| 2006-10-04 00:00:00 | -----------------DENIED----------------- |
| | NOTE:THESE COMMENTS ARE NUMBERED FOR |
| | CONTINUITY WITH PREVIOUS PLAN REVIEW |
| | COMMENTS AND RESPONSES. |
| | |
| | FBC 2001 |
| | FBC,M 2001 |
| | |
| | 1. OK |
| | |
| | 2. PG.A8-10 RESIDENTIAL DOOR SCHEDULE: |
| | MECHANICAL CLOSET DOORS INDICATES WOOD |
| | DOORS WITH INTUMESCENT PAINT. ABSENT A |
| | LISTING FROM AN APPROVED TESTING AGENCY |
| | SHOWING THIS ASSEMBLY TO BE |
| | NON-COMBUSTIBLE, IT MUST BE SUBMITTED |
| | UNDER FBC 103.7.1 ALTERNATE MATERIALS |
| | AND METHODS. |
| | |
| | 3. PG.M2-00 EF1 & EF2, PLEASE INDICATE |
| | WHETHER THESE FANS ARE TO RUN CONTINUOUS |
| | OR BE THERMOSTATICALLY CONTROLLED. WILL |
| | THEY WORK IN ANY WAY IN CONJUNCTION WITH |
| | GEF1 OR CO SENSORS? |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | 6. PG.M2-01 NO LONGER SHOWS A CONDENSER |
| | LOCATED INDOORS. HOWEVER, STORAGE ROOMS |
| | X47 AND X48 DO NOT SHOW WHAT EQUIPMENT |
| | IS TO BE USED. IF THEY ARE SPLIT SYSTEMS |
| | THERE IS NO LOCATION OF CONDENSERS SHOWN |
| | ON PLAN. |
| | |
| | 7. PG.M3-00 UNIT 'D1' SHOWS A 30X12 |
| | RAFG. IS THIS A TRANSFER GRILL THROUGH A |
| | WALL OR IS IT GOING INTO A PLENUM |
| | CEILING?PER 601.4 A TRANSFER GRILL |
| | WOULD REQUIRE A MINIMUM OF 450 SQ.IN. |
| | SINCE IT IS RETUNING 900 CFM. IF THERE |
| | IS A CEILING PLENUM, THERE CAN BE NO |
| | EXHAUST DUCTS UNDER POSITIVE PRESSURE IN |
| | THE PLENUM PER 601.3. |
| | |
| | 8. OK |
| | |
| | 9. PLEASE PROVIDE DETAIL/SPECS FOR TYPE |
| | OF DRYER VENT HOOD (WALL CAP) TO BE |
| | USED. TYPE OF WALL CAP MAY IMPACT |
| | ALLOWABLE DRYER DUCT LENGTH PER DRYER |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| | |
| | 10. SUBMITTAL DATA FOR GOODMAN |
| | RESIDENTIAL A/C EQUIPMENT ONLY SHOWS |
| | COPPER LINE SIZES UP TO A LENGTH OF 35'. |
| | PROVIDE DOCUMENTATION SIGNED AND SEALED |
| | BY A GOODMAN ENGINEER (NOT A SALESMAN) |
| | AFFIRMING SUITABILITY OF SPECIFIED |
| | EQUIPMENT FOR COPPER LINE LENGTH AND |
| | VERTICAL DISTANCE BETWEEN AIR HANDLERS |
| | AND CONDENSING UNITS. PROPER COPPER LINE |
| | SIZES FOR THIS APPLICATION ARE ALSO |
| | REQUIRED. |
| | |
| | 11. OK |
| | |
| | 12. PG.M4-00 FBC 412.5 SMOKE CONTROL |
| | REQUIRES REMOVAL OF THE PRODUCTS OF |
| | COMBUSTION (SMOKE) VIA NATURAL OR |
| | MECHANICAL VENTILLATION. PLEASE CLARIFY |
| | HOW SMOKE IS TO BE REMOVED FROM EFFECTED |
| | AREAS. THE SYSTEM DESCRIBED ON THIS PAGE |
| | DOES NOT APPEAR TO BE RELATED IN ANY WAY |
| | TO MEETING THE REQUIREMENTS OF FBC |
| | 412.5. |
| | |
| | 13. OK |
| | |
| | 14. OK |
| | |
| | 15. PG.M5-01 DETAIL #11 STILL SHOWS DUCT |
| | SMOKE DETECTOR IN R/A PLENUM. DUCT SMOKE |
| | DETECTORS ARE TO BE INSTALLED IN SUPPLY DUCTS |
| | PER FBC,M 606.2.1. |
| | |
| | PLEASE NOTE: THIS REFERS TO DETAIL #11, NOT DETAIL #4. |
| | |
| | 16. OK |
| | |
| | 17. OK |
| | |
| | 18. OK |
| | |
| | 19. PG.M2-00 AHU 1 SHOWS 16X14 SUPPLY AND |
| | 10" ROUND O/A DUCTS PENETRATING RATED WALLS. IT |
