| 2006-09-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | WPB CITY CODE |
| | |
| | FROM PREVIOUS REVIEW. COMMENT NUMBER TO |
| | REMAIN THE SAME. |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SHT CD-11 DETAIL #1 CLEAR FLOOR SPACE |
| | AT THE TOILET SHALL COMPLY WITH ONE OF 3 |
| | SHOWN ON PAGE 7.43 FHA DESIGN MANUAL. |
| | ***RESPONSE NOTED, BUT BOTH DIMENSIONS |
| | SHALL BE SHOWN. |
| | |
| | 6. SHT CD-11 RESIDENTIAL UNIT |
| | ACCESSIBLITY NOTES: |
| | #7 OK |
| | #8(II)(B)(V) CALLS FOR DETAIL 3/CD-4. |
| | NO DETAIL 3 FOUND THAT SHEET. CLARIFY. |
| | SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT IT NOW CALLS FOR |
| | DETAIL 3/CD-11. THIS DETAIL DOES NOT |
| | SHOW LAVS/VANITIES. SECTION 104.2.1. |
| | |
| | 7. OK |
| | |
| | 8. SHT CD-12 NOTES FOR W/C REFERENCE |
| | DETAIL 3/CD-03.DETAIL NOT FOUND. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT IT ONLY SHOWS |
| | DIMENSION 5'6". BOTH DIMENSIONS SHALL BE |
| | SHOWN. PAGE 7.43. |
| | |
| | 9.OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | |
| | 16. SHT A1-04 4TH FLOOR BALCONYS APPEAR |
| | TO HAVE A PARAPET WALL ON ALL THREE |
| | SIDES. SHT REFERENCES DETAIL 1/A6-05, |
| | BUT SHT A6-05 WAS NOT SUBMITTED. SHT |
| | ALSO REFERENCES DETAIL 11/A6.20 WHICH |
| | SHOWS 1-1/2" WEEP HOLES. DRAINAGE PER |
| | SECTIONS 1106 & 1107WILL BE REQUIRED |
| | FOR STORM WATER IF A PARAPET WALL IS ON |
| | ALL SIDES. PLEASE SUBMIT A DETAIL AND |
| | CLARIFY. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT SCUPPERS SHALL BE |
| | A MINIMUM 4" HIGH. SECTION 1503.4.2. THE |
| | PEDESTRAIN TRAFFIC COATING IS INDICATED |
| | AS 4" HIGH UP THE WALL ON DETAIL |
| | 11/A6.20. THIS APPEARS TO COVER THE |
| | SCUPPERS. PLEASE CLARIFY OR SUBMIT AN |
| | ELEVATION DETAIL OF THE SCUPPERS. |
| | SECTION 104.2.1. |
| | |
| | 17. SHTS A3-20, A3-21 SHOW DIMENSIONS OF |
| | OPENINGS FOR EACH WATER CLOSET. MINIMUM |
| | 33" OPENING REQUIRED. 18" OFF THE WALL |
| | TO THE CENTER OF THE FIXTURE, AND |
| | MINIMUM 15" TO THE NEXT FIXTURE. MINIMUM |
| | 18" OFF ONE FIXTURE, AND 15" MINIMUM OFF |
| | THE OTHER FIXTURE. FHA DESIGN MANUAL |
| | PAGES 7.43, 7.44, 7.45, 7.46. |
| | ***RESPONSE NOTED, BUT DETAILS 7 & 9 SHT |
| | A3-20, (INDICATED AS 2ND DETAIL #5), AND |
| | DETAILS 3 & 4 SHT A3-21, THE 18" FROM |
| | THE CENTERLINE OF THE WATER CLOSET TO |
| | THE WILL IS AN ABSOLUTE MEASUREMENT, NOT |
| | A MINIMUM AS SHOWN. PAGE 6.5 FHA DESIGN |
| | MANUAL. |
| | |
| | 18. N/A |
| | 19. SHT A1-18 OVERFLOW SCUPPERS ARE |
| | REQUIRED FOR THE UPPER ROOF. SECTION |
| | 1106.5. SHOW LOCATION AND INDICATE SIZE |
| | OF OVERFLOW SCUPPERS PER SECTION 1101.7, |
| | 1107.3 AND TABLE 1106.7. |
| | ***RESPONSE NOTED, BUT OVERFLOW SCUPPERS |
