Plan Review Notes
Plan Review Notes For Permit 05110247
Permit Number 05110247
Review Stop P
Sequence Number 2
Notes
Date Text
2006-09-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 FROM PREVIOUS REVIEW. COMMENT NUMBER TO
 REMAIN THE SAME.
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SHT CD-11 DETAIL #1 CLEAR FLOOR SPACE
 AT THE TOILET SHALL COMPLY WITH ONE OF 3
 SHOWN ON PAGE 7.43 FHA DESIGN MANUAL.
 ***RESPONSE NOTED, BUT BOTH DIMENSIONS
 SHALL BE SHOWN.
  
 6. SHT CD-11 RESIDENTIAL UNIT
 ACCESSIBLITY NOTES:
 #7 OK
 #8(II)(B)(V) CALLS FOR DETAIL 3/CD-4.
 NO DETAIL 3 FOUND THAT SHEET. CLARIFY.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT IT NOW CALLS FOR
 DETAIL 3/CD-11. THIS DETAIL DOES NOT
 SHOW LAVS/VANITIES. SECTION 104.2.1.
  
 7. OK
  
 8. SHT CD-12 NOTES FOR W/C REFERENCE
 DETAIL 3/CD-03.DETAIL NOT FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT IT ONLY SHOWS
 DIMENSION 5'6". BOTH DIMENSIONS SHALL BE
 SHOWN. PAGE 7.43.
  
 9.OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
  
 16. SHT A1-04 4TH FLOOR BALCONYS APPEAR
 TO HAVE A PARAPET WALL ON ALL THREE
 SIDES. SHT REFERENCES DETAIL 1/A6-05,
 BUT SHT A6-05 WAS NOT SUBMITTED. SHT
 ALSO REFERENCES DETAIL 11/A6.20 WHICH
 SHOWS 1-1/2" WEEP HOLES. DRAINAGE PER
 SECTIONS 1106 & 1107WILL BE REQUIRED
 FOR STORM WATER IF A PARAPET WALL IS ON
 ALL SIDES. PLEASE SUBMIT A DETAIL AND
 CLARIFY. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT SCUPPERS SHALL BE
 A MINIMUM 4" HIGH. SECTION 1503.4.2. THE
 PEDESTRAIN TRAFFIC COATING IS INDICATED
 AS 4" HIGH UP THE WALL ON DETAIL
 11/A6.20. THIS APPEARS TO COVER THE
 SCUPPERS. PLEASE CLARIFY OR SUBMIT AN
 ELEVATION DETAIL OF THE SCUPPERS.
 SECTION 104.2.1.
  
 17. SHTS A3-20, A3-21 SHOW DIMENSIONS OF
 OPENINGS FOR EACH WATER CLOSET. MINIMUM
 33" OPENING REQUIRED. 18" OFF THE WALL
 TO THE CENTER OF THE FIXTURE, AND
 MINIMUM 15" TO THE NEXT FIXTURE. MINIMUM
 18" OFF ONE FIXTURE, AND 15" MINIMUM OFF
 THE OTHER FIXTURE. FHA DESIGN MANUAL
 PAGES 7.43, 7.44, 7.45, 7.46.
 ***RESPONSE NOTED, BUT DETAILS 7 & 9 SHT
 A3-20, (INDICATED AS 2ND DETAIL #5), AND
 DETAILS 3 & 4 SHT A3-21, THE 18" FROM
 THE CENTERLINE OF THE WATER CLOSET TO
 THE WILL IS AN ABSOLUTE MEASUREMENT, NOT
 A MINIMUM AS SHOWN. PAGE 6.5 FHA DESIGN
 MANUAL.
  
 18. N/A
 19. SHT A1-18 OVERFLOW SCUPPERS ARE
 REQUIRED FOR THE UPPER ROOF. SECTION
 1106.5. SHOW LOCATION AND INDICATE SIZE
 OF OVERFLOW SCUPPERS PER SECTION 1101.7,
 1107.3 AND TABLE 1106.7.
 ***RESPONSE NOTED, BUT OVERFLOW SCUPPERS
 ARE NOT INDICATED ON THE MECHANICAL ROOM
 OR STAIRWELL ROOFS. SECTIONS 1107.1,
 1107.2 & 1107.3.
  
