| 2006-10-03 00:00:00 | *****BECAUSE OF THE SYSTEM LIMITIONS, |
| | THE SECOND REVIEW NOTES WILL BE SPLIT UP |
| | INTO TWO REVIEW STOPS. THE FOLLOWING IS |
| | THE COMMENTS FROM THE SECOND REVIEW. |
| | |
| | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FHA- 98DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY MUNICIPAL CODE WPB |
| | |
| | *************NEW COMMENTS************** |
| | |
| | 1B. SHTS P2-00 & P2-01 NO CD/5 SHOWN. |
| | PLEASE CORRELATE RISER WITH FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 2B. SHT P2-02B NO SECONDARY DRAINS |
| | SHOWN. - NO DRAINAGE SHOWN IN THE TENNIS |
| | COURT AREA, NOR IN THE AMENITY DECK AREA |
| | AS REQUIRED IN SECTIONS 1101.2, 1107.1, |
| | 1107.2 & 1107.3. |
| | |
| | 3B. SHT P2-02B 3 DRAINS SHOWN ARE NOT |
| | REFLECTED ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE DRAINS WITH RISER DIAGRAM. |
| | SECTION 104.2.1. |
| | |
| | 4B. SHT P2-02B TOTAL AREA OF TERRACE |
| | LEVEL DOES NOT APPEAR TO BE SHOWN ON THE |
| | FLOOR PLAN. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | |
| | 5B. TWO CD/5 RISERS SHOWN. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | |
| | 6B. SHT P4-00 RISER SV1 DOES NOT REFLECT |
| | THE FLOOR PLAN 1ST FLOOR UNDERGROUND. |
| | SV1 ON THE FLOOR PLAN FOR ONE RISER |
| | SHOWS AN OFFSET, BUT ANOTHER SV1 ON THE |
| | FLOOR PLAN DOES NOT SHOW AN OFFSET. THE |
| | RISER DOES NOT REFLECT THE FLOOR PLAN |
| | AFTER THE OFFSET. RISERS SHALL BE |
| | SPECIFIC TO THE FLOOR PLAN. DIFFERENT |
| | FLOOR PLANS REQUIRE DIFFERENT RISERS. |
| | SECTION 104.2.1. |
| | |
| | 7B. SHT P4-00 RISER SV2 DOES NOT REFLECT |
| | THE FLOOR PLAN FOR THE 1ST FLOOR |
| | UNDERGROUND. CORRELATE RISER AND FLOOR |
| | PLAN. SECTION 104.2.1. |
| | |
| | 8B. SHT P4-00 RISER SV3 DOES NOT REFLECT |
| | THE FLOOR PLAN. ALSO OFFSET ON ONE FLOOR |
| | PLAN RISER BUT NOT THE OTHER. OFFSET |
| | PIPING AND PIPING FOR 12 THRU 16 FLOORS |
| | DO NOT REFLECT THE FLOOR PLAN. CORRELATE |
| | RISER AND FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 9B. SHT P4-00 RISER SV4 DOES NOT REFLECT |
| | THE FLOOR PLAN. CORRELATE THE RISER AND |
| | FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 10B. SHT P4-00 SV5 DOES NOT REFLECT THE |
| | FLOOR PLAN. SOME ALSO SHOW TUBS WHILE |
| | THE OTHERS SHOW SHOWERS. OFFSET PIPING |
| | ONLY SHOWN ON THE FLOOR PLAN FOR ONE. |
| | PIPING AFTER THE OFFSET DOES NOT REFLECT |
| | THE FLOOR PLAN. CORRELATE RISER AND |
| | FLOOR PLANS. SECTION 104.2.1. |
| | |
| | 11B. SHT P4-00 RISER SV6 2ND THRU 5TH |
| | FLOORS NOT PIPED THE SAME ON ALL FLOOR |
| | PLANS. 2 FLOOR PLANS RELFECT THE FLOOR |
| | PLAN, BUT THE OTHER DOES NOT. TYPICAL |
| | RISERS DO NOT WORK AS THE FLOOR PLANS |
| | ARE DIFFERENT. RISER SHALL REFLECT THE |
| | FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 12B. SHT P4-00A SV7 DOES NOT REFLECT THE |