| | ARE NOT INDICATED ON THE MECHANICAL ROOM |
| | OR STAIRWELL ROOFS. SECTIONS 1107.1, |
| | 1107.2 & 1107.3. |
| | |
| | 20. SHT AP1-06 SHOW THE LOCATION OF ALL |
| | SECONDARY ROOF DRAINS. SECTION 1107. |
| | ***RESPONSE NOTED, BUT THE SECONDARY |
| | DRAINS ARE REQUIRED AT THE 6TH FLOOR |
| | DECK AREA. PLEASE INDICATE THE LOCATION, |
| | SIZE AND SQUARE FOOTAGE DRAINED BY EACH |
| | SECONDARY DRAIN. SECTION 1107.1, 1107.2, |
| | AND 1107.3. |
| | |
| | 21. SHT ID7-01 PER SECTION 1210.2 WALLS |
| | WITHIN 2' OF A WATER CLOSET SHALL BE |
| | NONABSORBENT UP TO 4'. PLANS INDICATE |
| | THAT ONLY THE WALL BEHIND THE WATER |
| | CLOSET HAS TILE. PLEASE INDICATE HOW THE |
| | VINAL WALL PAPER COMPLYS WITH THE NON- |
| | ABSORBENT REQUIREMENT. |
| | ***RESPONSE NOTED, BUT A SUBMITTAL FOR |
| | THE PRODUCT, WITH INSTALLATION |
| | INSTRUCTIONS, SHALL BE SUBMITTED FOR |
| | REVIEW AND APPROVAL. SECTION 104.2.1.2. |
| | |
| | 22. SHT ID8-01 DETAILS 1 & 2 SHOW THE |
| | FOLLOWING ON THE DETAILS: |
| | 11-4.16.2 CLEAR FLOOR SPACE (W/C) OK |
| | 11-4.16.3 HEIGHT 9W/C) OK |
| | |
| | 11-4.16.5 FLUSH CONTROLS (W/C) NOT |
| | ADDRESSED. |
| | |
| | 11-4.16.6 DISPENSERS (W/C) OK |
| | |
| | 11-4.19.2 HEIGHT & CLEARANCES (LAV) |
| | CLEARANCES NOT ADDRESSED. |
| | |
| | 11-4.19.3 CLEAR FLOOR SPACE (LAV) OK |
| | |
| | 11-4.19.5 FAUCETS (LAV) NOT ADDRESSED |
| | |
| | 11-4.19.6 MIRRORS (LAV) OK |
| | 11-4.22.3 5' TURNING AREA (TOILET ROOM) |
| | OK |
| | 23. OK |
| | |
| | 24. ALL PLUMBING SHEETS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME, ADDRESS, |
| | AND LICENSE NUMBER ON EACH SHEET, AND IF |
| | PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE |
| | NUMBER, AS WELL AS, THE NAME, ADDRESS, |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS ON EACH |
| | SHEET. FAC 61G15-23.002(2) & FS 471.2055 |
| | ***RESPONSE NOTED, BUT LICENSE NUMBER IS |
| | NOT IS NOT INDCATED. |
| | |
| | 25. OK |
| | |
| | 26. SHT P0-01 PLUMBING FIXTURE SCHEDULE, |
| | SHOW ALL PIPE SIZES TO ALL WATER |
| | HEATERS. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT EWH-3 |
| | SPECIFICATION SHEET INDICATES 1-1/4" |
| | OPENING FOR THE HOT & COLD WATER. |
| | FIXTURE SCHEDULE INDICATES 1/2" COLD |
| | WATER SUPPLY. PLEASE CORRELATE SUPPLY |
| | SIZE PIPE FOR ALL HEATERS WITH MANUF. |
| | SPECIFICATION FOR PIPE SIZE CONNECTIONS. |
| | SECTION 104.2.1. |
| | |
| | 27. N/A |
| | 28. N/A |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | 34. OK |
| | 35. OK |
| | |
| | 36. SHT P2-00 NO KEYED NOTE FOR #5 |
| | FOUND. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT KEY NOTE #1 WAS |
| | CHANGED TO #3 ON THE FLOOR PLAN AND DOES |
| | NOT REFLECT THE INFORMATION INDICATED IN |
