| | "KA", HOWEVER PANEL "KA" IS ONLY REATED |
| | AT 100A'S? |
| | PLEASE CORRELATE AND ADJUST. |
| | 215.5, |
| | |
| | 15)NOTE: PLEASE SEE PANEL "LDY" IS SHOWN |
| | AS A 100A MLO, YET MSB SHOWS A 225A |
| | BRKR/OCP FEEDING THIS PANEL. |
| | PLEASE ADJUST AND CORRELATE. |
| | 215.5 |
| | |
| | 16)NOTE: PLEASE SEE PANEL "L" IS SHOWN |
| | AS 100A MLO, WITH MSB SHWOING 150A OCP |
| | FEEDING THIS PANEL. |
| | PLEASE ADJUST AND CORRELATE. |
| | 215.5 |
| | |
| | 17)NOTE: PLEASE SEE RISER AND MSB SHOWS |
| | ALL 1H1, 2H2, 3H3 ETC AS 1H, 2H, 3H ETC |
| | ON PANEL SCHEDULES FOR THESE. |
| | PLEASE CORRELATE THE IDENTIFICATION OF |
| | THESE. |
| | 215.5 |
| | |
| | 18)NOTE: PLEASE SEE 240.4C, WHICH |
| | REQUIRES THE CONDUCTOR FEEDING DEVICES |
| | RATED OVER 800A'S TO MEET OR EXCEED |
| | RAITNG OF SUCH DEVICE. |
| | PLEASE SEE MSB OS SHOWN AS A 3000A MAIN |
| | , HOWEVER CONDUCTORS ARE ONLY RATED FOR |
| | 2100 A'S? |
| | 5-SETS OF 600MCM, RATED @420A'S EACH.(75 |
| | DEGREE COL). |
| | 110.14, 215.5,215.3 |
| | PLEASE ADJUST ON MORE THAN ONE SHEET, |
| | SEE 13,14. |
| | |
| | 19)NOTE: PLEASE ALSO SEE CONDUCTORS FOR |
| | MAIN FEEDERS TO CHILLER FROM MSB. |
| | PLEASE SEE MSB SHOWS 3-300 MCM, HOWEVER |
| | PLEASE SEE CALCUALTIONS FOR CHILLER |
| | WHICH INDICATE 2-600'S. |
| | PLEASE CORRELARE. 215.5 |
| | |
| | 20)NOTE: PLEASE SEE RISER INDICATES |
| | "BLDG STEEL" AS PART OF THE GROUNDING |
| | ELECTRODE SYSTEM, WHICHIS OK AND IS |
| | REQUIRED IF "BLDG STEEL" IS PRESENT. |
| | PLEASE ALSO INCLUDE THE REQUIRED "FOOTER |
| | STEEL" IN DETAIL. |
| | 250.50 |
| | |
| | 21)NOTE: PLEASE KNOW, THE REQUIRED WIND |
| | LOAD CALCULATIONS FOR LT POLES WITH |
| | FIXTURES ON THEM ARE REQUIRED AT THIS |
| | TIME. |
| | PLEASE KNOW, THESE WILL BE REVIEWED BY A |
| | STRUCTUAL PLANS REVIEWER. |
| | IF THIS INFORMATION IS NOT SUBMITTED AT |
| | THIS TIME, ALL SITE LIGHTING WOULD BE |
| | REQUIRED TO BE UNDER A SEPARATE PERMIT, |
| | WITH SEPARATE PLANS AND FEES. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE SEE ONE SET OF ELECTRICAL |
| | PLANS HAVE MANY OF THE ABOVE ITMES |
| | REDLINED IN LOCATIONS FOR NOTES. |
| | IE,FLR ELEC RMS, RECEPTS ETC. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED |
| | ELECTRICAL PAGES AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | 19)NOTE: PLEAS |
| 2005-12-26 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. |
| | PLANS WILL GO INTO "F" STATUS. |
| | REVIEW IN PROGRESS, NOTES TO FOLLOW. |