Plan Review Notes
Plan Review Notes For Permit 05110247
Permit Number 05110247
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-05 16:34:06**** THE EDGE PHASE II ** 17 STORY **
  
 ********** UNSAT 2ND REVIEW ***************
  
 ** PLEASE KNOW PLANS ARE NOT COMPLETE AT THIS TIME FOR
 CODE COMPLIANCE.
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS BASED ON
 PLANS SUBMITTED.
 ** PLEASE SEE NOTE BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH NEW NOTES ADDED TO THE BOTTOM OF
 THE REVIEW.
  
  
 1) NOTE: OK.
  
 2) NOTE:NO, PLEASE SEE TITLE BLOCKS FOR
 MECHANICAL/PLUMBING COMPANY DOES NOT CONTAIN THE
 CORRECT LICENSURE INFORMATION AS REQUIRED. PLEASE ALSO
 KNOW IT IS KNOWN TO THIS OFFICE THAT CEASE AND DESIST
 LETTERS WERE SENT TO THE COMPANY AND ENGINEERS AS SHOWN
 ON RECORD. PLEASE SEE NEW PLANS WERE SUBMITTED EVEN
 AFTER THIS WAS ISSUED BY THE STATE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS. PLEASE KNOW THAT ONE COMPLETE
 SET OF PLANS WILL BE FORWARDED TO THE BOARD AS
 REQUESTED BY THE STATE ONCE ALL REVIEWS ARE COMPLETED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING LICENSE INFORMATION REQUIRED ON
 TITLE BLOCKS FOR CONSULTING ENGINEERING FIRM AS
 REQUIRED UNDER FLORIDA STATUES 471.023, FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002.
 PLEASE SEE COMPANIES AS LISTED ARE PROVIDING
 ENGINEERING SERVICES" AND NO
 CERTIFICATE OF AUTHORIZATION NUMBER COULD BE LOCATED ON
 STATE WEBSITE OF DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. (DBPR).
 PLEASE KNOW AS REQUIRED BY THE SAID FLORIDA STATUES AND
 LICENSING UNDER FS
 468 FOR THIS OFFICE, ONE SET OF MEP PLANS ARE BEING
 RETAINED AND SHALL BE FORWARDED TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW OF SAID REQUIREMENTS.
 WE HAVE CONSULTED WITH THE FBPE'S ON THE ABOVE. PLEASE
 CONTACT MR. JERRY ONGLEY AND MR. DOUGLAS SUNSHINE IF
 THERE ARE ANY QUESTIONS.
 ** PLEASE KNOW, THESE REQUIREMENTS ARE ALSO FOR THE
 OTHER CONSULTING COMPANIES AS LISTED ON SAID TITLE
 BLOCKS.
  
 3) NOTE:NO, PLEASE SUBMIT ALL AS PREVIOUS REQUESTED.
 PLEASE SEE REVIEW OF CODE COMPLAINT ITEMS CAN NOT BE
 VERIFIED AS THERE HAVE BEEN CHANGES SINCE PHASE ONE
 PLANS PER RESPONSE AND REVIEW OF THESE DO NOT
 CORRELATE.110.3, 90.7, NFPA-20 ETC.
 FBC ADMIN SECTION 104.2.1
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SPECS SUBMITTED FOR FIRE PUMP CONTAIN THE
 TITLE AND THE RESPONSIBLE ENGINEER AS STEVEN FELLER OF
 FELLER ENGINEERING. STEVEN FELLER AND FELLER
 ENGINEERING ARE THE CONSULTING ENGINEERS OF PHASE-ONE.
 PLEASE CORRECT ALL SUBMITTALS FOR FIRE PUMP, FIRE PUMP
 CONTROLLER ETC.
  
 4) NOTE: NO, RESPONSE MENTIONS THIS PROJECT IS UNDER
 THE 2001 FBC WHICH WAS NOT THE REQUEST. PLEASE LIST THE
 FOLLOWING CODES ON PLANS RELEVANT TO DESIGN AS THE
 FOLLOWING CODES ARE IN EFFECT FOR THIS PROJECT UNDER
 THE 2001 FBC.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE PLANS REFERENCE ALL CURRENT CODE IN
 EFFECT FOR THIS PROJECT. PLEASE KNOW WE ARE CURRENTLY
 UNDER THE 2003 NFPA-101, 2002 NFPA-72 AND 2002 NFPA-70
 ETC.
  