| | KEY NOTE. PLEASE CLARIFY SECTION |
| | 104.2.1. |
| | |
| | 37. SHT P2-00 RD-21, SV2, SV3, SV-4, P1. |
| | P2, P-3, CD-10 AND OTHER RISERS SHOWN ON |
| | SHT P2-01 BUT NOT SHOWN ON THIS SHEET. |
| | ALL RISERS START ON THE FIRST FLOOR AND |
| | ALL RISERS LOCATIONS SHALL BE SHOWN |
| | WHERE THEY START IN THE SYSTEM. |
| | ***RESPONSE NOTED, BUT MANY RISER |
| | NUMBERS CHANGE FROM FLOOR TO FLOOR ON |
| | THE FLOOR PLAN. SOME RISERS ARE NOT |
| | INDICIATED ON THE FIRST FLOOR, SOME |
| | RISER DESIGNATIONS HAVE NO RISER |
| | DIAGRAMS. SOME RISER START OFF AS ONE |
| | RISER NUMBER, CHANGE TO ANOTHER RISER |
| | NUMBER AND THEN CHANGE BACK TO THE |
| | ORIGINAL NUMBER. PLEASE CORRELATE ALL |
| | RISERS. SECTION 104.2.1. |
| | |
| | 38. EACH SANITARY RISER DIAGRAM, BE IT A |
| | CONVENTIONAL SYSTEM OR A SOVENT SYSTEM |
| | RISER SHALL HAVE ITS OWN RISER |
| | DESIGNATION, SUCH AS P-1, P-2. P3 OR |
| | SV-1, SV-2, SV-3 ETC. SHOWING MULTIPLE |
| | RISERS WITH THE SAME RISER DESIGNATION |
| | IS CONFUSING BECAUSE, (FOR EXAMPLE), NOT |
| | ALL P-1 RISERS ARE THE SAME AS THE |
| | PIPING IS NOT ALWAYS THE SAME AND THE |
| | OFFSETS ARE NOT ALL THE SAME FOR EACH |
| | P-1. SEE FOR EXAMPLE THE WATER RISERS, |
| | THE CONDENSATE RISERS, OR THE STORM |
| | RISERS. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT THE RISERS ARE |
| | STILL CONFUSING. ALL SANTARY RISERS |
| | SHOULD HAVE THERE OWN RISER NUMBER. |
| | EXAMPLE SANT. 1, SANT. 2, SANT. 3 ETC. |
| | EACH RISER CAN BE A TYPICAL OF A RISER |
| | TYPE FOR EXAMPLE SV-4 OR P-4, BUT EACH |
| | RISER WOULD BE ABLE TO BE LOCATED |
| | INDIVIDUALLY, AND WHEN A COMMENT IS MADE |
| | CONCERNING A SANT. RISER, IT WOULD BE |
| | EASY TO UNDERSTAND WHICH RISER IS BEING |
| | COMMENTED ON.SECTION 104.2.1. |
| | |
| | |
| | 39. ALL SHEETS SHOWING PIPING ON FLOOR |
| | PLANS: SHOW ALL PIPING INCLUDING ARMS TO |
| | LAVS OR KITCHEN SINKS. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT NO PIPING IS |
| | SHOWN FOR COMMON AREA TOILET ROOMS 104, |
| | & 105. SECTION 104.2.1. |
| | |
| | 40. OK |
| | |
| | 41. SHT P2-01 RISERS RD-6, RD-9, RD-12 |
| | AND RD-13 HAVE BEEN OFFSET, BUT NO |
| | OFFSET PIPING IS SHOWN. PLEASE SHOW ALL |
| | OFFSET PIPING ON PLANS. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT RD-6 RISER STILL |
| | DOES NOT REFLECT THE FLOOOR PLAN. |
| | SECTION 104.2.1. |
| | |
| | 42. SEE COMMENT 38. |
| | 43. SEE COMMENT 38 |
| | 44. SEE COMMENT 38 |
| | 45. SEE COMMENT 38 |
| | |
| | 46. SHT P2-02 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY DRAINS PER |
| | SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. SHOW SQUARE FOOOTAGE BEING |
| | DRAINED AT EACH PRIMARY DRAIN AND SHOW |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS ADDED IN CALCULATIONS AS WELL |