| | OFFSET ON THE FLOOR PLAN, AND IS NOT |
| | SHOWN ON THE FIRST FIVE FLOORS. |
| | CORRELATE THE RISER AND THE FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 13B. SHT P4-00A TWO SV9 RISERS SHOWN. |
| | NEITHER INDICATE A FIRST FLOOR BATHROOM. |
| | ONE FLOOR PLAN SV9 SHOWS A BATHROOM. |
| | DOES NOT REFLECT THE FLOOR PLAN AT |
| | OFFSET. PLEASE CLARIFY. SECTION 104.2.1. |
| | |
| | 14B. SHT P4-00A SV10 IS NOT INDICATED ON |
| | THE FLOOR PLAN OF SHT P2-00 AND DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE OFFSET. |
| | PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 15B. SHT P4-00A SV12 OFFSET ON FLOOR |
| | PLAN NOT SHOWN ON THE RISER DIAGRAM. |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 16B. SHT P4-00B SV13 DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE FIRST FLOOR |
| | UNDERGROUND, AND VENT NOT SHOWN ON THE |
| | 11TH THRU 16TH FLOOR. FLOOR PLAN SHOWS |
| | ONE SV13 CONNECTING TO SHOWER DRAIN. |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 17B. SHT P4-00B SV14 DOES NOT REFLECT |
| | THE FLOOR PLAN 1ST FLOOR UNDERGROUND. |
| | ONE FLOOR PLAN SHOWS NO FIXTURES THRU |
| | THE FIRST FIVE FLOORS. DOES NOT REFLECT |
| | AT THE OFFSET, SHOWN AS SHOWERS ON FLOOR |
| | PLAN 11TH THRU 16TH FLOORS FOR ONE RISER |
| | AND NOT SHOWN AS VTR ON ONE RISER. |
| | PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 18B. SHT P4-00B SV15 DOES NOT REFLECT |
| | THE FLOOR PLAN 1ST FLOOR UNDERGROUND, |
| | AND ONE RISER SHOWN ON THE FLOOR PLAN |
| | INDICATES FIXTURES ON THE FIRST FLOOR. |
| | PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 19B. SHT P4-00B SV16 DOES NOT REFLECT |
| | THE FLOOR PLAN 1ST FLOOR UNDERGROUND. |
| | FLOOR PLANS ALSO SHOWS NO FIXTURES ON |
| | FIRST FLOOR. CORRELATE RISER WITH FLOOR |
| | PLANS. SECTION 104.2.1. |
| | |
| | 20B. SHT P4-00B SV17 NOT FOUND ON THE |
| | FIRST FLOOR PIPING LAYOUT SHT P2-00. |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 21B. SHT P4-01 RISER P1 OFFSET VENTS |
| | REQUIRED. SECTIONS 915.2 & 915.3. |
| | |
| | 22B. SHT P4-01 RISER P2 RISER SHOWS NO |
| | BRANCH LINE FOR 5TH FLOOR. DOES NOT |
| | REFLECT THE FLOOR PLAN. CORRELATE RISER |
| | AND FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 23B. SHT P4-01 RISER P3 REFLECTS ONE |
| | FLOOR PLAN BUT NOT THE OTHER. FLOOR |
| | PLANS ARE NOT TYPICAL. SEPARATE RISERS |
| | REQUIRED. SECTION 104.2.1. |
| | |
| | 24B. SHT P4-01 RISER P4 CHANGES TO P15 |
| | ONE FLOOR PLAN FOR ONE P4. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 25B. SHT P4-01 RISER P5 DOES NOT REFLECT |
| | THE FLOOR PLAN 1ST FLOOR. CORRELATE THE |
| | RISER AND THE FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 26B. SHT P4-01 RISERS P7, (10), SOME |
| | DIFFER FROM OTHERS. SOME DO NOT SHOW |
| | FIXTURES ON THE FIRST FLOOR. RISER CAN |
| | NOT BE TYPICAL IF FLOOR PLAN IS NOT THE |
| | SAME. PLEASE CORRELATE RISERS TO FLOOR |
