Plan Review Notes
Plan Review Notes For Permit 05110247
Permit Number 05110247
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-25 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 1. ALL "CS", "CD" AND ARCHITECTURAL
 SHEETS SHALL BE DATED WHEN THE SEAL AND
 SIGNATURE ARE AFFIXED TO THE DOCUMENT.
 FAC 61G1-16.003, 61G1-16.004(5) AND FS
 481.2055.
 2. SHT CD-10 APPLICABLE CODES INDICATE
 2001-FBC. CURRENT CODES IN EFFECT ARE
 FBC-2004 AND PLANS ARE TO BE DESIGNED
 PER THIS CODE. PLEASE INDICATE ON PLANS.
 3. SHT CD-10 SCUPPERS TO BE SIZED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. PLEASE INDICATE THIS ON THE
 PLANS AND THE SIZING OF THE SCUPPERS CAN
 NOT BE DETERMINED WITH OUT REFERENCE TO
 THE DEFLECTION OF THE ROOF.
 4. SHT CD-11 BACKING FOR SHOWERS ARE TO
 BE PER PAGE 6.12 FHA DESIGN MANUAL. SHOW
 ALL 3 SIDES, (ELEVATIONS) OF THE SHOWER,
 AND BACKING SHALL BE SIDE TO SIDE EACH
 ELEVATION.
 5. SHT CD-11 DETAIL #1 CLEAR FLOOR SPACE
 AT THE TOILET SHALL COMPLY WITH ONE OF 3
 SHOWN ON PAGE 7.43 FHA DESIGN MANUAL.
 6. SHT CD-11 RESIDENTIAL UNIT
 ACCESSIBLITY NOTES:
 #7 CALLS FOR DETAIL 2/A-6.11. SHT
 A-6.11 HAS NOT BEEN SUBMITTED. CLARIFY.
 SECTION 106.1.1.
 #8(II)(B)(V) CALLS FOR DETAIL 3/CD-4.
 NO DETAIL 3 FOUND THAT SHEET. CLARIFY.
 SECTION 106.1.1.
 7. SHT CD-12 NOTES FOR BATHROOM
 REFERENCE DETAIL 4/CD-05. THIS SHEET HAS
 NOT BEEN SUBMITTED. PLEASE CLARIFY.
 SECTION 106.1.1.
 8. SHT CD-12 NOTES FOR W/C REFERENCE
 DETAIL 3/CD-03.DETAIL NOT FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
 9. SHT CD-12 DETAIL 2 UNIT TYPE A2,
 U-SHAPED KITCHEN REQUIRES A 5' TURNING
 AREA. SEE PAGE 7.9 FHA DESIGN MANUAL.
 10. SHT CD-13 DETAIL 2 UNIT TYPE D3,
 SHOWER CLEAR FLOOR SPACE SHALL BE
 PARALLEL AND FLUSH WITH THE CONTROL
 WALL. PAGE 7.56 FHA DESIGN MANUAL.
 11. SHT CD-14 DETAIL 5 UNIT TYPE P3, A
 U-SHAPED KITCHEN REQUIRES A 5' DIA.
 TURNING AREA. PAGE 7.9 FHA DESIGN
 MANUAL.
 12. SHT CD-14 UNIT TYPE P1 DETAIL 3 LAV
 WITH FORWARD APPROACH TO HAVE REMOVABLE
 BASE CABINET. PAGES 7.49, 7.50, AND 7.51
 FHA DESIGN MANUAL. SUBMIT A DETAIL.
 13. SHT CD-14 UNIT TYPE P1 DETAIL 3
 U-SHAPED KITCHEN REQUIRES A 5' DIAMETER
 TURNING AREA. PAGE 7.9 FHA DESIGN MAN.
 14. SHT CD-14 DETAIL 1 UNIT TYPE G1A
 SHOWER CLEAR FLOOR SPACE SHALL BE
 PARALLEL TO SHOWER AND FLUSH WITH THE
 CONTROL WALL. PAGE 7.56 FHA DESIGN MAN.
 15. SHTS CD-12, CD-13, CD-14 ALL UNITS,
 SPECIFICATION "A" OR "B" REQUIRED TO BE
 SHOWN ON EACH UNIT/BATHROOM. FHA DESIGN
 MANUAL PAGES 7.34, 7.35.