| | AS ANY AREAS FROM UPPER ROOFS ADDED TO |
| | THE DECK AREA. |
| | ***RESPONSE NOTED, BUT CALCULATIONS FOR |
| | PRIMARY ROOF DRAINS AND FOR AREA DRAINS |
| | FOR THE 6TH FLOOR TERRACE AREAS HAVE NOT |
| | BEEN SUBMITTED. TABLE 1106.3 |
| | |
| | 47. SHT P2-02 MANY AREA DRAINS ARE |
| | MISLABELED AS PLANTER DRAINS, MANY |
| | DRAINS ARE NOT LABELED, MANY LABELS SHOW |
| | NO DRAIN. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | ***RESPONSE NOTED, BUT SOME DRAINS ARE |
| | STILL MISLABELED. SECTION 104.2.1. |
| | |
| | 48. OK |
| | 49. SEE COMMENT 38 |
| | 50. SEE COMMENT 38 |
| | 51. SEE COMMENT 38 |
| | 52. SEE COMMENT 38 |
| | 53. SEE COMMENT 38 |
| | 54. SEE COMMENT 38 |
| | 55. SEE COMMENT 38 |
| | 56. SEE COMMENT 38 |
| | 57. SEE COMMENT 38 |
| | 58. SEE COMMENT 38 |
| | 59. SEE COMMENT 38 |
| | 60. SEE COMMENT 38 |
| | 61. SEE COMMENT 38 |
| | 62. SEE COMMENT 38 |
| | 63. SEE COMMENT 38 |
| | 64. SEE COMMENT 38 |
| | 65. SEE COMMENT 38 |
| | 66. OK |
| | 67. SEE COMMENT 38 |
| | 68. SEE COMMENT 38 |
| | 69. SEE COMMENT 38 |
| | 70. SEE COMMENT 38 |
| | 71. SEE COMMENT 38 |
| | 72. SEE COMMENT 38 |
| | 73. OK |
| | 74. OK |
| | 75. OK |
| | |
| | 76. SHT P2-06 THE VENTS THRU THE ROOF DO |
| | NOT REFLECT THE VENTS SHOWN ON SHT P2-05 |
| | FOR LOCATION. PLEASE CORRELATE VENTS |
| | FROM FLOOR TO FLOOR. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT SOME VENTS ARE |
| | NOT SHOWN OR DO NOT CONNECT TO OTHER |
| | VENTS AS SHOWN BELOW. SECTION 104.2.1. |
| | |
| | 77. OK |
| | 78. OK |
| | 79. OK |
| | 80. OK |
| | 81. OK |
| | 82. OK |
| | 83. OK |
| | 84. OK |
| | 85. OK |
| | |
| | 86. SHT P4-00 ALL SV RISERS DO NOT |
| | REFLECT THE FLOOR PLANS FOR THE FIRST |
| | FLOOR PIPING. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT THE SOME RISERS |
| | DO NOT REFLECT THE FLOOR PLANS ON THE |
| | FIRST FLOOR, OR AT THE OFFSETS. SOME |
| | RISERS REFLECT THE FLOOR PLANS IN ONE |
| | INSTANCE, BUT THE FLOOR PLAN CHANGES FOR |
| | THE SAME RISER IN ANOTHER INSTANCE. |
| | RISER CAN NOT BE TYPICAL IF NOT EXACTLY |
| | THE SAME IN EACH CASE. SECTION 104.2.1. |
| | |
| | 87. SHT P4-00 ALL SV RISERS DO NOT |
| | REFLECT THE FLOOR PLANS FOR THE 16TH |
| | FLOORS. NO VENT PIPING SHOWN FOR THE |
| | REVENTS SHOWN ON THE 16TH FLOOR. SECTION |
| | 106.1.1. |
| | ***RESPONSE NOTED, BUT FOR EXAMPLE THE |
| | VENTS P1/P19/SV-13/SV-1 ARE CONNECTED |
| | TOGETHER ON THE FLOOR PLAN, BUT THE VTR |
| | ON THE ROOF PLAN DOES NOT SHOW THIS. |
| | SV-13 DOES NOT INDICATE CONNECTING TO |
| | SV-1. P19 OFFSET VENT BUT DOES NOT |
| | INDICATE TO WHICH VENT STACK. THIS IS |
| | EVEN MORE OF A PROBLEM WHEN THERE ARE |