| | PLAN. SECTION 104.2.1. |
| | |
| | 27B. SHT P4-01 RISER P8 ONE RISER STARTS |
| | ON THE 1ST FLOOR AND IS NOT SHOWN ON THE |
| | 6TH FLOOR & OFFSET DOES NOT REFLECT THE |
| | FLOOR PLAN. CORRELATE RISER AND FLOOR |
| | PLANS. SECTION 104.2.1. |
| | |
| | 28B. SHT P4-01 RISER P9 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN ON ONE 1ST THRU |
| | 5TH FLOORS NO FIXTURE BRANCH. NOT SHOWN |
| | ABOVE THE 5TH FLOOR AT ALL ON ONE FLOOR |
| | PLAN. CORRELATE RISER AND FLOOR PLANS. |
| | SECTION 104.2.1. |
| | |
| | 29B. SHT P4-01A RISER P15 CHANGES TO P4 |
| | ON SHT P2-01. PLEASE CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 30B. SHT P4-01A RISER P17 DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE FIRST |
| | FLOOR. CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 31B. SHT P4-01B RISER P18 NOT INDICATED |
| | ON FLOORS 1 THRU 5. CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 32B. SHT P4-01B RISER P20 OFFSET VENTS |
| | REQUIRED. SECTIONS 915.2 & 915.3. |
| | |
| | 33B. SHT P4-02 RISER 11 DOES NOT REFLECT |
| | THE FLOOR PLAN 6TH FLOOR. OFFSET NOT |
| | SHOWN. CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 34B. SHT 4-02 RISER 1/2 DOES NOT REFLECT |
| | THE FLOOR PLAN 1ST & 2ND FLOORS. |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 35B. SHT P4-02 RISER CONNECTIONS TO THE |
| | MAIN FOR RISERS 9/10 & 11 DO NOT REFLECT |
| | THE FLOOR PLAN. CORRELATE THE RISER AND |
| | THE FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 36B. SHT P4-02 RISER CONNECTIONS TO MAIN |
| | FOR RISERS 17, 18/19, & 20/21 DO NOT |
| | REFLECT THE FLOOR PLAN. PLEASE CORRELATE |
| | RISERS AND FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 37B. SHT P4-03 RISER 18/19 DOES NOT |
| | REFLECT THE FLOOR PLAN. PLEASE CORRELATE |
| | THE FLOOR PLAN AND RISERS. SECTION |
| | 104.2.1. |
| | |
| | 38B. SHT P4-03 RISER 20 DOES NOT REFLECT |
| | THE FLOOR PLAN 7TH THRU 10TH FLOORS. |
| | OFFSET NOT SHOWN. CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 39B. SHT P4-03 RISER 20/21 DOES NOT |
| | REFLECT THE FLOOR PLAN 1ST THRU 6TH |
| | FLOORS. CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 40B. SHT P4-04 RD4 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN. OFFSETS NOT |
| | SHOWN. CORRELATE THE RISER WITH THE |
| | FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 41B. SHT P4-04 RD6 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN. OFFSET NOT |
| | SHOWN. CORRELATE THE RISER AND THE FLOOR |
| | PLAN. SECTION 104.2.1. |
| | |
| | 42B. SHT P4-04 RD16 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN. OFFSET NOT |
| | SHOWN. CORRELATE THE RISER AND THE FLOOR |
| | PLAN. SECTION 104.2.1. |
| | |
| | 43B. SHT P4-05 CD RISER #5 DOES NOT |
| | REFLECT THE FLOOR PLAN 11TH FLOOR AND |
| | ABOVE. CORRELATE RISER AND FLOOR PLANS. |
| | SECTION 104.2.1. |
| | |
