Plan Review Notes
Plan Review Notes For Permit 05110247
Permit Number 05110247
Review Stop B
Sequence Number 2
Notes
Date Text
2006-12-17 15:28:55BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/22/06:
  
 1) WORKING DRAWING REVIEW ONLY.NO PERMIT CAN BE
 ISSUED UNTIL THE PERMIT APPLICATION AND FEES ARE
 SUBMITTED.
  
 2) INFORMATIVE:
 A NOTICE OF COMMENCEMENT SHALL BE RECORDED, COUNTY
 IMPACT FEES PAID AND A SIGNED THRESHOLD INSPECTION
 AGREEMENT SUBMITTED BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.1.2THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.IT IS NOTED THAT THE NAME AND LICENSE
 NUMBER OF EACH DESIGN PROFESSIONAL HAS BEEN ADDED TO
 THE ENERGY CODE COMPLIANCE FORM, BUT THE SIGNATURES AND
 DATES REQUIRED TO CERTIFY CODE COMPLIANCE HAVE NOT BEEN
 INCLUDED.BEFORE A BUILDING PERMIT CAN BE ISSUED, THE
 'CERTIFICATION' BOX ON SHEET 2 OF THE SUBMITTED ENERGY
 CODE COMPLIANCE FORMS SHALL BE SIGNED AND DATED BY THE
 'PREPARER' AND THE BUILDING OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER. ALSO, SHEET 1 SHOULD BE COMPLETED WITH
 THE PERMIT NUMBER (05110247).
  
 19) FBC 1606.1TRANSFORMER VAULT DOOR 117A.SUBMITTAL
 OF PRODUCT APPROVAL NOA# 02-0222.06 (FL2198.3) FOR A
 6070 DOUBLE DOOR IS NOTED BUT SHEETS 1 AND 2 OF 11 BOTH
 STATE MAXIMUM POSITIVE AND NEGATIVE DESIGN PRESSURES OF
 +60 PSF AND -60 PSF FOR THE PROPOSED DOOR.THE
 PRESSURES REQUIRED BY THE SUBMITTED RWDI WIND LOAD
 STUDY REPORT FOR THE SOUTH ELEVATION OF THE PHASE II
 BUILDING ARE +65 PSF AND -65 PSF.SUBMIT AN
 ALTERNATIVE PRODUCT APPROVAL.
  
 21) FBC 1606.1HORIZONTAL SLIDER WINDOW W2, W4, W6,
 W6.1.THE RESPONSE IS NOTED AS STATING THAT A CUT DOWN
 EFCO CORP. SERIES 3014 SLIDING GLASS DOOR WILL BE USED
 FOR W2 AND W6 WHERE THE REQUIRED DESIGN PRESSURE IS 95
 PSF, AND AN EFCO CORP. SERIES 3500 HORIZONTAL SLIDING
 WINDOW WILL BE USED FOR W2, W4, W6, W6.1 WHERE THE
 REQUIRED DESIGN PRESSURE IS LESS THAN 95 PSF.NO
 PRODUCT APPROVAL WAS SUBMITTED FOR EFCO CORP. SERIES
 3014 SLIDING GLASS DOOR AND ONLY ONE COPY OF THE
 PRODUCT APPROVAL (ONE COPY ATTACHED TO THE COMMENT
 RESPONSE LETTER) FOR EFCO CORP. SERIES 3500 HORIZONTAL
 SLIDING WINDOW WERE SUBMITTED.SUBMIT THREE COPIES OF
 THE PRODUCT APPROVALS INCLUDING THE FLORIDA STATEWIDE
 PRODUCT APPROVAL COVER SHEET (FL####).FOR EASE OF
 REFERENCE A COPY OF THE FLORIDA STATEWIDE PRODUCT
 APPROVAL COVER SHEET FOR EFCO CORP. SERIES 3500
 HORIZONTAL SLIDING WINDOW HAS BEEN INSERTED INTO THE
 COMMENT RESPONSE LETTER ATTACHMENT PACKET FOR YOUR
 USE.
  
 22) INFORMATIVE:
 FBC 1606.1PRODUCT APPROVAL SUBMITTAL. ALL THREE
 COPIES OF THE SUBMITTED DOCUMENT BINDERS INCLUDE SOME
 INCOMPLETE PRODUCT APPROVAL DOCUMENTS.PLEASE REVIEW
 THE BINDERS TO ENSURE THAT A PRODUCT APPROVAL HAS BEEN
 SUBMITTED FOR EACH TYPE OF PRODUCT THAT IS TO BE
 INSTALLED.PLAN REVIEW WILL ONLY ENSURE THAT THE
 BINDERS INCLUDE PRODUCT APPROVALS TO COVER THE WORST
 CASE.FOR, EXAMPLE IF ONLY A LARGE MISSILE IMPACT
 PRODUCT APPROVAL IS SUBMITTED, THAT WOULD MEET PLAN
 REVIEW REQUIREMENTS BUT IT WOULD MEAN THAT PRODUCT
 WOULD HAVE TO BE USED EVEN WHERE LARGE MISSILE IMPACT
 RATING IS NOT REQUIRED.REMOVE, FROM EACH BINDER, ALL
 PRODUCT APPROVAL DOCUMENTS WHICH ARE NO LONGER
 APPLICABLE DUE TO THE SUBSTITUTIONS MADE.ALSO, WHERE
 MULTIPLE OPTIONS ARE COVERED BY A PRODUCT APPROVAL, THE
 APPROPRIATE PAGES OF THE PRODUCT APPROVAL SHALL BE
 MARKED TO SHOW WHICH PRODUCT OPTIONS/SIZES ARE PROPOSED
 SO THAT THE APPLICABLE DESIGN PRESSURE RATING CAN BE
 DETERMINED.
  
