2006-02-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110263
 ADD: LOT# 7 CENTERPARK WEST
 CONT: "PLAN REVIEW" HILTON
 JOHN COSTAS
 TEL: (561)523-3699
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 ***IMPORTANT***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE NOC WILL BE NULL & VOID 90 DAYS
 AFTER RECORDING AT THE CLERK OF THE
 COURTS OFFICE IF WORK HAS NOT STARTED.
 FL S S 713.13(2).
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 5) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
 THIS STATEMENT IS FOUND ON THE
 STRUCTURAL SHEETS BUT NOT THE
 ARCHITECTURAL SHEETS.
  
 7A) CONTACT LILI URSA FOR ADDRESSING
 REQUIREMENTS @ (561)822-1239
  
 7B)PROVIDE A COPY OF THE NEW PLAT, SHEET
 SP.01 APPEARS TO HAVE BEEN SUBDIVIDED
 WITH ADDITIONAL BUILDINGS TO BE ON THE
 SAME LOT.
  
 7C) PLEASE FILL OUT AN ACTUAL
 APPLICATION SHEET PROVIDING THE PROPERTY
 CONTROL NUMBER FOR ADDRESSING.
  
 7D) PROVIDE A SURVEY OF THE SITE.
  
 8) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 106.1.2*:
 8)A) FLOOD ZONE
 8)B) FLOOD ELEVATION (IF A ZONE)
 8)C) LOMAR (IF A ZONE)
 8)D) NUMBER OF UNITS
 8)E) NUMBER OF FLOORS
 8)F) NUMBER OF BEDROOMS
 8)G) NUMBER OF ROOMS
 8)H) NUMBER OF BATHROOM
 88)I) SQ FT LIVING SPACE(TOTAL)
 8)J) SQ FT FOOT PRINT
 8)K) SQ FT UNDER ROOF (TOTAL)
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10) SINCE THISWILL BE A THRESHOLD
 PROJECT (3) SETS OF ALL INFORMATION
 SUBMITTED WILL BE REQUIRED.
  
 11) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS NO WINDOW SCHEDULE ON INDEX
 SHEET
 B) EXTERIOR DOORS, SOLID
 C) EXTERIOR DOORS GLAZED
 D) EXTERIOR DOORS BYPASS
 E) MULLIONS
 F) LOUVERS
 G) TRUSS ANCHORS
 H) ROOF ASSEMBLIES, FLAT AND TILE
 I) PREMANUFACTURED A/C STANDS
  
 14) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 15) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 16) SHEET SP. 01
 16A) INDICATES THAT THE TOTAL REQUIRED
 PARKING SPACES OF 118 PARKING SPOTS.
 PLANS ONLY INDICATE (4)
 ACCESSIBLE PARKING STALLS, 11-4.1.2(5)
 IF TOTAL PARKING SPOTS ARE BETWEEN 101
 TO 150 THEN THE MINIMUM NUMBER ODF
 ACCESSIBLE SPACES ARE 5.
  
 16B) THIS SHEET NOR A.01 INDICATE
 CLEARLY THE PASSENGER LOADING ZONE UNDER
 THE CANOPY PLEASE CLARIFY THE PASSENGER
 LOADING ZONE, 11-4.6.6 PASSENGER LOADING
 ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN
 ACCESS AISLE AT LEAST 60 INCHES (1525
 MM) WIDE AND 20 FEET (6096 MM) LONG
 ADJACENT AND PARALLEL TO THE VEHICLE
 PULL-UP SPACE (SEE FIGURE 11-10 ). IF
 THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A
 CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL
 WITH SURFACE SLOPES NOT EXCEEDING 1:50
 (2 PERCENT) IN ALL DIRECTIONS.
  
 17) SHEET SP.02 REFLECTING POOL PROVIDE
 A CROSS SECTION OF THIS SITE AMENITY,
 11-4.29.6 DETECTABLE WARNINGS AT
 REFLECTING POOLS. THE EDGES OF
 REFLECTING POOLS SHALL BE PROTECTED BY
 RAILINGS, WALLS, CURBS, OR DETECTABLE
 WARNINGS COMPLYING WITH 11-4.29.2.
  