 5) NOTE:NO, PLEASE SEE NOW DOORS ARE EVEN MISSING
 FROM ELECTRICAL FLOOR PLANS? PLEASE KNOW THE ENTRANCE
 LOCATION FOR ACCESS IS ALSO A MAIN CONCERN. RESPONSE
 SPEAKS OF EGRESS WHICH IS ALSO IMPORTANT, HOWEVER
 OBTAINING ACCESS TO THE MAIN ELECTRICAL ROOM IS MOST
 IMPORTANT IF THE FIRE DEPT PERSONNEL IS IN NEED OF
 SHUTTING DOWN POWER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, ENTRANCE TO MAIN ELECTRICAL ROOM SHALL BE
 DETERMINED BY THIS OFFICE AND FIRE MARSHAL'S OFFICE FOR
 ACCESSIBILITY. PLANS INDICATE ACCESS GRANTED THROUGH
 GARAGE AREA AND TRAVEL DISTANCE IN BLDG MAY REQUIRED A
 MORE ACCESSIBLE MEANS TO MAIN ELECTRICAL ROOM.
 ** PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS.
  
 6) NOTE: NO, PLEASE SEE NOTE ABOVE AS DOORS ARE NOT
 SHOWN ON LAYER AS PRINTED FOR FIRST FLR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 110.26 FOR MIN DOOR(S) REQUIRED FOR MAIN
 ELECTRICAL ROOM. PLEASE SEE ONE MAIN/EQUIPMENT LOCATED
 DIRECTLY IN-FRONT OF THE EGRESS PATH/DOOR. PLEASE SEE
 PANIC HARDWARE SHALL BE REQUIRED AND DOORS MUST OPEN IN
 THE DIRECTION OF TRAVEL. PLEASE PROVIDE A NOTE ON PLANS
 FOR THIS.
 A NOTE ON E4.00 STATES "DOOR NEEDS TO BE RELOCATED",
 HOWEVER THIS WAS NOT DONE AND IS SHOWN THE SAME IN
 A-SHEETS AND E-SHEETS.
 PLEASE ADD NOTE(S) TO PLANS FOR ALL CLEARANCES PER
 110.26 SHALL BE MET.
 4.00 ETC
  
 7) NOTE: OK.
  
 8) NOTE: NO, SAME NOTE, A BATTERY BACK UP FIXTURE IN
 STAIRS WILL BE REQUIRED MIN AT EVERY OTHER LANDING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72 WHICH REQUIRES BATTERY BACK UP
 FIXTURES IN STAIR TOWERS AND OTHER AREAS WHERE EM LTS
 ARE REQUIRED FOR MIN EGRESS PATHS.
 PLEASE SEE 7.9.2.2 WHICH STATES NO SINGLE MEANS OF OVER
 CURRENT PROTECTION OR SWITCHING ETC SHALL LEAVE ANY
 EGRESS PATHS IN TOTAL DARKNESS AS SHOWN ON PLANS.
 PLEASE KNOW AS REQUIRED BY THE AHJ AND THE FIRE
 MARSHAL'S OFFICE A BATTERY BACK-UP FIXTURE OF SOME SORT
 WILL BE REQUIRED FOR THESE EGRESS PATHS TO ALLEVIATE
 THE ABOVE.
  
 9) NOTE: NO/YES, PLEASE PROVIDE THE STAIRS SEPARATELY;
 THE CALCULATIONS SEEM TO FIGURE IN ALL OTHER AREAS. THE
 STAIR MINIMUM LIGHTING LEVELS ARE THE MOST IMPORTANT.
  
 ** PREVIOUS REVIEW NOTE **PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FORALL STAIR-TOWERS AND EGRESS PATHS.
 PLEASE SEE LS 101 7.8.1.3 WHICH REQUIRES A MINIMUM OF
 10FT/CANDLES (108 LUX) FOR STAIR TOWERS UNDER NORMAL
 CONDITIONS AND A MIN OF 1FT/CD UNDER EMERGENCY
 CONDITIONS.
 7.9.2.2
  
 10) NOTE: OK, HOWEVER PLEASE KNOW FIXTURE TYPE FOR
 STAIR TOWERS WILL BE REVISED.
  
 11) NOTE: OK.
  
 12) NOTE: NO, COULD NOT LOCATE IN PACKAGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT A LETTER FROM THE
 FLORIDA POWER AND LIGHT REPRESENTATIVE ON THE
 ACCEPTANCE OF FPL VAULT AS SHOWN.
  
 13) NOTE:NO, PLEASE SEE THERE ARE STILL SOME COMMON
 AREAS WHICH ARE MISSING CIRCUITING AND SOME MINOR
 CIRCUITS IN UNITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE
 WITH SUBMITTED PANEL SCHEDULES. REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE BE SURE TO SEE 210.52B1,210.52D,210.11C3 ETC.
  