| | MORE THAN ONE RISER FOR A RISER |
| | DESIGNATION. (SEE COMMENT 38). |
| | |
| | 88.OK |
| | |
| | 89. SHT P4-00 16TH FLOOR SHALL BE |
| | DIFFERENT FROM OTHER FLOOR ON ALL RISERS |
| | AS THE VENTING/REVENTING IS ONLY ON THIS |
| | FLOOR. SHOW ALL VENTING/REVENTING ON |
| | RISERS. (THIS IS REQUIRED FOR ALL VENTS |
| | INCLUDING SOVENT SYSTEM IF VENTS FROM |
| | OTHER STACKS ARE TYING INTO THEM. |
| | SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT SOME FLOORS ARE |
| | NOT TYPICAL AND INDIVIDUAL FLOORS FOR |
| | THE FLOORS THAT ARE NOT TYPICAL SHALL BE |
| | SUBMITTED SEPARATELY. |
| | |
| | 90. OK |
| | 91. OK |
| | |
| | 92. SEE COMMENT 38 |
| | |
| | 93. SHT P4-00 SUBMIT A RISER DIAGRAM FOR |
| | EACH SANTITARY RISER DIAGRAM AND EACH |
| | SOVENT RISER DIAGRAM. COMMON RISERS WITH |
| | DIFFERENT FLOOR PLANS ARE NOT |
| | ACCEPTABLE. IF THE TUB AND LAV ARE ON |
| | THE OPPOSITE SIDE OF THE WATER CLOSET |
| | FROM ONE FLOOR PLAN TO THE OTHER, OR |
| | OFFSETS ARE DIFFERENT, OR ON DIFFERENT |
| | FLOOR PLANS, THEN SEPARATE RISER |
| | DIAGRAMS ARE REQUIRED. RISER DIAGRAMS |
| | SHALL REFLECT THE FLOOR PLAN FROM THEIR |
| | CONNECTION TO THE BUILDING DRAIN UP THRU |
| | THE ROOF FOR VENTING. BECAUSE THIS IS AN |
| | ENGINEERED SYSTEM, SEPARATE RISERS ARE |
| | REQUIRED, AND SEPARATE RISER |
| | DESIGNATIONS ARE REQUIRED. SOME RISERS |
| | CHANGE RISER NUMBERS FROM FLOOR TO FLOOR |
| | PLEASE CLARIFY. FLOOR PLANS SHOW REVENTS |
| | FROM OTHER RISERS TYING TOGETHER PRIOR |
| | TO VENTING THRU THE ROOF. THIS IS NOT |
| | REFLECTED ON ANY OF THE RISER DIAGRAMS. |
| | ***RESPONSE NOTED, BUT PROBLEM NOT |
| | ADDRESSED. SEE COMMENT 38. |
| | |
| | 94. SUBMIT AN APPROVED DESIGN MANUAL FOR |
| | THE SOVENT SYSTEM. SUBMIT MANUFACTURE |
| | SPECIFICATIONS FOR AERATORS AND |
| | DEAERATORS FOR PRODUCT APPROVAL PER |
| | SECTIONS 303.1 & 303.4. |
| | ***COMMENT NOT ADDRESSED. NO RESPONSE. |
| | |
| | |
| | 95. PLANS APPEAR TO BE INCOMPLETE AT |
| | THIS TIME, AS ALL THE SV RISERS ARE NOT |
| | SUBMITTED AS WELL AS THE BLDG DRAIN FOR |
| | OTHER SYSTEMS. OTHER COMMENTS MAY OR MAY |
| | NOT FOLLOW UPON SUBMITTAL OF REQUIRED |
| | INFORMATION AND INFORMATION NOT |
| | SUBMITTED AT THIS TIME. SECTIONS 106.1.1 |
| | AND 106.3.5.1.3. |
| | ***RESPONSE NOTED, BUT PLANS DO NOT SEEM |
| | TO BE COMPLETE YET. (SEE NEW COMMENTS) |
| | |
| | 96. SHT P4-01 ALL STACKS, RELIEF VENTS |
| | ARE REQUIRED PER SECTION 914.1 AND SHALL |
| | BE PROVIDED AT EACH 10TH INTERVAL |
| | BEGINNING WITH THE TOP FLOOR. SECTION |
| | 914.1. |
| | ***RESPONSE NOTED, BUT THE STACKS WITH |
| | VENT STACKS REQUIRE RELIEF VENTS PER |
| | SECTION 914.1 HAS NOT BEEN ADDRESSED. |
| | |
| | 97. OK |
| | 98. OK |
| | 99. OK |
| | |
