2006-10-03 00:00:00*****BECAUSE OF THE SYSTEM LIMITIONS,
 THE SECOND REVIEW NOTES WILL BE SPLIT UP
 INTO TWO REVIEW STOPS. THE FOLLOWING IS
 THE COMMENTS FROM THE SECOND REVIEW.
  
 DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA- 98DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY MUNICIPAL CODE WPB
  
 *************NEW COMMENTS**************
  
 1B. SHTS P2-00 & P2-01 NO CD/5 SHOWN.
 PLEASE CORRELATE RISER WITH FLOOR PLAN.
 SECTION 104.2.1.
  
 2B. SHT P2-02B NO SECONDARY DRAINS
 SHOWN. - NO DRAINAGE SHOWN IN THE TENNIS
 COURT AREA, NOR IN THE AMENITY DECK AREA
 AS REQUIRED IN SECTIONS 1101.2, 1107.1,
 1107.2 & 1107.3.
  
 3B. SHT P2-02B 3 DRAINS SHOWN ARE NOT
 REFLECTED ON THE RISER DIAGRAM. PLEASE
 CORRELATE DRAINS WITH RISER DIAGRAM.
 SECTION 104.2.1.
  
 4B. SHT P2-02B TOTAL AREA OF TERRACE
 LEVEL DOES NOT APPEAR TO BE SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
  
 5B. TWO CD/5 RISERS SHOWN. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 6B. SHT P4-00 RISER SV1 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR UNDERGROUND.
 SV1 ON THE FLOOR PLAN FOR ONE RISER
 SHOWS AN OFFSET, BUT ANOTHER SV1 ON THE
 FLOOR PLAN DOES NOT SHOW AN OFFSET. THE
 RISER DOES NOT REFLECT THE FLOOR PLAN
 AFTER THE OFFSET. RISERS SHALL BE
 SPECIFIC TO THE FLOOR PLAN. DIFFERENT
 FLOOR PLANS REQUIRE DIFFERENT RISERS.
 SECTION 104.2.1.
  
 7B. SHT P4-00 RISER SV2 DOES NOT REFLECT
 THE FLOOR PLAN FOR THE 1ST FLOOR
 UNDERGROUND. CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
  
 8B. SHT P4-00 RISER SV3 DOES NOT REFLECT
 THE FLOOR PLAN. ALSO OFFSET ON ONE FLOOR
 PLAN RISER BUT NOT THE OTHER. OFFSET
 PIPING AND PIPING FOR 12 THRU 16 FLOORS
 DO NOT REFLECT THE FLOOR PLAN. CORRELATE
 RISER AND FLOOR PLAN. SECTION 104.2.1.
  
 9B. SHT P4-00 RISER SV4 DOES NOT REFLECT
 THE FLOOR PLAN. CORRELATE THE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 10B. SHT P4-00 SV5 DOES NOT REFLECT THE
 FLOOR PLAN. SOME ALSO SHOW TUBS WHILE
 THE OTHERS SHOW SHOWERS. OFFSET PIPING
 ONLY SHOWN ON THE FLOOR PLAN FOR ONE.
 PIPING AFTER THE OFFSET DOES NOT REFLECT
 THE FLOOR PLAN. CORRELATE RISER AND
 FLOOR PLANS. SECTION 104.2.1.
  
 11B. SHT P4-00 RISER SV6 2ND THRU 5TH
 FLOORS NOT PIPED THE SAME ON ALL FLOOR
 PLANS. 2 FLOOR PLANS RELFECT THE FLOOR
 PLAN, BUT THE OTHER DOES NOT. TYPICAL
 RISERS DO NOT WORK AS THE FLOOR PLANS
 ARE DIFFERENT. RISER SHALL REFLECT THE
 FLOOR PLAN. SECTION 104.2.1.
  