 14) NOTE:NO, PLEASE SEE SOME HEAT STRIP UNITS ARE NOT
 INDICATING THIS. PLEASE SEE SOME OF THESE ARE SHOWN
 ABOVE THE NORMAL?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 424.3B WHICH REQUIRES OCP FOR AHU/HEAT TO BE
 SIZED AT A MIN OF 125%. PLEASE SEE SOME OCP AS
 INDICATED WILL NEED TO BE ADJUSTED.
 ** PLEASE BE SURE TO ADJUST AND CONDUCTOR SIZES AS
 NEEDED. PER 310.16,240.4 ETC
  
 15) NOTE: OK.
  
 16) NOTE: OK, HOWEVER SEE NEW NOTES WITH RESPECT TO
 PANEL SCHEDULES NOW THAT ROOMS AND AREAS ARE SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PLACE ALL AREA AND ROOM DESIGNATIONS ON PLANS.
 PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO COMPLIANCE
 WITH CIRCUITING.
  
 17) NOTE: OK.
  
 18) NOTE: NO,/ OK, PLEASE SEE THE DETECTORS ARE NOW
 SHOWN HOWEVER AS THESE ACT ON A INDIVIDUAL UNIT BASIS,
 PLEASE SEE NFPA-72 DEFINITIONS AS SMOKE DETECTORS DO
 ONLY THAT, DETECT. PLEASE ADJUST NOTES TO READ AS SMOKE
 ALARMS AS THESE ARE DEVICES WHICH ACTUALLY DETECT AND
 SOUND AN ALARM WHICH IS WHAT IS BEING STATED IN THE
 NOTES.
 PLEASE ALSO SEE 11.8.3. AS INSTALLATION ALSO INCLUDES
 ANY DEVICES WITHIN 20FT OF COOKING APPLIANCES WHICH
 REQUIRE A DIFFERENT TYPE OF DEVICE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72 11.8.3.5, 11.5.1.1 FOR SMOKE
 DETECTORS REQUIRED INSIDE AND OUTSIDE ALL SLEEPING
 RMS.
 PLEASE SEE UNIT D1, PLEASE ALSO SEE OTHER UNITS WHERE
 SD'S DO NOT APPEAR TO BE "OUTSIDE" SLEEPING AREAS OR
 CORRIDORS. PLEASE SEE A DOOR SEPARATES BEDRM HALLWAYS
 FROMLIVING/COMMON AREA OF UNIT. THIS SEEMS TO SHOW
 NO SD COVERAGE FOR AREAS OUTSIDE BEDROOMS. PLEASE FIRE
 REVIEW COMMENTS.
 ** PLEASE PLACE NOTE ON PLANS WITH REFERENCE TO THE MIN
 PLACEMENT REQUIREMENTS OF ABOVE NFPA. PLEASE SEE THAT
 SD'S ARE LOCATED A MIN OF 3' FROM BATH, KITCHEN DOORS,
 3' FROM SUPPLY REGISTERS, ETC: WITH EXCEPTIONS AS
 LISTED FOR LOCATIONS WITHIN 20' OF COOKING APPLIANCES.
 ** PLEASE SEE SPECS/LISTING FROM SD MANUFACTURE AS MANY
 REQUIRED SD'S TO BE FURTHER THAN LISTED ABOVE AND MOST
 REQUIRED SD'S TO BE 5' FROM THE RETURN AIR GRILLE.
 ** PLEASE KNOW, ANY CEILING HEIGHT VARIATIONS MAY
 CHANGE LOCATION OF SD'S, AS THEY ARE REQUIRED TO BE
 LOCATED WITHIN 12" OF THE HIGHEST POINT OF A FLAT
 CEILING.
  
 19) NOTE: OK.
  
 20) NOTE: OK, SEEM TO BE OK..
  
 21) NOTE: OK.
  
 22) NOTE: OK, HOWEVER SEE NOTE FOR FIRST FLR AREA IN
 NEW NOTE.
  
 23) NOTE:NO, PLEASE SEE 3RD FLOOR. ALSO SEE OTHER
 NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE ELECTRICAL ROOMS AND RISER DIAGRAM.
 PLEASE SEE E4.0 SHOWS ELECTRICAL RM ON EVERY FLR,
 HOWEVER RISER DOES NOT.
 PLEASE SEE OTHER COMMENTS WITH RESPECT TO ELECTRICAL
 RMS.
 215.5
  
 24) NOTE: OK.
  