 20. SHT AP1-06 SHOW THE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTION 1107.
 ***RESPONSE NOTED, BUT THE SECONDARY
 DRAINS ARE REQUIRED AT THE 6TH FLOOR
 DECK AREA. PLEASE INDICATE THE LOCATION,
 SIZE AND SQUARE FOOTAGE DRAINED BY EACH
 SECONDARY DRAIN. SECTION 1107.1, 1107.2,
 AND 1107.3.
  
 21. SHT ID7-01 PER SECTION 1210.2 WALLS
 WITHIN 2' OF A WATER CLOSET SHALL BE
 NONABSORBENT UP TO 4'. PLANS INDICATE
 THAT ONLY THE WALL BEHIND THE WATER
 CLOSET HAS TILE. PLEASE INDICATE HOW THE
 VINAL WALL PAPER COMPLYS WITH THE NON-
 ABSORBENT REQUIREMENT.
 ***RESPONSE NOTED, BUT A SUBMITTAL FOR
 THE PRODUCT, WITH INSTALLATION
 INSTRUCTIONS, SHALL BE SUBMITTED FOR
 REVIEW AND APPROVAL. SECTION 104.2.1.2.
  
 22. SHT ID8-01 DETAILS 1 & 2 SHOW THE
 FOLLOWING ON THE DETAILS:
 11-4.16.2 CLEAR FLOOR SPACE (W/C) OK
 11-4.16.3 HEIGHT 9W/C) OK
  
 11-4.16.5 FLUSH CONTROLS (W/C) NOT
 ADDRESSED.
  
 11-4.16.6 DISPENSERS (W/C) OK
  
 11-4.19.2 HEIGHT & CLEARANCES (LAV)
 CLEARANCES NOT ADDRESSED.
  
 11-4.19.3 CLEAR FLOOR SPACE (LAV) OK
  
 11-4.19.5 FAUCETS (LAV) NOT ADDRESSED
  
 11-4.19.6 MIRRORS (LAV) OK
 11-4.22.3 5' TURNING AREA (TOILET ROOM)
 OK
 23. OK
  
 24. ALL PLUMBING SHEETS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET, AND IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS, THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.2055
 ***RESPONSE NOTED, BUT LICENSE NUMBER IS
 NOT IS NOT INDCATED.
  
 25. OK
  
 26. SHT P0-01 PLUMBING FIXTURE SCHEDULE,
 SHOW ALL PIPE SIZES TO ALL WATER
 HEATERS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT EWH-3
 SPECIFICATION SHEET INDICATES 1-1/4"
 OPENING FOR THE HOT & COLD WATER.
 FIXTURE SCHEDULE INDICATES 1/2" COLD
 WATER SUPPLY. PLEASE CORRELATE SUPPLY
 SIZE PIPE FOR ALL HEATERS WITH MANUF.
 SPECIFICATION FOR PIPE SIZE CONNECTIONS.
 SECTION 104.2.1.
  
 27. N/A
 28. N/A
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
  
 36. SHT P2-00 NO KEYED NOTE FOR #5
 FOUND. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT KEY NOTE #1 WAS
 CHANGED TO #3 ON THE FLOOR PLAN AND DOES
 NOT REFLECT THE INFORMATION INDICATED IN
 KEY NOTE. PLEASE CLARIFY SECTION
 104.2.1.
  
 37. SHT P2-00 RD-21, SV2, SV3, SV-4, P1.
 P2, P-3, CD-10 AND OTHER RISERS SHOWN ON
 SHT P2-01 BUT NOT SHOWN ON THIS SHEET.
 ALL RISERS START ON THE FIRST FLOOR AND
 ALL RISERS LOCATIONS SHALL BE SHOWN
 WHERE THEY START IN THE SYSTEM.
 ***RESPONSE NOTED, BUT MANY RISER
 NUMBERS CHANGE FROM FLOOR TO FLOOR ON
 THE FLOOR PLAN. SOME RISERS ARE NOT
 INDICIATED ON THE FIRST FLOOR, SOME
 RISER DESIGNATIONS HAVE NO RISER
 DIAGRAMS. SOME RISER START OFF AS ONE
 RISER NUMBER, CHANGE TO ANOTHER RISER
 NUMBER AND THEN CHANGE BACK TO THE
 ORIGINAL NUMBER. PLEASE CORRELATE ALL
 RISERS. SECTION 104.2.1.
  