 16. SHT A1-04 4TH FLOOR BALCONYS APPEAR
 TO HAVE A PARAPET WALL ON ALL THREE
 SIDES. SHT REFERENCES DETAIL 1/A6-05,
 BUT SHT A6-05 WAS NOT SUBMITTED. SHT
 ALSO REFERENCES DETAIL 11/A6.20 WHICH
 SHOWS 1-1/2" WEEP HOLES. DRAINAGE PER
 SECTIONS 1106 & 1107WILL BE REQUIRED
 FOR STORM WATER IF A PARAPET WALL IS ON
 ALL SIDES. PLEASE SUBMIT A DETAIL AND
 CLARIFY. SECTION 106.1.1.
 17. SHTS A3-20, A3-21 SHOW DIMENSIONS OF
 OPENINGS FOR EACH WATER CLOSET. MINIMUM
 33" OPENING REQUIRED. 18" OFF THE WALL
 TO THE CENTER OF THE FIXTURE, AND
 MINIMUM 15" TO THE NEXT FIXTURE. MINIMUM
 18" OFF ONE FIXTURE, AND 15" MINIMUM OFF
 THE OTHER FIXTURE. FHA DESIGN MANUAL
 PAGES 7.43, 7.44, 7.45, 7.46.
 18. SHT A1-17 OVERFLOW SCUPPERS SHALL BE
 SIZED PER FBC-2004 PLUMBING SECTIONS
 1101.7, 1107.3 AND TABLE 1106.7. THE
 SIZING OF THE SCUPPERS CAN NOT BE
 DETERMINED WITH OUT REFERENCE TO THE
 DEFLECTION OF THE ROOF. PLEASE PROVIDE
 CALCULATION AND SHOW COMPLIANCE WITH
 ABOVE SECTIONS AND TABLE ON PLANS
 INDICATING THE SIZE OF THE SCUPPERS.
 19. SHT A1-18 OVERFLOW SCUPPERS ARE
 REQUIRED FOR THE UPPER ROOF. SECTION
 1106.5. SHOW LOCATION AND INDICATE SIZE
 OF OVERFLOW SCUPPERS PER SECTION 1101.7,
 1107.3 AND TABLE 1106.7.
 20. SHT AP1-06 SHOW THE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTION 1107.
 21. SHT ID7-01 PER SECTION 1210.2 WALLS
 WITHIN 2' OF A WATER CLOSET SHALL BE
 NONABSORBENT UP TO 4'. PLANS INDICATE
 THAT ONLY THE WALL BEHIND THE WATER
 CLOSET HAS TILE. PLEASE INDICATE HOW THE
 VINAL WALL PAPER COMPLYS WITH THE NON-
 ABSORBENT REQUIREMENT.
 22. SHT ID8-01 DETAILS 1 & 2 SHOW THE
 FOLLOWING ON THE DETAILS:
 11-4.16.2 CLEAR FLOOR SPACE (W/C)
 11-4.16.3 HEIGHT 9W/C)
 11-4.16.5 FLUSH CONTROLS (W/C)
 11-4.16.6 DISPENSERS (W/C)
 11-4.19.2 HEIGHT & CLEARANCES (LAV)
 11-4.19.3 CLEAR FLOOR SPACE (LAV)
 11-4.19.5 FAUCETS (LAV)
 11-4.19.6 MIRRORS (LAV)
 11-4.22.3 5' TURNING AREA (TOILET ROOM)
 23. SHT ID10-01 FLOOR COVERING SCHEDULE
 DOES NOT INDICATE MEN'S OR WOMEN'S
 RESTROOMS. - WALL COVERING SCHEDULE
 (REMARK) INDICATE WHAT A "WET WALL" IS.
 - BASE SCHEDULE (WB-2) INDICATE HOW
 SEMI-GLOSS PAINT MEETS THE NONABSORBENT
 REQUIREMENT FOR MEN'S AND WOMEN'S TOILET
 ROOMS. SECTION 1210.2.
 24. ALL PLUMBING SHEETS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET, AND IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS, THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.2055
 25. SHT P0-01 REFERENCES FBC-2001.
 ADOPTED CODE IS FBC-2004. PLEASE DESIGN
 PER FBC-2004 AND CHANGE REFERENCE.