| | 100. SHT P4-02 RISERS W1, W2, W6, W8, & |
| | W10 FULL OPEN VALVES SHALL BE INSTALLED |
| | ON THE BASE OF EVERY WATER RISER PIPE. |
| | SECTION 606.1(3). |
| | ***RESPONSE NOTED, BUT W8 RISER STILL |
| | SHOWS NO VALVE. |
| | |
| | 101. SHT P4-04 SUBMIT THE BUILDING STORM |
| | DRAIN IN AN ISOMETRIC RISER DIAGRAM THAT |
| | REFLECTS THE PIPING SHOWN ON THE |
| | UNDERGROUND PLUMBING PLAN SHT P2-00. |
| | SECTION 106.3.5.1.3. SHOW ALL PIPE SIZES |
| | AND SQUARE FOOTAGE AS IT ACCUMULATES IN |
| | THE SYSTEM. IDENTIFY ALL RISERS AS THEY |
| | CONNECT TO THE BUILDING DRAIN IN THE |
| | ISOMETRIC DIAGRAM OF THE BUILDING DRAIN. |
| | SHOW ALL OFFSETS IN THE STORM RISERS, |
| | AND INDICATE ALL PIPE SIZES. |
| | ***RESPONSE NOTED, BUT RISER NUMBER ARE |
| | NOT SHOWN TO IDENTIFY RISERS. (EXAMPLE |
| | RWL-1, RWL-2 ETC.). SECTION 104.2.1. |
| | |
| | 102. SHTS P4-05 & P4-06 INDICATE |
| | MATERIAL FOR CONDENSATE SYSTEM. NO |
| | FLAMABLE MATERIAL IN THE AIR CONDITION |
| | ROOM IF IT IS USED AS A PLENUM. INDICATE |
| | METHOD OF VENTING THE CONDENSATE RISERS. |
| | VENTS CAN NOT TERMINATE IN THE WALLS OR |
| | IN A PLENUM. |
| | ***RESPONSE NOTED, BUT THE MATERIAL FOR |
| | THE CONDENSATE SYSTEM WAS NOT FOUND ON |
| | SHT P0-01. SECTION 104.2.1. |
| | |
| | 103. SHTS P4-05 & P4-06 SUBMIT A |
| | BUILDING DRAIN CONDENSATE ISOMETRIC |
| | RISER DIAGRAM THAT REFLECTS THE |
| | UNDERGROUND PIPING ON SHT P2-00. SECTION |
| | 106.3.5.1.3. |
| | ***RESPONSE NOTED, BUT THE HORIZONTAL |
| | BUILDING DRAIN FOR THE CONDENSATE IS |
| | REQUIRED BY SECTION 104.3.1.1. THE |
| | CONDENSATE AND THE WATER HEATER PAN |
| | DRAIN LINE CAN NOT BE COMBINED. SEPARATE |
| | DRAIN LINES AND SYSTEMS ARE REQUIRED. |
| | SECTION 504.8.2. |
| | |
| | 104. SHT P5-00 DETAIL 05 WASHER BOX |
| | CONNECTION WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT THE WASHER BOX PER 604.9. |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING. PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. |
| | ***RESPONSE NOTED, BUT WATER HAMMER |
| | ARRESTORS ARE NOT SHOWN. SECTION |
| | 104.2.1. |
| | |
| | 105. OK |
| | 106. OK |
| | |
| | 107. SHT P5-00 DETAIL 04 WATER HEATER |
| | SUBMIT EMERGENCY PAN DRAIN ISOMETRIC |
| | RISER DIAGRAM SHOWING ALL PIPE SIZES, |
| | MATERIAL, AND TERMINATION POINT. SECTION |
| | 106.3.5.1.3. |
| | ***RESPONSE NOTED, BUT RESPONSE DID NOT |
| | ADDRESS COMMENT. SECTION 104.3.1.1. |
| | |
| | 108. OK |
| | |
| | 109. SHT P5-00 DETAIL 07 DOMESTIC WATER |
| | BOOSTER PUMP DETAIL: SUBMIT MANUF. |
| | SPECIFICATION SHEETS FOR PUMP. PUMP |
| | SHALL BE LISTED. SECTION 303.4. |
| | ***RESPONSE NOTED, BUT RESPONSE NEEDS TO |
| | BE CLARIFIED. SCHEDULED PUMP? |
| | |
| | 110. OK |
| | 111. OK |