 38. EACH SANITARY RISER DIAGRAM, BE IT A
 CONVENTIONAL SYSTEM OR A SOVENT SYSTEM
 RISER SHALL HAVE ITS OWN RISER
 DESIGNATION, SUCH AS P-1, P-2. P3 OR
 SV-1, SV-2, SV-3 ETC. SHOWING MULTIPLE
 RISERS WITH THE SAME RISER DESIGNATION
 IS CONFUSING BECAUSE, (FOR EXAMPLE), NOT
 ALL P-1 RISERS ARE THE SAME AS THE
 PIPING IS NOT ALWAYS THE SAME AND THE
 OFFSETS ARE NOT ALL THE SAME FOR EACH
 P-1. SEE FOR EXAMPLE THE WATER RISERS,
 THE CONDENSATE RISERS, OR THE STORM
 RISERS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT THE RISERS ARE
 STILL CONFUSING. ALL SANTARY RISERS
 SHOULD HAVE THERE OWN RISER NUMBER.
 EXAMPLE SANT. 1, SANT. 2, SANT. 3 ETC.
 EACH RISER CAN BE A TYPICAL OF A RISER
 TYPE FOR EXAMPLE SV-4 OR P-4, BUT EACH
 RISER WOULD BE ABLE TO BE LOCATED
 INDIVIDUALLY, AND WHEN A COMMENT IS MADE
 CONCERNING A SANT. RISER, IT WOULD BE
 EASY TO UNDERSTAND WHICH RISER IS BEING
 COMMENTED ON.SECTION 104.2.1.
  
  
 39. ALL SHEETS SHOWING PIPING ON FLOOR
 PLANS: SHOW ALL PIPING INCLUDING ARMS TO
 LAVS OR KITCHEN SINKS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT NO PIPING IS
 SHOWN FOR COMMON AREA TOILET ROOMS 104,
 & 105. SECTION 104.2.1.
  
 40. OK
  
 41. SHT P2-01 RISERS RD-6, RD-9, RD-12
 AND RD-13 HAVE BEEN OFFSET, BUT NO
 OFFSET PIPING IS SHOWN. PLEASE SHOW ALL
 OFFSET PIPING ON PLANS. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT RD-6 RISER STILL
 DOES NOT REFLECT THE FLOOOR PLAN.
 SECTION 104.2.1.
  
 42. SEE COMMENT 38.
 43. SEE COMMENT 38
 44. SEE COMMENT 38
 45. SEE COMMENT 38
  
 46. SHT P2-02 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SQUARE FOOOTAGE BEING
 DRAINED AT EACH PRIMARY DRAIN AND SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED IN CALCULATIONS AS WELL
 AS ANY AREAS FROM UPPER ROOFS ADDED TO
 THE DECK AREA.
 ***RESPONSE NOTED, BUT CALCULATIONS FOR
 PRIMARY ROOF DRAINS AND FOR AREA DRAINS
 FOR THE 6TH FLOOR TERRACE AREAS HAVE NOT
 BEEN SUBMITTED. TABLE 1106.3
  
 47. SHT P2-02 MANY AREA DRAINS ARE
 MISLABELED AS PLANTER DRAINS, MANY
 DRAINS ARE NOT LABELED, MANY LABELS SHOW
 NO DRAIN. PLEASE CLARIFY. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT SOME DRAINS ARE
 STILL MISLABELED. SECTION 104.2.1.
  
 48. OK
 49. SEE COMMENT 38
 50. SEE COMMENT 38
 51. SEE COMMENT 38
 52. SEE COMMENT 38
 53. SEE COMMENT 38
 54. SEE COMMENT 38
 55. SEE COMMENT 38
 56. SEE COMMENT 38
 57. SEE COMMENT 38
 58. SEE COMMENT 38
 59. SEE COMMENT 38
 60. SEE COMMENT 38
 61. SEE COMMENT 38
 62. SEE COMMENT 38
 63. SEE COMMENT 38
 64. SEE COMMENT 38
 65. SEE COMMENT 38
 66. OK
 67. SEE COMMENT 38
 68. SEE COMMENT 38
 69. SEE COMMENT 38
 70. SEE COMMENT 38
 71. SEE COMMENT 38
 72. SEE COMMENT 38
 73. OK
 74. OK
 75. OK
  
 76. SHT P2-06 THE VENTS THRU THE ROOF DO
 NOT REFLECT THE VENTS SHOWN ON SHT P2-05
 FOR LOCATION. PLEASE CORRELATE VENTS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT SOME VENTS ARE
 NOT SHOWN OR DO NOT CONNECT TO OTHER
 VENTS AS SHOWN BELOW. SECTION 104.2.1.
  