 18)SHEET SP.03, NOTE: POOL,
 SEE DEPARTMENT OF HEALTH FOR REGULATIONS
 FOR POOL SAFETY FENCE, RULE 64E-9.
  
 19)SHEET A.01:
  
 19A) LAUNDRY CHUTE TERMINATION ROOM &
 DOOR 48ATO MEET THE REQUIREMENTS OF ,
 707.13.4 TERMINATION ROOM.
 REFUSE AND LAUNDRY CHUTES SHALL
 DISCHARGE INTO AN ENCLOSED ROOM
 COMPLETELY SEPARATED FROM THE REMAINDER
 OF THE BUILDING BY CONSTRUCTION THAT HAS
 A FIRE-RESISTANCE RATING OF NOT LESS
 THAN 1 HOUR AND OPENINGS INTO THE
 TERMINATION ROOM SHALL BE PROTECTED BY
 OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN ?
 HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE. REFUSE CHUTES SHALL NOT TERMINATE
 IN AN INCINERATOR ROOM. REFUSE AND
 LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH
 CHUTES NEED ONLY COMPLY WITH TABLE
 302.1.1 .
  
 19B) 707.13.3 REFUSE AND LAUNDRY CHUTE
 ACCESS ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY
 CHUTES SHALL BE LOCATED IN ROOMS OR
 COMPARTMENTS COMPLETELY ENCLOSED BY
 CONSTRUCTION THAT HAS A FIRE-RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR AND
 OPENINGS INTO THE ACCESS ROOMS SHALL BE
 PROTECTED BY OPENING PROTECTIVES HAVING
 A FIRE PROTECTION RATING OF NOT LESS
 THAN ? HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
  
 19C) PROVIDE A 2 HR SHAFT TO SURROUND
 THE LAUNDRY CHUTE, 707.4 FIRE-RESISTANCE
 RATING. SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN
 2 HOURS WHERE CONNECTING FOUR STORIES OR
 MORE AND NOT LESS THAN1 HOUR WHERE
 CONNECTING LESS THAN FOUR STORIES. THE
 NUMBER OF STORIES CONNECTED BY THE SHAFT
 ENCLOSURE SHALL INCLUDE ANY BASEMENTS
 BUT NOT ANY MEZZANINES. SHAFT ENCLOSURES
 SHALL BE CONSTRUCTED AS FIRE BARRIERS IN
 ACCORDANCE WITH SECTION 706 . SHAFT
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE
 RATING NOT LESS THAN THE FLOOR ASSEMBLY
 PENETRATED, BUT NEED NOT EXCEED 2 HOURS.
  
  
 19D) 707.13.6 AUTOMATIC FIRE SPRINKLER
 SYSTEM. AN APPROVED AUTOMATIC FIRE
 SPRINKLER SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 903.2.10.2 .
  
 19E) PROVIDE A LIFE SAFETY PLAN FOR
 EXITING. PROVIDE THE LOADS FROM THE
 FLOORS ABOVE AS WELL AS THE FIRST FLOOR.
 TABLE 1004.1.2/ TABLE 1005.1.
  
 19F) MEETING ROOM # 34 OCC LOAD OF 96,
 24X28=672/7= 96 OCC LOAD.1014.1 EXIT OR
 EXIT ACCESS DOORWAYS REQUIRED.
  
 19G)TWO EXITS OR EXIT ACCESS DOORWAYS
 FROM ANY SPACE SHALL BE PROVIDED WHERE
 ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1014.1.(1)THE OCCUPANT LOAD OF THE
 SPACE EXCEEDS THE VALUES IN TABLE 1014.1
 .
  
 19H) BREAAKFAST AREA, THIS SHEET AND
 A.15 TO INDICATE COMPLIANCE WITH:
 11-5.1- 11-5.6.
  