 12B. SHT P4-00A SV7 DOES NOT REFLECT THE
 OFFSET ON THE FLOOR PLAN, AND IS NOT
 SHOWN ON THE FIRST FIVE FLOORS.
 CORRELATE THE RISER AND THE FLOOR PLAN.
 SECTION 104.2.1.
  
 13B. SHT P4-00A TWO SV9 RISERS SHOWN.
 NEITHER INDICATE A FIRST FLOOR BATHROOM.
 ONE FLOOR PLAN SV9 SHOWS A BATHROOM.
 DOES NOT REFLECT THE FLOOR PLAN AT
 OFFSET. PLEASE CLARIFY. SECTION 104.2.1.
  
 14B. SHT P4-00A SV10 IS NOT INDICATED ON
 THE FLOOR PLAN OF SHT P2-00 AND DOES NOT
 REFLECT THE FLOOR PLAN AT THE OFFSET.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 15B. SHT P4-00A SV12 OFFSET ON FLOOR
 PLAN NOT SHOWN ON THE RISER DIAGRAM.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 16B. SHT P4-00B SV13 DOES NOT REFLECT
 THE FLOOR PLAN AT THE FIRST FLOOR
 UNDERGROUND, AND VENT NOT SHOWN ON THE
 11TH THRU 16TH FLOOR. FLOOR PLAN SHOWS
 ONE SV13 CONNECTING TO SHOWER DRAIN.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 17B. SHT P4-00B SV14 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR UNDERGROUND.
 ONE FLOOR PLAN SHOWS NO FIXTURES THRU
 THE FIRST FIVE FLOORS. DOES NOT REFLECT
 AT THE OFFSET, SHOWN AS SHOWERS ON FLOOR
 PLAN 11TH THRU 16TH FLOORS FOR ONE RISER
 AND NOT SHOWN AS VTR ON ONE RISER.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 18B. SHT P4-00B SV15 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR UNDERGROUND,
 AND ONE RISER SHOWN ON THE FLOOR PLAN
 INDICATES FIXTURES ON THE FIRST FLOOR.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 19B. SHT P4-00B SV16 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR UNDERGROUND.
 FLOOR PLANS ALSO SHOWS NO FIXTURES ON
 FIRST FLOOR. CORRELATE RISER WITH FLOOR
 PLANS. SECTION 104.2.1.
  
 20B. SHT P4-00B SV17 NOT FOUND ON THE
 FIRST FLOOR PIPING LAYOUT SHT P2-00.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 21B. SHT P4-01 RISER P1 OFFSET VENTS
 REQUIRED. SECTIONS 915.2 & 915.3.
  
 22B. SHT P4-01 RISER P2 RISER SHOWS NO
 BRANCH LINE FOR 5TH FLOOR. DOES NOT
 REFLECT THE FLOOR PLAN. CORRELATE RISER
 AND FLOOR PLAN. SECTION 104.2.1.
  
 23B. SHT P4-01 RISER P3 REFLECTS ONE
 FLOOR PLAN BUT NOT THE OTHER. FLOOR
 PLANS ARE NOT TYPICAL. SEPARATE RISERS
 REQUIRED. SECTION 104.2.1.
  
 24B. SHT P4-01 RISER P4 CHANGES TO P15
 ONE FLOOR PLAN FOR ONE P4. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 25B. SHT P4-01 RISER P5 DOES NOT REFLECT
 THE FLOOR PLAN 1ST FLOOR. CORRELATE THE
 RISER AND THE FLOOR PLAN. SECTION
 104.2.1.
  
 26B. SHT P4-01 RISERS P7, (10), SOME
 DIFFER FROM OTHERS. SOME DO NOT SHOW
 FIXTURES ON THE FIRST FLOOR. RISER CAN
 NOT BE TYPICAL IF FLOOR PLAN IS NOT THE
 SAME. PLEASE CORRELATE RISERS TO FLOOR
 PLAN. SECTION 104.2.1.
  