| | 44B. SHT P4-05 CD RISER #2 DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE 11TH |
| | FLOOR. OFFSET NOT SHOWN. CORRELATE RISER |
| | WITH FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 45B. SHEETS FOR ALL FLOOR PLANS. KEYED |
| | NOTES ARE NOT SHOWN ON ALL FLOOR PLANS. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | |
| | 46B. SHT PO-01 CODE REFERENCE TO |
| | IBC-2000 AND INTERNATIONAL ENERGY |
| | CONSERVATION CODE 2000 DO NOT APPLY. |
| | ADOPTED CODE IS THE FBC-2001 PLUMBING |
| | CODE ONLY. DELETE OTHER REFERENCES. |
| | |
| | 47B. SHT PO-01 HORIZONTAL STORM DRAINAGE |
| | PIPING REFERENCES FBC-2004. ADOPTED CODE |
| | IS FBC-2001. |
| | |
| | 48B. SHT P2-00 INDICATES SV19 RISER ON |
| | THE FLOOR PLAN. NO SV19 RISER SUBMITTED. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | |
| | 49B. SHT P2-00KEYED NOTE #1 HAS BEEN |
| | CHANGED TO NOTE #3 ON THE FLOOR PLAN AND |
| | NOTE #3 DOES NOT APPLY. PLEASE CORRELATE |
| | KEYED NOTES WITH INFORMATION INDICATED |
| | ON THE FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 50B. SHT P2-00 THE PIPE SIZE FOR THE |
| | STORM SYSTEM IS INCORRECT IN SOME |
| | PLACES. RECHECK ALL PIPE SIZES PER TABLE |
| | 1106.3. |
| | |
| | 51B. SHT P2-00 NOT ALL KEYED NOTES SHOWN |
| | ON THE FLOOR PLAN REFLECT THE FLOOR |
| | PLAN. (EXAMPLE, KEYED NOTE #2 ON THE |
| | FLOOR PLAN SHOWS A CONDENSATE LINE |
| | OFFSET, BUT THE KEYED NOTED IN THE INDEX |
| | STATES "4" STORM DOWN FROM TERACE |
| | ABOVE"). PLEASE CORRELATE KEYED NOTES |
| | WITH INFORMATION INDICATED ON THE FLOOR |
| | PLAN. |
| | |
| | 52B. SHT P2-01 INDICATES 2ND THRU 5TH |
| | FLOORS. THERE ARE OFFSETS SHOWN ON THE |
| | FLOOR PLAN. ARE THESE OFFSETS TYPICAL |
| | FOR ALL FLOORS? IF NOT THEN FLOOR PLANS |
| | THAT ARE NOT TYPICAL SHALL BE SUBMITTED |
| | INDIVIDUALLY AND NOT SHOWN AS TYPICAL. |
| | (SEE KEYED NOTE #8, "ROUTE PIPING |
| | SUSPENDED FROM CEILING ON THIS LEVEL". |
| | LEVEL NOT INDICATED)PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | |
| | 53B. SHT P2-01 SV9 SHOWN IN THE BLOCK |
| | WALL FOR STAIRWELL #1. PLEASE INDICATE |
| | HOW THE FIRE RATING WILL BE MAINTAINED |
| | FOR THE STAIRWELL. ALSO SHOW COMPLIANCE |
| | WITH SECTIONS 1907.3, 1907.4, |
| | 1907.5(1)(3), AND 1907.3.6(3). SUBMIT A |
| | DETAIL. |
| | SECTION 104.2.3. |
| | |
| | 54B. SHT P2-01 NOT ALL KEYED NOTES SHOWN |
| | ON THE FLOOR PLAN REFLECT THE FLOOR |
| | PLAN. (EXAMPLE, KEYED NOTE #2 STATES |
| | "OFFSET 2" SANITARY DRAIN" AND IS |
| | INDICATED ON A CONDENSATE LINE). |
| | CORRELATE KEYED NOTES AND FLOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 55B. SHT P2-01 SHEET APPEARS TO BE |
| | INCOMPLETE. SHOW A MATCH LINE AND |
| | INDICATE WHERE THE REST OF THE FLOOR |
| | PLAN CAN BE LOCATED, OR SUBMIT A SHEET |
| | THAT IS 100% COMPLETE. SECTION 104.2.1. |
| | |
| | 56B. SHT P2-01 RD11 SHOWS AN OFFSET ON |
| | THE FLOOR PLAN THAT IS NOT REFLECTED ON |