 77. OK
 78. OK
 79. OK
 80. OK
 81. OK
 82. OK
 83. OK
 84. OK
 85. OK
  
 86. SHT P4-00 ALL SV RISERS DO NOT
 REFLECT THE FLOOR PLANS FOR THE FIRST
 FLOOR PIPING. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT THE SOME RISERS
 DO NOT REFLECT THE FLOOR PLANS ON THE
 FIRST FLOOR, OR AT THE OFFSETS. SOME
 RISERS REFLECT THE FLOOR PLANS IN ONE
 INSTANCE, BUT THE FLOOR PLAN CHANGES FOR
 THE SAME RISER IN ANOTHER INSTANCE.
 RISER CAN NOT BE TYPICAL IF NOT EXACTLY
 THE SAME IN EACH CASE. SECTION 104.2.1.
  
 87. SHT P4-00 ALL SV RISERS DO NOT
 REFLECT THE FLOOR PLANS FOR THE 16TH
 FLOORS. NO VENT PIPING SHOWN FOR THE
 REVENTS SHOWN ON THE 16TH FLOOR. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT FOR EXAMPLE THE
 VENTS P1/P19/SV-13/SV-1 ARE CONNECTED
 TOGETHER ON THE FLOOR PLAN, BUT THE VTR
 ON THE ROOF PLAN DOES NOT SHOW THIS.
 SV-13 DOES NOT INDICATE CONNECTING TO
 SV-1. P19 OFFSET VENT BUT DOES NOT
 INDICATE TO WHICH VENT STACK. THIS IS
 EVEN MORE OF A PROBLEM WHEN THERE ARE
 MORE THAN ONE RISER FOR A RISER
 DESIGNATION. (SEE COMMENT 38).
  
 88.OK
  
 89. SHT P4-00 16TH FLOOR SHALL BE
 DIFFERENT FROM OTHER FLOOR ON ALL RISERS
 AS THE VENTING/REVENTING IS ONLY ON THIS
 FLOOR. SHOW ALL VENTING/REVENTING ON
 RISERS. (THIS IS REQUIRED FOR ALL VENTS
 INCLUDING SOVENT SYSTEM IF VENTS FROM
 OTHER STACKS ARE TYING INTO THEM.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT SOME FLOORS ARE
 NOT TYPICAL AND INDIVIDUAL FLOORS FOR
 THE FLOORS THAT ARE NOT TYPICAL SHALL BE
 SUBMITTED SEPARATELY.
  
 90. OK
 91. OK
  
 92. SEE COMMENT 38
  
 93. SHT P4-00 SUBMIT A RISER DIAGRAM FOR
 EACH SANTITARY RISER DIAGRAM AND EACH
 SOVENT RISER DIAGRAM. COMMON RISERS WITH
 DIFFERENT FLOOR PLANS ARE NOT
 ACCEPTABLE. IF THE TUB AND LAV ARE ON
 THE OPPOSITE SIDE OF THE WATER CLOSET
 FROM ONE FLOOR PLAN TO THE OTHER, OR
 OFFSETS ARE DIFFERENT, OR ON DIFFERENT
 FLOOR PLANS, THEN SEPARATE RISER
 DIAGRAMS ARE REQUIRED. RISER DIAGRAMS
 SHALL REFLECT THE FLOOR PLAN FROM THEIR
 CONNECTION TO THE BUILDING DRAIN UP THRU
 THE ROOF FOR VENTING. BECAUSE THIS IS AN
 ENGINEERED SYSTEM, SEPARATE RISERS ARE
 REQUIRED, AND SEPARATE RISER
 DESIGNATIONS ARE REQUIRED. SOME RISERS
 CHANGE RISER NUMBERS FROM FLOOR TO FLOOR
 PLEASE CLARIFY. FLOOR PLANS SHOW REVENTS
 FROM OTHER RISERS TYING TOGETHER PRIOR
 TO VENTING THRU THE ROOF. THIS IS NOT
 REFLECTED ON ANY OF THE RISER DIAGRAMS.
 ***RESPONSE NOTED, BUT PROBLEM NOT
 ADDRESSED. SEE COMMENT 38.
  