| | 112. OK |
| | |
| | 113. ALL SETS OF PLANS AND ALL SHEETS IN |
| | EACH SET OF PLANS: IF THE DESIGN |
| | PROFESSIONAL IS AN ENGINEER, THEN HE OR |
| | SHE SHALL AFFIX HIS OR HER OFFICIAL |
| | SEAL, SIGNATURE AND DATE TO SAID |
| | DRAWINGS AS REQUIRED BY FLORIDA |
| | STATUTES. NO INITIALS. LEGAL SIGNATURE |
| | IS REQUIRED. |
| | ***RESPONSE NOTED, BUT INITIALS APPEAR |
| | TO BE SUBMITTED IN PLACE OF A SIGNATURE. |
| | IF THIS IS THE LEGAL SIGNATURE, PLEASE |
| | SUBMIT A SIGNED, SEALED, DATED, |
| | NOTORIZED LETTER INDICATING LEGAL |
| | SIGNATURE FOR OUR FILES. FAC |
| | 61G15-23.002(2) AND FS |
| | 471.025. |
| | |
| | 114. SUBMIT WATER ISOMETRIC RISER |
| | DIAGRAMS FOR EACH UNIT SHOWING ALL PIPE |
| | SIZES, VALVES, AND WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9. |
| | SECTION 106.3.5.1.3. |
| | ***RESPONSE NOTED, BUT RESPONSE HAS |
| | NOTHING TO DO WITH COMMENT INFORMATION |
| | REQUESTED. SECTION 104.3.1.1. |
| | |
| | 115. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS APPLICATION: |
| | |
| | ***DUE TO THE FACT THAT THERE ARE NOT |
| | APPROVED GAS PLANS FROM PHASE I, THE |
| | INFORMATION IS STILL REQUIRED.*** |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGHTS PER FBC-2004 |
| | FUEL GAS. |
| | ***RESPONSE NOTED, BUT CORRESPONDING |
| | LENGTHS NOT SHOWN. FBC-2001 FUEL GAS. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | ***RESPONSE NOTED, BUT INFORMATION SHALL |
| | BE LOCATED AT RISER WITH REQUIRED INFO. |
| | SECTION 104.2.1. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | ***RESPONSE NOTED, INFORMATION REQUIRED |
| | ON PLANS WITH RISER. |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | ***RESPONSE NOTED, BUT TOTAL BTU LOAD OF |
| | SYSTEM NOT SHOWN. INFORMATION REQUIRED |
| | ON PLANS WITH RISER. |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ***NO RESPONSE NOT ADDRESSED. |
| | |
| | F. NA |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF |
| | 2 PSI INDICATE LOCATION OF REGULATORS |
| | AND SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR REGULATORS INDICATING MODEL. IF |
| | VENTED REGULATORS, INDICATE MATERIAL FOR |
| | VENTS AND SHOW ROUTING OF PIPING. |
| | ***NO RESPONSE, NOT ADDRESSED. |
| | |
| | H. NA |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***NO RESPONSE, NOT ADDRESSED. |
| | |
| | J. N/A |
| | K. N/A |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE RESUBMIT RED LINED SET OF |
| | PLUMBING PLANS FROM FIRST REVIEW TO HELP |
| | TO EXPEDITE THE SECOND REVIEW. |
| | ***NO RESPONSE, NOT ADDRESSED ADDING |
| | MANY HOURS TO REVIEW. RED LINED SET OF |
| | PLUMBING PLANS TO BE RETAINED TO |
| | EXPEDITE NEXT REVIEW. |
| | |
| | END OF COMMENTS FROM FIRST REVIEW. |
| | |