 25) NOTE: NO, PLEASE SEE ONE STILL SHOWN AS 2500A'S AND
 THE OTHER 3200A'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE MAIN ELECTRICAL ROOM EQUIPMENT WITH
 RISER DIAGRAM. PLEASE SEE ONE SHOWS 3000A MAIN, THE
 OTHER 4000A, PLEASE SEE ELECTRICAL PANELS SHOWN ON 4.00
 ALSO DO NOT CORRELATE WITH RISER.
 PLEASE SEE MANY OF THESE ITEMS/LOCATIONS WERE REDLINED
 ON ONE SET.
  
 26) NOTE: NO, SEE 3RD FLR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE METER CENTERS ON ELECTRICAL ROOMS SHOWN ON
 E4.00 DO NOT CORRESPOND TO THE METER CENTERS ON 5.02
  
 27) NOTE: OK.
  
 28) NOTE: OK.
  
 29) NOTE:NO, PLEASE SEE LETTER RESPONSE MENTIONS THIS
 IS IN PHASE ONE PLANS, HOWEVER THIS BUILDING OF PHASE
 II IS BEING DONE UNDER ITS OWN RECORD AND SHALL
 INDICATE ALL INFORMATION PERTINENT TO THE DESIGN, LIFE
 SAFETY OF CONDUCTORS OVER CURRENT PROTECTION ETC.
 PLEASE SEE RESPONSE LETTER MENTIONS OCP IS AT 800A'S?,
 HOWEVER PLEASE SEE THE FEEDERS AS SHOWN ON THIS RISER
 ONLY INDICATE CONDUCTORS RATED FOR 680A'S. PLEASE SEE
 240.4B, AND 240.6. AS THE FEEDERS ARE ONLY RATED AT
 680A'S AND THE LOAD ITSELF SHOWN IS 708A'S, PLEASE MAKE
 NEEDED ADJUSTMENTS WITH THE CONDUCTORS AS SHOWN.
 310.16, 110.14
 PLEASE STILL BE SURE TO CORRELATE ALL WITH THE PHASE I
 ENGINEERING DESIGN TEAM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE OCP LOCATED AT GENERATOR WHICH IS PART
 OF THE PHASE 1 HIGH-RISE BLDG.
 PLEASE SEE EQUIPMENT SPECS INDICATE THE
 GEN AT 1000KW.
 215.5
  
 30) NOTE: OK, HOWEVER NOTES FOR SIGNAGE NOT SHOWN.
 PLEASE ALSO SEE RISER SHOWS EDPH2 AND MCB, YET EDPH2 IS
 BEING SHOWN AS MLO ON PANEL SCHEDULE.
 PLEASE SEE NEW NOTES WITH RESPECT TO THE LOCATION OF
 SUCH EQUIPMENT.
  
 ** PREVIOUS REVIEW NOTE **]
 PLEASE PROVIDE A MEANS OF DISCONNECT FOR THE FEEDERS
 COMING FROM
 GEN.225.31-225.39
 PLEASE SEE A MAIN CIRCUIT BRKR LOCATED IN EDPH2 WOULD
 BE ACCEPTABLE.
 SHALL ALSO REQUIRE SIGNAGE.
 230.2E,700.8 ETC.
  
 31) NOTE:NO, PLEASE SEE PLANS AND CIRCUITS IN THIS
 BUILDING STILL INDICATE ELECTRICAL BEING IN THIS
 BUILDING FROM A PANEL IN THE PHASE I BUILDING WHICH IS
 NOT AND WILL NOT BE PERMITTED. THESE ARE SEPARATE
 BUILDINGS AND NO ELECTRICAL IN THIS PHASE II BLDG MAY
 BE FED FROM THE PHASE II.
 PLEASE SEE FBC DEFINITIONS OF BUILDINGS, WHICH WOULD
 REQUIRE A FIREWALL, PLEASE SEE FIREWALL DEFINITION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL "GH" AS SHOWN ON RISER WHICH IS SHOWN
 FROM ANOTHER BLDG AND ANOTHER SERVICE, MAY NOT BE
 LOCATED IN THIS BLDG.230.3
 *****PLEASE KNOW AS CONDITION SET FORTH BY THE DESIGN
 TEAM ON PHASE ONE, A COMPLETE SEPARATION OF ALL
 ELECTRICAL SYSTEMS WILL TAKE PLACE AND A COMPLETE 4 HR
 SEPARATION WILL BE PROVIDED BETWEEN PARKING GARAGE AND
 PHASE II HIGH RISER BLDG. PLANS DO NOT SEEM TO
 CORRELATE WITH THIS. PLEASE KNOW, GARAGE IS NOW SHOWING
 ELECTRICAL DEVICES/SYSTEMS FED FROM TWO SEPARATE
 SERVICES WHICH WILL NOT BE PERMIT. A DEFINITIVE
 SEPARATION WILL BE PROVIDED AND CROSSING OVER OF
 SYSTEMS WILL NOT BE ACCEPTABLE.
 230.2, 230.3 ETC, 90.4
  
 32) NOTE: OK.
  