 27B. SHT P4-01 RISER P8 ONE RISER STARTS
 ON THE 1ST FLOOR AND IS NOT SHOWN ON THE
 6TH FLOOR & OFFSET DOES NOT REFLECT THE
 FLOOR PLAN. CORRELATE RISER AND FLOOR
 PLANS. SECTION 104.2.1.
  
 28B. SHT P4-01 RISER P9 RISER DOES NOT
 REFLECT THE FLOOR PLAN ON ONE 1ST THRU
 5TH FLOORS NO FIXTURE BRANCH. NOT SHOWN
 ABOVE THE 5TH FLOOR AT ALL ON ONE FLOOR
 PLAN. CORRELATE RISER AND FLOOR PLANS.
 SECTION 104.2.1.
  
 29B. SHT P4-01A RISER P15 CHANGES TO P4
 ON SHT P2-01. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 30B. SHT P4-01A RISER P17 DOES NOT
 REFLECT THE FLOOR PLAN AT THE FIRST
 FLOOR. CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 31B. SHT P4-01B RISER P18 NOT INDICATED
 ON FLOORS 1 THRU 5. CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 32B. SHT P4-01B RISER P20 OFFSET VENTS
 REQUIRED. SECTIONS 915.2 & 915.3.
  
 33B. SHT P4-02 RISER 11 DOES NOT REFLECT
 THE FLOOR PLAN 6TH FLOOR. OFFSET NOT
 SHOWN. CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 34B. SHT 4-02 RISER 1/2 DOES NOT REFLECT
 THE FLOOR PLAN 1ST & 2ND FLOORS.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 35B. SHT P4-02 RISER CONNECTIONS TO THE
 MAIN FOR RISERS 9/10 & 11 DO NOT REFLECT
 THE FLOOR PLAN. CORRELATE THE RISER AND
 THE FLOOR PLAN. SECTION 104.2.1.
  
 36B. SHT P4-02 RISER CONNECTIONS TO MAIN
 FOR RISERS 17, 18/19, & 20/21 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE
 RISERS AND FLOOR PLAN. SECTION 104.2.1.
  
 37B. SHT P4-03 RISER 18/19 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE
 THE FLOOR PLAN AND RISERS. SECTION
 104.2.1.
  
 38B. SHT P4-03 RISER 20 DOES NOT REFLECT
 THE FLOOR PLAN 7TH THRU 10TH FLOORS.
 OFFSET NOT SHOWN. CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 39B. SHT P4-03 RISER 20/21 DOES NOT
 REFLECT THE FLOOR PLAN 1ST THRU 6TH
 FLOORS. CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
  
 40B. SHT P4-04 RD4 RISER DOES NOT
 REFLECT THE FLOOR PLAN. OFFSETS NOT
 SHOWN. CORRELATE THE RISER WITH THE
 FLOOR PLAN. SECTION 104.2.1.
  
 41B. SHT P4-04 RD6 RISER DOES NOT
 REFLECT THE FLOOR PLAN. OFFSET NOT
 SHOWN. CORRELATE THE RISER AND THE FLOOR
 PLAN. SECTION 104.2.1.
  
 42B. SHT P4-04 RD16 RISER DOES NOT
 REFLECT THE FLOOR PLAN. OFFSET NOT
 SHOWN. CORRELATE THE RISER AND THE FLOOR
 PLAN. SECTION 104.2.1.
  
 43B. SHT P4-05 CD RISER #5 DOES NOT
 REFLECT THE FLOOR PLAN 11TH FLOOR AND
 ABOVE. CORRELATE RISER AND FLOOR PLANS.
 SECTION 104.2.1.
  
 44B. SHT P4-05 CD RISER #2 DOES NOT
 REFLECT THE FLOOR PLAN AT THE 11TH
 FLOOR. OFFSET NOT SHOWN. CORRELATE RISER
 WITH FLOOR PLAN. SECTION 104.2.1.
  