| | THE RISER DIAGRAM. PLEASE CORRELATE THE |
| | RISER WITH THE FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 57B. SHT P2-01 RISER 8, 9, 10 DOES NOT |
| | INDICATE WHERE THE RISER ROUTES DOWN TO |
| | THE FLOOR BELOW. PLEASE CLARIFY SECTION |
| | 104.2.1. |
| | |
| | 58B. SHT P2-01B RECHECK PIPE SIZING AS |
| | SOME SIZING IS INCORRECT. ALSO SOME AREA |
| | DRAINS ARE SHOWN AS PLANTER DRAINS AND |
| | SOME PLANTER DRAINS ARE SHOWN AS AREA |
| | DRAINS. CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 104.2.1 AND TABLE 1106.3. |
| | |
| | 59B. SHT P2-01B SHOW THE SF OF EACH |
| | DRAIN AND INDICATE SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. TABLE 1106.3. |
| | |
| | 60B. SHT P2-02 CD5 SHOWN ON FLOOR PLAN |
| | WAS NOT SHOWN ON FLOORS 1 THRU 5. |
| | INDICATE WHERE CD5 TERMINATES. SECTION |
| | 104.2.1. |
| | |
| | 61B. SHT P2-02B THREE PLANTER DRAINS |
| | SHOWN ON THE FLOOR PLAN ARE NOT SHOWN |
| | ON THE RISER DIAGRAM. CORRELATE THE |
| | RISER AND THE FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 62B. SHT P2-02B NO DRAINAGE IS SHOWN FOR |
| | THE AMENITY DECK AREA NOR FOR THE TENNIS |
| | COURT AREA AS REQUIRED BY SECTION |
| | 1101.2. PLEASE CLARIFY. |
| | |
| | 63B. SHT P2-02B SHOW THE LOCATION FOR |
| | ALL REQUIRED SECONDARY ROOF DRAINS, AND |
| | INDICATE THE SIZE. SECTIONS 1107.1, |
| | 1107.2, & 1107.3. |
| | |
| | 64B. SHT P2-03 IS FOR FLOORS 7 THRU 10. |
| | THERE ARE OFFSETS SHOWN ON THE FLOOR |
| | PLAN. ARE THESE OFFSETS FOR EACH FLOOR? |
| | IF NOT THE FLOORS CAN NOT BE TYPICAL, |
| | AND INDIVIDUAL SHEETS ARE REQUIRED FOR |
| | EACH FLOOR THAT IS NOT TYPICAL. SECTION |
| | 104.2.1. |
| | |
| | 65B. SHT P2-03 KEYED NOTES DO NOT |
| | REFLECT WHERE THEY ARE APPLIED ON THE |
| | FLOOR PLAN. CORRELATE KEYED NOTES AND |
| | THE FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 66B. P2-05 IS FOR SHEETS 12, 14 THRU 16. |
| | THERE ARE OFFSETS SHOWN ON THE FLOOR |
| | PLAN, AND VENTS CONNECTING TO EACH OTHER |
| | AND VENTING THRU THE ROOF. ARE THESE |
| | OFFSETS AND VENTS CONNECTING ON EACH |
| | FLOOR? SEPARATE SHEETS SHALL BE |
| | SUBMITTED FOR FLOOR PLANS THAT ARE NOT |
| | TYPICAL. SECTION 104.2.1. |
| | |
| | 67B. SHT P2-06 NOT ALL VENTS ARE SHOWN |
| | AS THRU THE ROOF. SOME VENTS CONNECTING |
| | WITH OTHER VENTS AS SHOWN ON SHT P2-05 |
| | DO NOT REFLECT WHAT IS SHOWN ON P2-06. |
| | CORRELATE ALL VENTS AS THEY COME THRU |
| | THE ROOF WITH THE FLOOR BELOW. ALL VENTS |
| | SHALL BE SHOWN AS VTR. SECTION 104.2.1. |
| | |
| | 68B. SUBMIT WATER RISER DIAGRAMS FOR ALL |
| | UNITS, (SHOWN ON SHTS P3-00 THRU P3-03), |
| | SHOWING ALL PIPE SIZES, VALVES, AND |
| | WATER HAMMER ARRESTORS, (REQUIRED BY |
| | SECTION 604.9). WATER HAMMER ARRESTORS |
| | SHALL BE LOCATED NEAR THE FIXTURE, IN AN |
| | "EFFECTIVE RANGE", (NOT IN THE CEILING), |
