Plan Review Notes
Plan Review Notes For Permit 05110263
Permit Number 05110263
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-01 00:00:00*** PLEASE SEE 2004 FBC CHAPETR 13.
 HOTELS, ROOM OCCUPANCY CONTROLS FOR
 ROOMS AND OTHER CONTROL FOR COMMON AREAS
 ETC.
2005-12-27 00:00:00***************************************
 ************** UNSAT ***************
  
 ** HILTON GARDENS **
  
 ** PLEASE KNOW, PLANS ONLY SUBMITTED FOR
 "PLAN REVIEW ONLY" AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE BLDG REVIEW COMMENTS AS
 THIS PROJECT MAY REQUIRE A THIRD SET OF
 PLANS
  
  
 1)NOTE: PLEASE BE SURE PLANS REFERENCE
 CURRENT CODES IN EFFECT.
 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002
 NFPA-72 ETC
  
 2)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 DOORS WILL BE REQUIRED TO OPEN OUTWARD
 AND SHALL HAVE PANIC HARDWARE.
 110.26
  
 3)NOTE: PLEASE BE SURE ALL ELECTRICAL
 RMS, ELEVATOR EQUIPMENT RMS CONTAIN A
 BATTERY BACK UP LIGHT OF SOME SORT.
 LS101 7.8,7.9, 700.16
  
 4)NOTE: PLEASE SEE ELECTRICAL RMS ON
 EACH FLOOR MAY NOT CONTAIN AREA FOR
 "HOUSEKEEPING/STORAGE.
 PLEASE SEE SHEETS E-5- E7 WHICH WOULD BE
 ACCEPTABLE BY PLACING A WALL BETWEEN
 THIS AREA ELECTRICAL ROOM WITH A
 SEPARATE ENTRANCE/DOOR.
 110.26, 407.7, 240.24
  
 5)NOTE: PLEASE SEE FIRST FLR CIRCUTING
 FOR HALL RECEPTS, SOME SHOWN AND SOME
 MISSING. PLEASE COMPLETE.
 THERE IS A NOTE ON PLANS, WHICH MENTIONS
 HALL RECEPTS TO BE CIRCUITED TO NEAREST
 GUEST RM, HOWEVER THIS CIRCUIT NEEDS TO
 BE SHOWN.
  
 6)NOTE: PLEASE COMPLETE ALL OTHER
 CIRCUITING, GUEST RMS ETC.
 215.5
  
 7)NOTE: PLEASE SEE ELECTRICAL EQUIPMENT
 LOCATED ON WALL NEXT TO POOL APEARS TO
 BE LOCATED TOO CLOSE WHICH DOES NOT MEET
 MIN CLEARENCES PER 680.22
  
 8)NOTE: PLEASE SEE 620.23, 620.24 WHICH
 REQUIRES A DEDICATED BRANCH CIRCUIT FOR
 RECEPTS AND LTS FOR ELEVATOR EQUIPMENT
 RMS AND ANY ELEVATOR PITS.
  
 9)NOTE: PLEASE SUBMIT COMPLETE
 PHOTOMETRICS FOR ALL COMMON AREAS, AND
 STAIR TOWERS.
 PLEASE SEE 2003 NFPA-1017.8.1.3 WHICH
 REQUIRES A MIN OF 1 FT CANDLEAND A MIN
 OF 10FT CANDLES ON THE WALKING SURFACE
 UNDER NORMAL POWER. PLEASE SEE7.9.2.1
 WHICH REQUIRES A MIN OF 1FT CANDLE OF
 LIGHTING ON ALL WALKING SURFACES UNDER
 EMERGENCY CONDITIONS.
  
 10)NOTE: PLEASE SEE PHOTOMETRICS SHOWN
 FOR POOL AREA SHALL BE SUBMITTED TO PALM
 BEACH COUNTY HEATH DEPARTMENT FOR ANY
 AFTER DUSK SWIMMMING.
 IF THERE IS NOT GOING TO BE ANY SWIMMING
 FROM DUSK TO DAWN, PLEASE PROVIDE A NOTE
 ON PLAN FOR REQUIRED SIGNAGE TO BE PLACE
 AT AND IN POOL AREA.
 ** PLEASE KNOW, THE SWIMMING POOL ITSELF
 WILL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT.
  
 11)NOTE: PLEASE CLARIFY NOTE ON PLANS
 FOR THE REQUIREMENTS OF GUEST BATH GFI.
 THIS CAN NOT BE VERIFIED AT THIS TIME
 DUE TO MISSING CIRCUITING.
  