 45B. SHEETS FOR ALL FLOOR PLANS. KEYED
 NOTES ARE NOT SHOWN ON ALL FLOOR PLANS.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 46B. SHT PO-01 CODE REFERENCE TO
 IBC-2000 AND INTERNATIONAL ENERGY
 CONSERVATION CODE 2000 DO NOT APPLY.
 ADOPTED CODE IS THE FBC-2001 PLUMBING
 CODE ONLY. DELETE OTHER REFERENCES.
  
 47B. SHT PO-01 HORIZONTAL STORM DRAINAGE
 PIPING REFERENCES FBC-2004. ADOPTED CODE
 IS FBC-2001.
  
 48B. SHT P2-00 INDICATES SV19 RISER ON
 THE FLOOR PLAN. NO SV19 RISER SUBMITTED.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 49B. SHT P2-00KEYED NOTE #1 HAS BEEN
 CHANGED TO NOTE #3 ON THE FLOOR PLAN AND
 NOTE #3 DOES NOT APPLY. PLEASE CORRELATE
 KEYED NOTES WITH INFORMATION INDICATED
 ON THE FLOOR PLAN. SECTION 104.2.1.
  
 50B. SHT P2-00 THE PIPE SIZE FOR THE
 STORM SYSTEM IS INCORRECT IN SOME
 PLACES. RECHECK ALL PIPE SIZES PER TABLE
 1106.3.
  
 51B. SHT P2-00 NOT ALL KEYED NOTES SHOWN
 ON THE FLOOR PLAN REFLECT THE FLOOR
 PLAN. (EXAMPLE, KEYED NOTE #2 ON THE
 FLOOR PLAN SHOWS A CONDENSATE LINE
 OFFSET, BUT THE KEYED NOTED IN THE INDEX
 STATES "4" STORM DOWN FROM TERACE
 ABOVE"). PLEASE CORRELATE KEYED NOTES
 WITH INFORMATION INDICATED ON THE FLOOR
 PLAN.
  
 52B. SHT P2-01 INDICATES 2ND THRU 5TH
 FLOORS. THERE ARE OFFSETS SHOWN ON THE
 FLOOR PLAN. ARE THESE OFFSETS TYPICAL
 FOR ALL FLOORS? IF NOT THEN FLOOR PLANS
 THAT ARE NOT TYPICAL SHALL BE SUBMITTED
 INDIVIDUALLY AND NOT SHOWN AS TYPICAL.
 (SEE KEYED NOTE #8, "ROUTE PIPING
 SUSPENDED FROM CEILING ON THIS LEVEL".
 LEVEL NOT INDICATED)PLEASE CLARIFY.
 SECTION 104.2.1.
  
 53B. SHT P2-01 SV9 SHOWN IN THE BLOCK
 WALL FOR STAIRWELL #1. PLEASE INDICATE
 HOW THE FIRE RATING WILL BE MAINTAINED
 FOR THE STAIRWELL. ALSO SHOW COMPLIANCE
 WITH SECTIONS 1907.3, 1907.4,
 1907.5(1)(3), AND 1907.3.6(3). SUBMIT A
 DETAIL.
 SECTION 104.2.3.
  
 54B. SHT P2-01 NOT ALL KEYED NOTES SHOWN
 ON THE FLOOR PLAN REFLECT THE FLOOR
 PLAN. (EXAMPLE, KEYED NOTE #2 STATES
 "OFFSET 2" SANITARY DRAIN" AND IS
 INDICATED ON A CONDENSATE LINE).
 CORRELATE KEYED NOTES AND FLOOR PLAN.
 SECTION 104.2.1.
  
 55B. SHT P2-01 SHEET APPEARS TO BE
 INCOMPLETE. SHOW A MATCH LINE AND
 INDICATE WHERE THE REST OF THE FLOOR
 PLAN CAN BE LOCATED, OR SUBMIT A SHEET
 THAT IS 100% COMPLETE. SECTION 104.2.1.
  