 94. SUBMIT AN APPROVED DESIGN MANUAL FOR
 THE SOVENT SYSTEM. SUBMIT MANUFACTURE
 SPECIFICATIONS FOR AERATORS AND
 DEAERATORS FOR PRODUCT APPROVAL PER
 SECTIONS 303.1 & 303.4.
 ***COMMENT NOT ADDRESSED. NO RESPONSE.
  
  
 95. PLANS APPEAR TO BE INCOMPLETE AT
 THIS TIME, AS ALL THE SV RISERS ARE NOT
 SUBMITTED AS WELL AS THE BLDG DRAIN FOR
 OTHER SYSTEMS. OTHER COMMENTS MAY OR MAY
 NOT FOLLOW UPON SUBMITTAL OF REQUIRED
 INFORMATION AND INFORMATION NOT
 SUBMITTED AT THIS TIME. SECTIONS 106.1.1
 AND 106.3.5.1.3.
 ***RESPONSE NOTED, BUT PLANS DO NOT SEEM
 TO BE COMPLETE YET. (SEE NEW COMMENTS)
  
 96. SHT P4-01 ALL STACKS, RELIEF VENTS
 ARE REQUIRED PER SECTION 914.1 AND SHALL
 BE PROVIDED AT EACH 10TH INTERVAL
 BEGINNING WITH THE TOP FLOOR. SECTION
 914.1.
 ***RESPONSE NOTED, BUT THE STACKS WITH
 VENT STACKS REQUIRE RELIEF VENTS PER
 SECTION 914.1 HAS NOT BEEN ADDRESSED.
  
 97. OK
 98. OK
 99. OK
  
 100. SHT P4-02 RISERS W1, W2, W6, W8, &
 W10 FULL OPEN VALVES SHALL BE INSTALLED
 ON THE BASE OF EVERY WATER RISER PIPE.
 SECTION 606.1(3).
 ***RESPONSE NOTED, BUT W8 RISER STILL
 SHOWS NO VALVE.
  
 101. SHT P4-04 SUBMIT THE BUILDING STORM
 DRAIN IN AN ISOMETRIC RISER DIAGRAM THAT
 REFLECTS THE PIPING SHOWN ON THE
 UNDERGROUND PLUMBING PLAN SHT P2-00.
 SECTION 106.3.5.1.3. SHOW ALL PIPE SIZES
 AND SQUARE FOOTAGE AS IT ACCUMULATES IN
 THE SYSTEM. IDENTIFY ALL RISERS AS THEY
 CONNECT TO THE BUILDING DRAIN IN THE
 ISOMETRIC DIAGRAM OF THE BUILDING DRAIN.
 SHOW ALL OFFSETS IN THE STORM RISERS,
 AND INDICATE ALL PIPE SIZES.
 ***RESPONSE NOTED, BUT RISER NUMBER ARE
 NOT SHOWN TO IDENTIFY RISERS. (EXAMPLE
 RWL-1, RWL-2 ETC.). SECTION 104.2.1.
  
 102. SHTS P4-05 & P4-06 INDICATE
 MATERIAL FOR CONDENSATE SYSTEM. NO
 FLAMABLE MATERIAL IN THE AIR CONDITION
 ROOM IF IT IS USED AS A PLENUM. INDICATE
 METHOD OF VENTING THE CONDENSATE RISERS.
 VENTS CAN NOT TERMINATE IN THE WALLS OR
 IN A PLENUM.
 ***RESPONSE NOTED, BUT THE MATERIAL FOR
 THE CONDENSATE SYSTEM WAS NOT FOUND ON
 SHT P0-01. SECTION 104.2.1.
  
 103. SHTS P4-05 & P4-06 SUBMIT A
 BUILDING DRAIN CONDENSATE ISOMETRIC
 RISER DIAGRAM THAT REFLECTS THE
 UNDERGROUND PIPING ON SHT P2-00. SECTION
 106.3.5.1.3.
 ***RESPONSE NOTED, BUT THE HORIZONTAL
 BUILDING DRAIN FOR THE CONDENSATE IS
 REQUIRED BY SECTION 104.3.1.1. THE
 CONDENSATE AND THE WATER HEATER PAN
 DRAIN LINE CAN NOT BE COMBINED. SEPARATE
 DRAIN LINES AND SYSTEMS ARE REQUIRED.
 SECTION 504.8.2.
  