| | PER PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. SECTION 104.3.1.1. |
| | |
| | 69B. SHT P4-00B RISER SV13 DOES NOT |
| | REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN |
| | ON THE FLOOR PLAN AT THE 11TH FLOOR. |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 70B. SHT P4-00B RISER SV17 IS NOT SHOWN |
| | ON THE FIRST FLOOR. CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 104.2.1. |
| | |
| | 71B. SHT P4-01A RISER P16 DOES NOT |
| | REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN |
| | ON FLOOR PLAN. CORRELATE RISER AND FLOOR |
| | PLAN. SECTION 104.2.1. |
| | |
| | 72B. SHT P4-03 SUBMIT WATER SUPPLY RISER |
| | ISOMETRIC RISER DIAGRAMS FOR TOILET |
| | ROOMS AND DRINKING FOUNTAIN. SECTION |
| | 104.3.1.1. - WATER HAMMER ARRESTORS |
| | SHALL BE LOCATED IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | 73B. SHT P4-04 ROOF DRAIN STORM WATER |
| | RISER. RECHECK THE PIPE SIZING, AS SOME |
| | SIZES ARE INCORRECT PER TABLE 1106.3. - |
| | RD3 SQUARE FOOTAGE DOES NOT REFLECT SF |
| | SHOWN ON THE ROOF PLAN.- RD-11 IS SHOWN |
| | AS 6", BUT IS SHOWN AS 4" ON THE ROOF |
| | PLAN. CORRELATE RISER WITH FLOOR PLAN. |
| | - RECHECK ADDITION FROM 10" (18656SF) |
| | AND ALL DOWNSTREAM FIGURES. SECTION |
| | 104.2.1. |
| | |
| | 74B. SHT P4-04B SOME PIPE SIZING IS |
| | INCORRECT. ADDITION NEEDS TO BE CHECKED |
| | FROM 8" (5960SF) AND DOWNSTREAM. SOME |
| | AREA DRAINS ARE SHOWN AS PLANTER DRAINS |
| | AND SOME PLANTER DRAINS ARE SHOWN AS |
| | AREA DRAINS. CORRELATE RISER AND FLOOR |
| | PLAN. SECTION 104.2.1 AND TABLE 1106.3. |
| | |
| | 75B. SHTS P4-05 & P4-06 THE CONDENSATE |
| | AND EMERGENCY PAN DRAIN LINE FOR THE |
| | WATER HEATER SHALL NOT BE COMBINED. PAN |
| | DRAIN SHALL BE SEPARATE. SECTION |
| | 504.8.2. |
| | |
| | 76B. SHT P4-06 CD18 DOES NOT REFLECT THE |
| | FLOOR PLAN ON THE 1ST FLOOR. CORRELATE |
| | RISER AND FLOOR PLAN. SECTION 104.2.1. |
| | |
| | |
| | 77B. SHT P4-06 CD15 IS NOT SHOWN ON |
| | FLOORS 1 THRU 5. PLEASE INDICATE WHERE |
| | CD15 TERMINATES. SECTION 104.2.1. |
| | |
| | 78B. SHT P6-00 INDICATES TWO SUPPLY |
| | LINES TO RISER W17. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | |
| | 79B. SUBMIT EMERGENCY PAN DRAIN LINE |
| | RISERS FOR THE WATER HEATERS. SHOW ALL |
| | PIPE SIZES, OFFSETS AND TERMINATION |
| | POINT. SECTION 104.3.1.1. |
| | |
| | 80B. SUBMIT A HORIZONTAL ISOMETRIC RISER |
| | DIAGRAM FOR THE BUILDING SANITARY DRAIN. |
| | SHOW ALL PIPE SIZES, RISER CONNECTION |
| | LOCATION, IDENTIFY RISER, AND SHOW DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM. |
| | SECTION 104.3.1.1. |
| | |
| | 81B. SHT P2-05 KEYED NOTES ON FLOOR PLAN |
| | BUT NO "PLUMBING KEYED NOTES INDEX" |
| | SUBMITTED ON THE SHEET. SUBMIT KEYED |
| | NOTES FOR THIS SHEET, MAKING SURE THEY |
| | REFLECT THE KEYED NOTES SHOWN ON THE |
| | FLOOR PLAN. SECTION 104.2.1. |
| | |
| | REVIEW BY KEN STEVENS |