 56B. SHT P2-01 RD11 SHOWS AN OFFSET ON
 THE FLOOR PLAN THAT IS NOT REFLECTED ON
 THE RISER DIAGRAM. PLEASE CORRELATE THE
 RISER WITH THE FLOOR PLAN. SECTION
 104.2.1.
  
 57B. SHT P2-01 RISER 8, 9, 10 DOES NOT
 INDICATE WHERE THE RISER ROUTES DOWN TO
 THE FLOOR BELOW. PLEASE CLARIFY SECTION
 104.2.1.
  
 58B. SHT P2-01B RECHECK PIPE SIZING AS
 SOME SIZING IS INCORRECT. ALSO SOME AREA
 DRAINS ARE SHOWN AS PLANTER DRAINS AND
 SOME PLANTER DRAINS ARE SHOWN AS AREA
 DRAINS. CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1 AND TABLE 1106.3.
  
 59B. SHT P2-01B SHOW THE SF OF EACH
 DRAIN AND INDICATE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. TABLE 1106.3.
  
 60B. SHT P2-02 CD5 SHOWN ON FLOOR PLAN
 WAS NOT SHOWN ON FLOORS 1 THRU 5.
 INDICATE WHERE CD5 TERMINATES. SECTION
 104.2.1.
  
 61B. SHT P2-02B THREE PLANTER DRAINS
 SHOWN ON THE FLOOR PLAN ARE NOT SHOWN
 ON THE RISER DIAGRAM. CORRELATE THE
 RISER AND THE FLOOR PLAN. SECTION
 104.2.1.
  
 62B. SHT P2-02B NO DRAINAGE IS SHOWN FOR
 THE AMENITY DECK AREA NOR FOR THE TENNIS
 COURT AREA AS REQUIRED BY SECTION
 1101.2. PLEASE CLARIFY.
  
 63B. SHT P2-02B SHOW THE LOCATION FOR
 ALL REQUIRED SECONDARY ROOF DRAINS, AND
 INDICATE THE SIZE. SECTIONS 1107.1,
 1107.2, & 1107.3.
  
 64B. SHT P2-03 IS FOR FLOORS 7 THRU 10.
 THERE ARE OFFSETS SHOWN ON THE FLOOR
 PLAN. ARE THESE OFFSETS FOR EACH FLOOR?
 IF NOT THE FLOORS CAN NOT BE TYPICAL,
 AND INDIVIDUAL SHEETS ARE REQUIRED FOR
 EACH FLOOR THAT IS NOT TYPICAL. SECTION
 104.2.1.
  
 65B. SHT P2-03 KEYED NOTES DO NOT
 REFLECT WHERE THEY ARE APPLIED ON THE
 FLOOR PLAN. CORRELATE KEYED NOTES AND
 THE FLOOR PLAN. SECTION 104.2.1.
  
 66B. P2-05 IS FOR SHEETS 12, 14 THRU 16.
 THERE ARE OFFSETS SHOWN ON THE FLOOR
 PLAN, AND VENTS CONNECTING TO EACH OTHER
 AND VENTING THRU THE ROOF. ARE THESE
 OFFSETS AND VENTS CONNECTING ON EACH
 FLOOR? SEPARATE SHEETS SHALL BE
 SUBMITTED FOR FLOOR PLANS THAT ARE NOT
 TYPICAL. SECTION 104.2.1.
  
 67B. SHT P2-06 NOT ALL VENTS ARE SHOWN
 AS THRU THE ROOF. SOME VENTS CONNECTING
 WITH OTHER VENTS AS SHOWN ON SHT P2-05
 DO NOT REFLECT WHAT IS SHOWN ON P2-06.
 CORRELATE ALL VENTS AS THEY COME THRU
 THE ROOF WITH THE FLOOR BELOW. ALL VENTS
 SHALL BE SHOWN AS VTR. SECTION 104.2.1.
  