 33) NOTE: OK.
  
 34) NOTE: NO/, PLEASE SEE RISER OF THE 3/0 SHALL EXTEND
 THROUGH OUT BUILDING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A COMPLETE GROUNDING ELECTRODE RISER IN
 BLDG AND PROVIDE THIS LINE DIAGRAM ON ELECTRICAL RISER.
 THIS SHOULD INCLUDE ALL GROUNDING FOR
 TRANSFORMER(S)/SEPARATELY DERIVED SYSTEMS.250.58
  
 35) NOTE: OK.
  
 36) NOTE:NO, THE LOADS SHOWN AS CONNECTED LOADS ON
 PANELS ARE NOT THE LOAD CALCULATIONS NEEDED FOR ALL
 MAINS AND BUILDING SERVICES AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED FOR
 MAINS, SERVICES, METER CENTERS ETC. MC1?
 PLEASE SEE SOME CONNECTED LOADS DO NOT INDICATE LOADS
 AND HOW THEY WERE DERIVED?
 PLEASE KNOW VERIFICATION OF CODE COMPLIANCE FOR SERVICE
 SIZES, FEEDERS,
 SEC'S ETC CAN NOT BE VERIFIED OR REVIEWED AT THIS
 TIME.
 310.16.240.4, 220, 215.5
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AND
 FIGURED AT 125%,
 215.3, 230.42 ETC.
  
 37) NOTE: NO, NOT SUBMITTED, PLEASE KNOW THIS IS
 REQUIRED AT THIS TIME IF PERMIT IS GOING TO BE ISSUED.
 PLEASE KNOW, ANY MANUFACTURE CAN BE CHOSEN WHICH MEETS
 THE SIZES AND LISTINGS AS NEEDED. PLEASE KNOW AT ANY
 TIME AT A LATER DATE THIS MAY BE REVISED.
 90.7, 110.3
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY AND SUBMIT SPECS FOR BUS-DUCT AS LOCAL
 AMENDMENT DOES NOT PERMIT ALUM AS THE EQUIPMENT
 GROUNDING METHOD. 250.62 SEE PREVIOUS NOTES.
  
 38) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SPEC BOOKS SUBMITTED ARE FOR EQUIPMENT AND
 SPEC BOOK FOR JOB-SITE WAS NOT SUBMITTED AT THIS TIME.
 PLEASE SEE SOME OF THE ABOVE COMMENTS WHICH MAY AFFECT
 PAGES IN THE JOB-SITE SPEC BOOKS. THESE SHOULD BE
 REVIEWED AND MAKE ANY CHANGES AS NEEDED.
  
 39) NOTE: OK, THE MAINS HAVE NOW BEEN DECREASED FROM
 1000A?S DOWN TO 800A?S; HOWEVER AS LOAD CALCULATIONS
 HAVE NOT YET BEEN SUBMITTED FOR ALL, THIS IS YET TO BE
 VERIFIED FULLY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 230.95, 240.13 WHICH REQUIRES GROUND FAULT
 PROTECTION FOR SYSTEMS WITH A VOLTAGE MORE THEN 150V TO
 GROUND AND OVER 1000A'S.
 PLEASE SEE "MSBH2.
  
 40) NOTE: OK, 4-POLE SHOWN..
  
 41) NOTE:NO, NOT VERIFIED AT THIS TIME. RESPONSE
 MENTIONS PART OF PHASE I WHICH IS KNOW, HOWEVER AS THIS
 STATES THE FIRE PUMP IS NOW DIESEL AND THE SPECS
 SUBMITTED ARE FOR AN ELECTRICAL FIRE PUMP, SOME
 COORDINATION NEEDS TO TAKE PLACE WITH THE DESIGN TEAM
 FROM PHASE I AND PLEASE KNOW AT THIS TIME CODE
 COMPLIANCE WITH NFPA-20 FOR MINIMUM FUEL CONSUMPTION IF
 INDEED DIESEL CAN NOT BE CONFIRMED.
 90.7, 110.3, NFPA-20, CHAPTERS 6, 7 AND 8, AT THIS TIME
 THERE ARE TOO MANY SECTIONS TO LIST WHEN INFORMATION
 PROVIDED DOES NOT CORRELATE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING FIRE PUMP AND EQUIPMENT NOT
 INDICATED ON RISER DIAGRAM.
 PLEASE SEE 695.4B1 FOR OCP REQUIRED FOR LOCKED ROTOR.
 PLEASE ALSO SEE NFPA-20 FOR ELECTRICAL REQUIREMENTS FOR
 MEANS-OF DISCONNECT LOCATION ETC. PLEASE SEE SPECS
 SUBMITTED APPEAR TO SHOW THIS, HOWEVER NONE OF THESE
 ITEMS ARE SHOWN ON RISER. UNABLE TO VERIFY CODE
 COMPLIANCE FOR FIRE PUMP, FIRE PUMP CONTROLLER,
 FEEDERS, SEC'S ETC.
 ** PLEASE SEE SPECS WHICH CONTAIN THE TITLE FROM STEVEN
 FELLER'S OFFICE INDICATE THE PUMP AS 277/480V, 125HP.
 215.5
  