 23) -PROVISO-
 WINDOW WALLS: THE WINDOW SHOP DRAWING SUBMITTAL SHALL
 INCLUDE A STRUCTURAL MULLION.THE MULLION MUST BE
 CAPABLE OF SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING FOR THOSE WINDOWS THAT EXCEED THE
 MAXIMUM HEIGHT STATED IN THE SUBMITTED MIAMI WALL
 SYSTEMS INC. FIXED WINDOW LARGE MISSILE IMPACT SERIES
 101 AND SMALL MISSILE IMPACT SERIES 101
 PRODUCT APPROVAL NOA'S 03-0415.18 AND 05-0420.01.
  
 24) -PROVISO-
 SLIDING GLASS DOORS:THE WINDOW/DOOR SUBCONTRACTOR
 SHALL PROVIDE RATIONAL ANALYSIS FROM A FLORIDA
 REGISTERED ENGINEER TO JUSTIFY THE USE OF THE PROPOSED
 SLIDING GLASS DOOR IN SIZES THAT EXCEED THE MAXIMUM IN
 THE SUBMITTED EFCO CORP. SERIES S-3005 SLIDING GLASS
 DOOR PRODUCT APPROVAL NOA 02-0722.02, AND MIAMI WALL
 SYSTEMS INC. SERIES 100 SLIDING GLASS DOOR PRODUCT
 APPROVAL NOA'S 04-0908.02 AND 01-1108.03.
 NOTE: MISSILE IMPACT RATING FOR THESE LARGER SIZES
 CANNOT BE JUSTIFIED BY RATIONAL ANALYSIS.MISSILE
 IMPACT TEST RESULTS MUST BE SUBMITTED.
  
 25) -PROVISO-
 HORIZONTAL SLIDER WINDOWS: IT IS NOTED THAT 'CUT-DOWN'
 SLIDING GLASS DOORS WILL BE USED FOR THOSE HORIZONTAL
 SLIDER WINDOWS WHICH EXCEED 6'-6" WIDE X 6'-0" HIGH
 (FOR EXAMPLE W2, W2.1, W3, W3.1, W3.2(SLIDER?), W3.P,
 W4, W4.1, W5, W5.1, W5.P, W6, W6.1).
  
 26) -PROVISO-
 FIXED WINDOWS:THE WINDOW SHOP DRAWING SUBMITTAL SHALL
 INCLUDE A STRUCTURAL MULLION.THE MULLION MUST BE
 CAPABLE OF SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING FOR THOSE WINDOWS THAT EXCEED THE
 6'-0" MAXIMUM HEIGHT STATED IN THE SUBMITTED MIAMI WALL
 SYSTEMS INC. SERIES 122 ALUMINUM FIXED WINDOW PRODUCT
 APPROVAL NOA 04-0322.09.
  
 28) STOREFRONT WINDOWS.PLEASE NOTE THAT THE SUBMITTED
 EFCO CORP. SERIES 5600 ALUMINUM CURTAIN WALL PRODUCT
 APPROVAL NOA# 02-0304.01 (FL 1561.1) IS RATED FOR SMALL
 MISSILE IMPACT ONLY.IT CAN ONLY BE USED IN LOCATIONS
 HIGHER THAN 30 FEET ABOVE GRADE.PLEASE NOTE THAT
 SHEET A6-61 REFERS TO THE FIRST FLOOR STOREFRONT AS SF1
 AND THE ROOF (LANTERN) STOREFRONT AS SF2 WHICH IS
 CONSISTENT WITH THE BUILDING ELEVATIONS.THE
 EXCEPTIONS ARE SHEETS A4-06 AND A4-11 SHOULD BE REVISED
 AS THEY REFER TO THE ROOF LANTERN STOREFRONT AS SF1.
  
 29) TO EXPEDITE REVIEW OF A RESUBMITTAL WHICH REQUIRES
 NEW PLANS IN ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW SHEETS
 INSERTED.ONE COPY OF EACH OLD SHEET SHOULD BE
 STAPLED/CLIPPED TO THE REMAINING OLD SHEETS, TO FORM A
 SET OF 'OLD/VOID SHEETS', FOR COMPARISON OF REVISIONS
 WHEN REVIEWING THE RESUBMITTED PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]