 104. SHT P5-00 DETAIL 05 WASHER BOX
 CONNECTION WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASHER BOX PER 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 ***RESPONSE NOTED, BUT WATER HAMMER
 ARRESTORS ARE NOT SHOWN. SECTION
 104.2.1.
  
 105. OK
 106. OK
  
 107. SHT P5-00 DETAIL 04 WATER HEATER
 SUBMIT EMERGENCY PAN DRAIN ISOMETRIC
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 MATERIAL, AND TERMINATION POINT. SECTION
 106.3.5.1.3.
 ***RESPONSE NOTED, BUT RESPONSE DID NOT
 ADDRESS COMMENT. SECTION 104.3.1.1.
  
 108. OK
  
 109. SHT P5-00 DETAIL 07 DOMESTIC WATER
 BOOSTER PUMP DETAIL: SUBMIT MANUF.
 SPECIFICATION SHEETS FOR PUMP. PUMP
 SHALL BE LISTED. SECTION 303.4.
 ***RESPONSE NOTED, BUT RESPONSE NEEDS TO
 BE CLARIFIED. SCHEDULED PUMP?
  
 110. OK
 111. OK
 112. OK
  
 113. ALL SETS OF PLANS AND ALL SHEETS IN
 EACH SET OF PLANS: IF THE DESIGN
 PROFESSIONAL IS AN ENGINEER, THEN HE OR
 SHE SHALL AFFIX HIS OR HER OFFICIAL
 SEAL, SIGNATURE AND DATE TO SAID
 DRAWINGS AS REQUIRED BY FLORIDA
 STATUTES. NO INITIALS. LEGAL SIGNATURE
 IS REQUIRED.
 ***RESPONSE NOTED, BUT INITIALS APPEAR
 TO BE SUBMITTED IN PLACE OF A SIGNATURE.
 IF THIS IS THE LEGAL SIGNATURE, PLEASE
 SUBMIT A SIGNED, SEALED, DATED,
 NOTORIZED LETTER INDICATING LEGAL
 SIGNATURE FOR OUR FILES. FAC
 61G15-23.002(2) AND FS
 471.025.
  
 114. SUBMIT WATER ISOMETRIC RISER
 DIAGRAMS FOR EACH UNIT SHOWING ALL PIPE
 SIZES, VALVES, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9.
 SECTION 106.3.5.1.3.
 ***RESPONSE NOTED, BUT RESPONSE HAS
 NOTHING TO DO WITH COMMENT INFORMATION
 REQUESTED. SECTION 104.3.1.1.
  
 115. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS APPLICATION:
  
 ***DUE TO THE FACT THAT THERE ARE NOT
 APPROVED GAS PLANS FROM PHASE I, THE
 INFORMATION IS STILL REQUIRED.***
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT CORRESPONDING
 LENGTHS NOT SHOWN. FBC-2001 FUEL GAS.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ***RESPONSE NOTED, BUT INFORMATION SHALL
 BE LOCATED AT RISER WITH REQUIRED INFO.
 SECTION 104.2.1.
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ***RESPONSE NOTED, INFORMATION REQUIRED
 ON PLANS WITH RISER.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ***RESPONSE NOTED, BUT TOTAL BTU LOAD OF
 SYSTEM NOT SHOWN. INFORMATION REQUIRED
 ON PLANS WITH RISER.
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ***NO RESPONSE NOT ADDRESSED.
  
 F. NA
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF
 2 PSI INDICATE LOCATION OF REGULATORS
 AND SUBMIT MANUF. SPECIFICATION SHEETS
 FOR REGULATORS INDICATING MODEL. IF
 VENTED REGULATORS, INDICATE MATERIAL FOR
 VENTS AND SHOW ROUTING OF PIPING.
 ***NO RESPONSE, NOT ADDRESSED.
  
 H. NA
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
  
 J. N/A
 K. N/A
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RESUBMIT RED LINED SET OF
 PLUMBING PLANS FROM FIRST REVIEW TO HELP
 TO EXPEDITE THE SECOND REVIEW.
 ***NO RESPONSE, NOT ADDRESSED ADDING
 MANY HOURS TO REVIEW. RED LINED SET OF
 PLUMBING PLANS TO BE RETAINED TO
 EXPEDITE NEXT REVIEW.
  
 END OF COMMENTS FROM FIRST REVIEW.
  