 42) NOTE: NO, PLEASE SEE RISER AND SCHEDULE STILL DO
 NOT CORRELATE.
 PLEASE SEE "ERL2", PLEASE SEE RISER 45KVA AND PANEL
 SHOWS 30 ETC.
 PLEASE SEE THE MAXIMUM OCP FOR THE 112 KVA TRANSFORMERS
 SHALL BE SIZED PER 450.3. (125%). PLEASE SEE ONLY IF
 MEETING ALL THE EXCEPTIONS, OCP CAN BE HIGHER THAN
 125%
 **PLEASE ALSO SEE NEW NOTES DUE TO PLANS AND CHANGES
 AND PANEL SCHEDULES SUBMITTED.
  
  
 **PLEASE CORRELATE ALL TRANSFORMERS WITH SCHEDULE(S).
 PLEASE SEE 112.5?, 150? KVA
 PLEASE ALSO CONFIRM KVA AS MAX OCP FOR TRANSFORMER MAY
 NOT EXCEED 125% AS 450.3
 TABLES.
  
 43) NOTE: OK.
  
 44) NOTE: NO, PLEASE ONE OF THE PREVIOUS NOTES ABOVE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE COMPLETE GROUNDING ELECTRODE
 SYSTEMS DETAIL PER
 250.50, 250.104, 250.64,,,
  
 45) NOTE: OK, HOWEVER SEE NOTES AS NOTES ABOVE WITH
 RESPECT TO THE MLO AND MCB BEING DIFFERENT ON PANEL AND
 RISER.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE EDPH2 IS SHOWN AS
 1000A'S ON PANEL SCHEDULES AND SHOWN AS 800A ON RISER??
 PLEASE CORRELATE.
 215.5
  
 46 NOTE: OK, AS MSBE HAS NOW CHANGED TO 800A?S.
  
 47)NOTE: OK, HOWEVER PLEASE KNOW, IF THIS INFORMATION
 IS NOT SUBMITTED, SEPARATE PERMITS PLANS AND FEES WILL
 BE REQUIRED BEFORE ANY SITE LIGHTING MAY BE INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL "SL" IS SHOWN AS HAVING "SITE
 LIGHTING" HOWEVER, SITE LIGHTING COULD NOT BE LOCATED
 ON ELECTRICAL PLANS?
 IF SITE LIGHTING CONTAINS LT POLES, PLEASE SUBMIT WIND
 LOAD CALCULATIONS FOR FBC 140MPH. THESE WILL BE
 REVIEWED BY A STRUCTURAL REVIEWER. ** PLEASE BE SHOULD
 POLE CONTAIN FIXTURES FOR CALCULATION PURPOSES.
  
 48) NOTE: OK.
  
 49) NOTE:NO, PLEASE SEE RISER SHOWS SOME ITEMS WHICH
 ARE STILL NOT LISTED ON PANELS SCHEDULES. PLEASE SEE
 4EH2 TO 4EL2, MISSING ON PANEL SCHEDULE AND MISSING
 TRANSFORMER INFORMATION ETC. CAN NOT BE VERIFIED AT
 THIS TIME.
  
 ** PREVIOUS REVIEW NOTE ** PLEASE LABEL ALL
 TRANSFORMERS ON RISER AS INDICATED ON PANEL SCHEDULES.
 215.5, 450, ETC
  
 50) NOTE: OK.
  
 51) NOTE:NO, PLEASE SEE NOTES WERE NOTED, HOWEVER
 PLEASE PROVIDE THE DETAIL FOR TYPICAL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A DISCONNECT DETAIL INCLUDING SIZE ETC
 FOR ROOF TOP UNITS. THIS MAY BE A "TYPICAL" DETAIL FOR
 EACH SIZE IF NOT ALL THE SAME.
 215.5, 440.11
  
 52) NOTE: OK.
  