 12)NOTE: PLEASE SEE 210.60 FOR REQUIRED
 RECEPT SPACING FOR GUEST RMS OF HOTELS
 WHICH REFERENCES 210.52 FOR MIN SPACING.
 PLEASE SEE THERE IS AN EXCEPTION TO THE
 MIN SPACING AS TO PROVIDE RECEPTS FOR
 FURNITURE PLANS, HOWEVER THE NUMBER OF
 RECEPTS TO BE PROVIDED SHALL MEET THE
 SAME NUMBER OF RECEPTS IF THEEY WERE
 INSTALLED PER 210.52
 PLEASE SEE MANY GUEST RM TYPES WHICH ARE
 MISSING THE REQUIRED NUMBER.
 PLEASE SEE MOSTOF THESE UNTIS ARE
 REDLINED ON ONE SET OF PLANS.
 KING,2,5 6,7,KING SUITE ETC. PLEASE KNOW
 THAT NOT ALL UNITS WERE REDLINED, PLEASE
 BE SURE TO GO OVER THE MIN.
 PLEASE KNOW THAT A MIN OF TWO RECEPTS
 SHALL BE READILY ACCESSIBLE AT ALL
 TIMES.
 MOST UNITS MEET THIS , HOWEVER A COUPLE
 ARE MISSING.
  
 13)NOTE: PLEASE PROVIDE A NOTE ON THE
 ROOOFTOP PLAN WHICH SHOULD NOTE/MENTION:
 ANY PROPOSED LIGHTNING PROTECTION SYSTEM
 SHALL MEET NFPA-780, OR WORDS TO THAT
 AFFECT.
 IT IS NOTED THAT NO SYSTEM IS SHOWN AT
 THIS TIME, AND ANY FUTURE WOULD BE UNDER
 A SEPARATE PERMIT, HOWEVER A NOTE IS
 REQUIRED AT THIS TIME.
  
 14)NOTE:PLEASE SEE PANEL "K" IS SHOWN
 LISTING A 125A OCP TO FEED TO PANEL
 "KA", HOWEVER PANEL "KA" IS ONLY REATED
 AT 100A'S?
 PLEASE CORRELATE AND ADJUST.
 215.5,
  
 15)NOTE: PLEASE SEE PANEL "LDY" IS SHOWN
 AS A 100A MLO, YET MSB SHOWS A 225A
 BRKR/OCP FEEDING THIS PANEL.
 PLEASE ADJUST AND CORRELATE.
 215.5
  
 16)NOTE: PLEASE SEE PANEL "L" IS SHOWN
 AS 100A MLO, WITH MSB SHWOING 150A OCP
 FEEDING THIS PANEL.
 PLEASE ADJUST AND CORRELATE.
 215.5
  
 17)NOTE: PLEASE SEE RISER AND MSB SHOWS
 ALL 1H1, 2H2, 3H3 ETC AS 1H, 2H, 3H ETC
 ON PANEL SCHEDULES FOR THESE.
 PLEASE CORRELATE THE IDENTIFICATION OF
 THESE.
 215.5
  
 18)NOTE: PLEASE SEE 240.4C, WHICH
 REQUIRES THE CONDUCTOR FEEDING DEVICES
 RATED OVER 800A'S TO MEET OR EXCEED
 RAITNG OF SUCH DEVICE.
 PLEASE SEE MSB OS SHOWN AS A 3000A MAIN
 , HOWEVER CONDUCTORS ARE ONLY RATED FOR
 2100 A'S?
 5-SETS OF 600MCM, RATED @420A'S EACH.(75
 DEGREE COL).
 110.14, 215.5,215.3
 PLEASE ADJUST ON MORE THAN ONE SHEET,
 SEE 13,14.
  
 19)NOTE: PLEASE ALSO SEE CONDUCTORS FOR
 MAIN FEEDERS TO CHILLER FROM MSB.
 PLEASE SEE MSB SHOWS 3-300 MCM, HOWEVER
 PLEASE SEE CALCUALTIONS FOR CHILLER
 WHICH INDICATE 2-600'S.
 PLEASE CORRELARE. 215.5
  
 20)NOTE: PLEASE SEE RISER INDICATES
 "BLDG STEEL" AS PART OF THE GROUNDING
 ELECTRODE SYSTEM, WHICHIS OK AND IS
 REQUIRED IF "BLDG STEEL" IS PRESENT.
 PLEASE ALSO INCLUDE THE REQUIRED "FOOTER
 STEEL" IN DETAIL.
 250.50
  
 21)NOTE: PLEASE KNOW, THE REQUIRED WIND
 LOAD CALCULATIONS FOR LT POLES WITH
 FIXTURES ON THEM ARE REQUIRED AT THIS
 TIME.
 PLEASE KNOW, THESE WILL BE REVIEWED BY A
 STRUCTUAL PLANS REVIEWER.
 IF THIS INFORMATION IS NOT SUBMITTED AT
 THIS TIME, ALL SITE LIGHTING WOULD BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT,
 WITH SEPARATE PLANS AND FEES.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE SEE ONE SET OF ELECTRICAL
 PLANS HAVE MANY OF THE ABOVE ITMES
 REDLINED IN LOCATIONS FOR NOTES.
 IE,FLR ELEC RMS, RECEPTS ETC.
  
 ** PLEASE REMOVE ALL OLD/VOIDED
 ELECTRICAL PAGES AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
 19)NOTE: PLEAS
2005-12-26 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.
 PLANS WILL GO INTO "F" STATUS.
 REVIEW IN PROGRESS, NOTES TO FOLLOW.