 68B. SUBMIT WATER RISER DIAGRAMS FOR ALL
 UNITS, (SHOWN ON SHTS P3-00 THRU P3-03),
 SHOWING ALL PIPE SIZES, VALVES, AND
 WATER HAMMER ARRESTORS, (REQUIRED BY
 SECTION 604.9). WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE, IN AN
 "EFFECTIVE RANGE", (NOT IN THE CEILING),
 PER PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS. SECTION 104.3.1.1.
  
 69B. SHT P4-00B RISER SV13 DOES NOT
 REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN
 ON THE FLOOR PLAN AT THE 11TH FLOOR.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 70B. SHT P4-00B RISER SV17 IS NOT SHOWN
 ON THE FIRST FLOOR. CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
  
 71B. SHT P4-01A RISER P16 DOES NOT
 REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN
 ON FLOOR PLAN. CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
  
 72B. SHT P4-03 SUBMIT WATER SUPPLY RISER
 ISOMETRIC RISER DIAGRAMS FOR TOILET
 ROOMS AND DRINKING FOUNTAIN. SECTION
 104.3.1.1. - WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 73B. SHT P4-04 ROOF DRAIN STORM WATER
 RISER. RECHECK THE PIPE SIZING, AS SOME
 SIZES ARE INCORRECT PER TABLE 1106.3. -
 RD3 SQUARE FOOTAGE DOES NOT REFLECT SF
 SHOWN ON THE ROOF PLAN.- RD-11 IS SHOWN
 AS 6", BUT IS SHOWN AS 4" ON THE ROOF
 PLAN. CORRELATE RISER WITH FLOOR PLAN.
 - RECHECK ADDITION FROM 10" (18656SF)
 AND ALL DOWNSTREAM FIGURES. SECTION
 104.2.1.
  
 74B. SHT P4-04B SOME PIPE SIZING IS
 INCORRECT. ADDITION NEEDS TO BE CHECKED
 FROM 8" (5960SF) AND DOWNSTREAM. SOME
 AREA DRAINS ARE SHOWN AS PLANTER DRAINS
 AND SOME PLANTER DRAINS ARE SHOWN AS
 AREA DRAINS. CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1 AND TABLE 1106.3.
  
 75B. SHTS P4-05 & P4-06 THE CONDENSATE
 AND EMERGENCY PAN DRAIN LINE FOR THE
 WATER HEATER SHALL NOT BE COMBINED. PAN
 DRAIN SHALL BE SEPARATE. SECTION
 504.8.2.
  
 76B. SHT P4-06 CD18 DOES NOT REFLECT THE
 FLOOR PLAN ON THE 1ST FLOOR. CORRELATE
 RISER AND FLOOR PLAN. SECTION 104.2.1.
  
  
 77B. SHT P4-06 CD15 IS NOT SHOWN ON
 FLOORS 1 THRU 5. PLEASE INDICATE WHERE
 CD15 TERMINATES. SECTION 104.2.1.
  
 78B. SHT P6-00 INDICATES TWO SUPPLY
 LINES TO RISER W17. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 79B. SUBMIT EMERGENCY PAN DRAIN LINE
 RISERS FOR THE WATER HEATERS. SHOW ALL
 PIPE SIZES, OFFSETS AND TERMINATION
 POINT. SECTION 104.3.1.1.
  
 80B. SUBMIT A HORIZONTAL ISOMETRIC RISER
 DIAGRAM FOR THE BUILDING SANITARY DRAIN.
 SHOW ALL PIPE SIZES, RISER CONNECTION
 LOCATION, IDENTIFY RISER, AND SHOW DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM.
 SECTION 104.3.1.1.
  
 81B. SHT P2-05 KEYED NOTES ON FLOOR PLAN
 BUT NO "PLUMBING KEYED NOTES INDEX"
 SUBMITTED ON THE SHEET. SUBMIT KEYED
 NOTES FOR THIS SHEET, MAKING SURE THEY
 REFLECT THE KEYED NOTES SHOWN ON THE
 FLOOR PLAN. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]