 53) NOTE: NO, RESPONSE MENTIONS DEVICES HEIGHTS SHOWN
 ON E0.00, HOWEVER THE HEIGHTS ON DEVICES ARE NOT THE
 ONLY REQUIREMENTS FOR ELECTRICAL DEVICES. PLEASE LIST
 NOTE AS PREVIOUSLY REQUESTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FAIR HOUSING ACT
 REGULATIONS, 24 CFR 100.205 WITH RESPECT TO THE
 LOCATIONS OF "ALL" ELECTRICAL DEVICES, CONTROLS.
 A NOTE IS LOCATED ON "GEN NOTES" WHICH MENTIONS THE
 HEIGHTS FOR RECEPTS AND SWITCHES, HOWEVER THIS SHOULD
 REFLECT
 FHAR ETC AS NOTED ABOVE.
  
 54) NOTE:NO? PLEASE KNOW AS THE PHASING OF THIS
 PROJECT ANDHOW THIS IS BEING DONE AND HOW THE PLANS
 HAVE BEEN SUBMITTED SHOWING PARTS OF PHASE II BEING FED
 FROM PHASE I IS UNCLEAR.
 THE EGRESS PATH SEEMS TO HAVE BEEN SHOWN, HOWEVER AS
 THE BUILDING OF EACH PHASE IS NOT CLEAR, UNABLE TO
 REVIEW FOR ACTUAL INSTALLATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE AMENITY DECK DETAILS COULD NOT BE
 LOCATED IN SETS.
 PLEASE SEE E2.06 WHICH ONLY SEEMS TO INDICATE A PARTIAL
 AREA SHOWN.
 PLEASE SEE NO ELECTRICAL SHOWN FOR LIGHTING ETC?
 PLEASE SEE LS 101 7.8 AND 7.9 WHICH REQUIRE MEANS OF
 EGRESS LIGHTING TO THE PUBLIC RIGHT OF WAY; THIS WOULD
 INCLUDE EMERGENCY LIGHTING AS REQUIRED.
 PLANS NOW SHOW A SEPARATE PHASE LINE, AS GARAGE WAS TO
 BE BUILT WITH PHASE ONE BLDG AND DID NOT SHOW GARAGE
 WITH PHASE LINE DOWN THE CENTER OF THE GARAGE.
  
  
 ** NEW NOTES 2ND REVIEW ***
 NOTES ARE BASED ON REVISIONS MADE TO PLANS AND
 INFORMATION NOW SUBMITTED. PLEASE SEE ALSO NEW NOTES
 WHICH WERE NOT COMMENTED ON THE PREVIOUS REVIEW #63 AND
 64 AS THIS WAS NOT PART OF THE ELECTRICAL REVIEW.
  
 55) NOTE: PLEASE SEE MSBH2 IS MISSING
 CONDUCTORS/FEEDERS FOR H-2 AND SL1.
 310.16, 240.4,215.5 ETC
  
 56)NOTE: PLEASE SEE MSBH2 PANEL SCHEDULE FOR OCP
 DEVICES FOR EACH PANEL BEING SERVED DOES NOT CORRELATE
 WITH THE OCP DEVICES SHOWN ON RISER. PLEASE ALSO
 CORRELATE CONDUCTORS/FEEDERS.
 408.4, 310.16, 240.4
  
 57) NOTE: PLEASE SEE FEEDERS ON THE SECONDARY SIDE FOR
 RL2 SHOW #6'S WHICH TERMINATE IN 100A OCP. PLEASE SEE
 240.21C, 408.16, 310.16 ETC,
 PLEASE SEE THE LOAD ON THIS PANEL EXCEEDS THAT OF THE
 RATING OF THE #6'S IN EITHER CASE.
  
 58) NOTE: PLEASE SEE PANEL SCHEDULE FOR MSBH2 WHICH
 SHOWS 400A OCP FEEDING PANEL H2 WHICH IS ONLY RATED AT
 225A'S? PLEASE SEE CONDUCTORS ON PANEL SCHEDULE ARE
 MISSING HOWEVER SHOWN ON RISER.
 240.4, 408, ETC
  
 59) NOTE: PLEASE SEE RISER SHOWS FPL SERVICE
 TRANSFORMER BEING 120/208V , YET THIS IS BEING SHOWN
 FEEDING 277/480V SYSTEMS??
  