| | IS NOT CLEAR ON PLANS IF AHU 1 O/A INTAKE |
| | COMPLIES WITH FBC,M 401.5.1 INTAKE OPENINGS. |
| | ITS PROXIMITY TO A PARKING SPACE INDICATES IT IS |
| | IN THE PARKING GARAGE, WHICH IS A PROHIBITED LOCATION. |
| | |
| | 20. PG.M2-00 AHU 1 DOES NOT SHOW ANY |
| | RETURN AIR FROM LOBBY OR MAIL ROOM AREAS. |
| | |
| | 21. PG.M2-00 6" ROUND SUPPLY TO MAIL ROOM |
| | SHOWS A FIRE DAMPER IN-LINE.HOW WILL FIRE |
| | DAMPER ACCESS BE PROVIDED IN FLEXIBLE DUCT? |
| | |
| | 22. PG.M2-00 AHU 2 DOES NOT SHOW ANY |
| | RETURN AIR FROM SUNDRIES SHOP. |
| | |
| | 23. PG.M3-00 - M3-02 UNITS C,D1,D2,D3, |
| | E,F,G,P1,P2,P3 SHOW TRANSFER GRILLS LOW ON |
| | ONE SIDE OF WALL AND HIGH ON OTHER SIDE. IS |
| | THE INTENTION TO USE THE STUD WALL CAVITY TO |
| | CONVEY RETURN AIR FROM BEDROOMS? IF SO, |
| | PLEASE PROVIDE DETAIL SHOWING COMPLIANCE |
| | WITH BOTH FBC,M 602.3(5) AND FBC CH.13 |
| | SECTION 610.1.ABC.3.6. |
| | |
| | 24. PG.M4-00 NO INFORMATION IS PROVIDED |
| | AS TO TYPE OF DUCT TO BE USED IN SHAFTS OR |
| | THE REQUIRED THICKNESS/R-VALUE OF DUCT |
| | INSULATION. ENSURE DIMENSIONS OF SHAFTS ARE |
| | LARGE ENOUGH TO ACCOMODATE DUCT INSULATION |
| | DIMENSIONS WITH SUPPORTS AND STANDING |
| | SEAMS AT DUCT JOINTS. |
| | |
| | 25. PG.M4-00 RTU SYSTEMS 1,2,3 SHOW |
| | 24X24 DIFFUSERS IN CORRIDORS. WHAT SIZE |
| | NECKS AND DUCT CONNECTIONS ARE NEEDED |
| | TO ACHIEVE DESIRED CFM? |
| | |
| | 26. PG.M4-00 PLEASE GIVE DETAILS AS TO HOW |
| | DESIGN CFM IS TO BE ACHIEVED DURING |
| | CORRIDOR PRESSURIZATION MODE. EXAMPLE: |
| | RTU 1 IS RATED FOR 8,600 CFM. IF ALL SMOKE |
| | DAMPERS EXCEPT TWO (FLOOR ABOVE AND FLOOR |
| | BELOW) ARE CLOSED, WILL FAN SPEED BE ADJUSTED |
| | TO PROVIDE CFM CALLED FOR ON PLAN DURING THIS |
| | MODE? WILL CORRIDOR DUCT BE CONSTRUCTED SO |
| | AS TO WITHSTAND THE ADDITIONAL |
| | VOLUME/PRESSURE? |
| | |
| | 27. PG.M4-00 RTU SYSTEMS 2,3 SHOW ONE |
| | 24X24 DIFFUSER ON EACH FLOOR BUT THERE IS A |
| | NOTE AT THE LOCATION WHICH SAYS "(QTY 2)". |
| | PLEASE CLARIFY. |
| | |
| | 28. PG.M4-01 RD-1 AND RD-2 REMOVE FIRE |
| | DAMPERS FROM THESE LOCATIONS AS A CLOSED |
| | FIRE DAMPER BLADE WILL ADVERSELY EFFECT THE |
| | PERFORMANCE OF THE STAIRWELL PRESSURIZATION |
| | SYSTEM. |
| | |
| | 29. PG.M4-01 SPF-1 AND SPF-2 REQUIRE DUCT |
| | SMOKE DETECTORS PER FBC,M 606.2.1 AS |
| | THEY EXCEED 2,000 CFM. |
| | |
| | 30. PG.M5-00 PLEASE PROVIDE ALL RELEVANT SUB- |
| | MITTAL DATA FOR EXHAUST FANS AND RTUS. |
| | |
| | 31. PG.M5-01 DETAIL 4 AND 9, PLEASE PROVIDE |
| | DETAILS FOR ATTACHING CURBS, STANDS, DUCTS AND |
| | EQUIPMENT ON ROOF PER FBC,M 301.13.NOTE: |
| | THE CITY OF WEST PALM BEACH IS IN THE 140 MPH |
| | ZONE PER FBC 1606. |
| | |
| | 32. PG.M5-01 ALL FIR OR FIRE/SMOKE DAMPERS ARE |
| | TO BE UL 555 LISTED AND INSTALLED PER MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS PER FBC,M 607.1.2. |
| | |
| | REVIEW BY: RONALD J REGUEIRO |
| | 561-805-6734 |
| | [email protected] |