 19I) INDICATE COMPLIANCE WITH: 11-9.3
 VISUAL ALARMS, NOTIFICATION DEVICES AND
 TELEPHONES. 11-9.3.1 GENERAL.
 IN SLEEPING ROOMS REQUIRED TO COMPLY
 WITH THIS SECTION, AUXILIARY VISUAL
 ALARMS SHALL BE PROVIDED AND SHALL
 COMPLY WITH SECTION 11-4.28.4 . VISUAL
 NOTIFICATION DEVICES SHALL ALSO BE
 PROVIDED IN UNITS, SLEEPING ROOMS AND
 SUITES TO ALERT ROOM OCCUPANTS OF
 INCOMING TELEPHONE CALLS AND A DOOR
 KNOCK OR BELL.
 NOTIFICATION DEVICES SHALL NOT BE
 CONNECTED TO AUXILIARY VISUAL ALARM
 SIGNAL APPLIANCES. PERMANENTLY INSTALLED
 TELEPHONES SHALL HAVE VOLUME CONTROLS
 COMPLYING WITH SECTION 11-4.31.5 ; AN
 ACCESSIBLE ELECTRICAL OUTLET WITHIN 4
 FEET (1219 MM) OF A TELEPHONE CONNECTION
 SHALL BE PROVIDED TO FACILITATE THE USE
 OF A TEXT TELEPHONE.
  
 20) SHEET A.02- A.04:
  
 20A) PLANS INDICATE NEXT TO THE ELEVATOR
 A SHAFT BUT NO DETAILS TO HR
 CONSTRUCTION OR WHAT IT WILL BE USED
 FOR?707.4.
  
 20B) PLANS ALSO INDICATE A SHAFT NEXT TO
 THE ELEVATOR SHAFT NO CUT SECTION?
 USAGE?
  
 21) SHEET A.20 & A.21 BOTH INDICATE
 STAIR TOWWERS BUT NO DETAIL SHEET
 INDICATING THE HANDRAIL GUARD RAIL
 COMPLYING WITH 11-4.9.4(2)IF
 HANDRAILS ARE NOT CONTINUOUS, THEY SHALL
 EXTEND AT LEAST 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND AT LEAST 12
 INCHES (305 MM) PLUS THE WIDTH OF ONE
 TREAD BEYOND THE BOTTOM RISER. AT THE
 TOP, THE EXTENSION SHALL BE PARALLEL
 WITH THE FLOOR OR GROUND SURFACE. AT THE
 BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE
 TREAD FROM THE BOTTOM RISER; THE
 REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 11-19 (C) AND
 FIGURE 11-19 (D)]. HANDRAIL EXTENSIONS
 SHALL COMPLY WITH SECTION 11-4.4 .
 DETAILS ON A.15 ARE MISSING.
  
 22) SHEET A.23:
  
 22A) PLANS INDICATE THE USE OF A PREFAB
 FIREPLACE AND FLUE SUBMIT ADDITIONAL
 INFORMATION:
  
 22B) MISSING SECTIONS ON A.24A DETAILS
 1-4. NOTE DETAIL 3 IS USED IN THE
 CLEARSTORY AS WELL AS COMMEON TRUSS
 DETAIL FOR HIP END. CORRECT.
  
 22C) SUBMIT STRUCTURAL PLANS INDICATING
 HOW TO BUILD THE SURROUND AROUND THE
 PREFAB FLUE?
  
 22D) THIS IS A FOUR STORY BUILDING, SHOW
  
 PRODUCT APPROVAL REPORT WHERE SHINGLES
 WILL BE ABLE TO BE USED WITH A MEAN ROOF
 HEIGTH OF OVER 40'-0"?
  
 23) SHEET A.25 DOOR SCHEDULE:
  
 23A) DOOR SCHEDULE DOESN,T INDICATE ANY
 HARDWARE FOR FIRE RATED DOORS, PLEASE
 SEE SECTION:715.3.3 FOR REQUIRED
 HARDWARE INCLUDING CLOSERS AND
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS
 THE BOTTOM OF THE DOOR TESTED IN
 ACCORDANCE WITH UL 1784.
  
 B) LOUVERS ARE OROHIBITED IN FIRE RATED
 DOORS.
  
 24) A.27WALL TYPE 11A PROVIDE A DESIGN
 NUMBER FOR 2 HR RATED SHAFT DESIGN
  
 25) A.34 PUBLIC RESTROOMS:1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 26) S3.1, A.23 NO DETAILS INDICATE THE
 TYPE OF MATERIAL TO BE USED FOR ROOF
 SHEATHING. PLANS ALSO DO NOT PROVIDE THE
 MINIMUM BUILDING DESIGN TABLE 503/ 601.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  