 60) NOTE: PLEASE SEE PANEL SCHEDULES FOR UNITS INDICATE
 A 1-POLE BREAKER FEEDING EACH OF THE DISHWASHER AND
 DISPOSAL RECEPTACLE, HOWEVER PLEASE SEE 210.4B AS THIS
 WOULD BE REQUIRED TO BE A 2-POLE BRKR IF FEEDING A
 DEVICE ON SAME YOKE.
  
 61) NOTE: PLEASE SEE FBC 2001 CHAPTER 13, THE ENERGY
 CALCULATIONS SUBMITTED ARE NOT SIGNED, DATED OR SEALED
 BY THE RESPONSIBLE DESIGN PROFESSIONAL.
 FS 471.025, FAC 61G15-23.002
  
 62) NOTE: PLEASE SEE FIRE SPRINKLER SHEETS ARE BEING
 SEALED WITH A SEAL AND STAMP WHICH IS NOT PERMITTED
 (RUBBER STAMP) AND SEAL WHICH IS NO LONGER VALID WITH
 THE STATE. PLEASE SEE RULING IN THE FAC 61G15-23.001
 WHICH REQUIRED ALL ENGINEERS TO OBTAIN THEIR NEW SEALS
 WITH THE WORDING OF "LICENSE" AND "CERTIFICATE" WAS NOT
 LONGER PERMITTED. THIS RULE WAS PAST IN 2/04, HOWEVER
 AN EXTENSION WAS GRANTED TO 12/31/05 ONLY.
  
 63) NOTE: PLEASE SEE FPL VAULT IS SHOWING A STROBE
 DEVICE FROM THE BUILDINGS FA SYSTEM WHICH IS NOT
 PERMITTED. NO EQUIPMENT OR ELECTRICAL DEVICES OF ANY
 KIND ARE PERMITTED IN THE FPL VAULT.
  
 64) NOTE:PLEASE SEE ALL AUDIBLE AND VISUAL DEVICES
 FOR FA SYSTEMS ARE REQUIRED TO MEET FBC 2001,
 11-4.28.1, PLEASE LIST AND SHOW COMPLIANCE FOR
 11-4.28.2 AND 11-4.28.3(4). PLEASE SEE THERE ARE MANY
 LOCATIONS FOR MIN CANDELAS DO NOT SEEM TO HAVE BEEN
 MET.
  
 65) NOTE: PLEASE SEE E2.01, PLEASE SEE AREAS AND WALL
 OUTSIDE UNIT A3, WHICH DO NOT SEEM TO BE COMPLETE?
 PLEASE CLARIFY HOW ACCESS TO THE FIRE COMMAND ROOM WILL
 TAKE PLACE, COULD NOT LOCATE ANY DOORS ON THIS SHEET
 FOR THIS??
  
 66) NOTE: PLEASE BE SURE TO GO BACK AND CHECK ALL
 KITCHEN COUNTER SPACES PER 210.52C1, E-2, G1A, ETC.
  
 67) NOTE: PLEASE SEE NOW THAT ROOM AND AREA
 DESIGNATIONS ARE PLACES ON PLANS, PLEASE REVISE PANEL
 SCHEDULES FOR UNITS TO CORRELATE WITH THESE ROOMS AND
 AREAS. INSTEAD OF GEN LTS, GEN RECEPTS, IT WOULD
 MENTION: BEDRM, #2 LTS, MASTER BDRM RECEPTS ETC.
 408.4.
  
 68) NOTE: PLEASE SEE NFPA-110 7.2.2.1. TRANSFER
 SWITCHES SHALL BE PERMITTED TO BE INSTALLED IN THE
 NORMAL ELECTRICAL SERVICE ROOM WHERE TWICE THE
 CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF NFPA 70,
 NATIONAL ELECTRICAL CODE, EXISTS BETWEEN EQUIPMENT
 ENCLOSURES.
 PLEASE ADJUST ROOM AS NEEDED AND REQUIRED.
  
  
  
 ** NOTE: PLEASE SEE MANY OF THE ABOVE ITEMS WERE
 REDLINED ON ONE SET FOR AREAS OF NOTES ABOVE.
  
 ** NOTE: PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL PLANS AND
 DESIGN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
2006-11-05 11:30:44REVIEW IN PROGRESS
2006-08-23 00:00:00REVIEW STOPPED ON 8/23 , PLANS WILL GO
 INTO "F" STATUS ONCE REVIEW IS
 COMPLETED.
 NOTES WILL FOLLOW.
2006-08-22 00:00:00REVIEW IN PROGRESS
2006-08-20 00:00:00** ONE ROLL OF MEP, FP IN ELECTRICAL
 FOR REVIEW.