 26. SHT P0-01 PLUMBING FIXTURE SCHEDULE,
 SHOW ALL PIPE SIZES TO ALL WATER
 HEATERS. SECTION 106.1.1.
 27. SHT P0-01 DOMESTIC WATER FIXTURE
 UNIT LOAD CALCS. REFER TO FBC-2001.
 PLEASE CALCULATE PER ADOPTED CODE WHICH
 IS FBC-2004.
 28. SHT P0-01 PLUMBING GENERAL NOTES
 REFERENCES UPC-2000. SHOULD REFERENCE
 FBC-2004.
 29. SHT P0-01 PLUMBING GENERAL NOTES
 UNDER PIPING & MATERIALS: UNABLE TO READ
 3RD SECTION, LINE 5, WORDS SUPERIMPOSED
 ON TOP OF EACH OTHER. SECTION 106.1.1.
 30. SHT P2-00 RAIN/STORM TO TRASH ROOM?
 PLEASE CLARIFY. SECTION 106.1.1.
 31 SHT P2-00 SV8 IS NOT CONNECTED TO THE
 BUILDING DRAIN. 106.1.1.
 32. SHT P2-00 CD-21 PIPED TO STORM?
 PLEASE CLARIFY. SECTION 106.1.1.
 33. SHT P2-00 SV2 IS NOT CONNECT TO THE
 BUILDING DRAIN. 106.1.1.
 34. SHT P2-00 CD-1 DESIGNATOR IS
 POINTING TO A SANITARY RISER. PLEASE
 CLARIFY. SECTION 106.1.1.
 35. SHT P2-00 RD-3 CONNECTING TO THE
 SANITARY SYSTEM. THIS IS NOT APPROVED
 PER CITY CODE SECTION 90-125(5).
 36. SHT P2-00 NO KEYED NOTE FOR #5
 FOUND. SECTION 106.1.1.
 37. SHT P2-00 RD-21, SV2, SV3, SV-4, P1.
 P2, P-3, CD-10 AND OTHER RISERS SHOWN ON
 SHT P2-01 BUT NOT SHOWN ON THIS SHEET.
 ALL RISERS START ON THE FIRST FLOOR AND
 ALL RISERS LOCATIONS SHALL BE SHOWN
 WHERE THEY START IN THE SYSTEM.
 38. EACH SANITARY RISER DIAGRAM, BE IT A
 CONVENTIONAL SYSTEM OR A SOVENT SYSTEM
 RISER SHALL HAVE ITS OWN RISER
 DESIGNATION, SUCH AS P-1, P-2. P3 OR
 SV-1, SV-2, SV-3 ETC. SHOWING MULTIPLE
 RISERS WITH THE SAME RISER DESIGNATION
 IS CONFUSING BECAUSE, (FOR EXAMPLE), NOT
 ALL P-1 RISERS ARE THE SAME AS THE
 PIPING IS NOT ALWAYS THE SAME AND THE
 OFFSETS ARE NOT ALL THE SAME FOR EACH
 P-1. SEE FOR EXAMPLE THE WATER RISERS,
 THE CONDENSATE RISERS, OR THE STORM
 RISERS. SECTION 106.1.1.
 39. ALL SHEETS SHOWING PIPING ON FLOOR
 PLANS: SHOW ALL PIPING INCLUDING ARMS TO
 LAVS OR KITCHEN SINKS. SECTION 106.1.1.
 40. ALL SHEETS RESEALED AND RESUBMITTED
 SHALL CONTAIN THE NEW TYPE SEAL REQUIRED
 AFTER DECEMBER 31 2005. SEE ATTACHED
 SHEET FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
 41. SHT P2-01 RISERS RD-6, RD-9, RD-12
 AND RD-13 HAVE BEEN OFFSET, BUT NO
 OFFSET PIPING IS SHOWN. PLEASE SHOW ALL
 OFFSET PIPING ON PLANS. SECTION 106.1.1.
 42. SHT P2-01 19 RISERS SHOWN ON THIS
 SHEET WERE NOT SHOWN ON SHEET P2-00.
 PLEASE CLARIFY. SECTION 106.1.1.
 43. SHT P2-01 RISER P-1 IS SHOWN AS
 RISER P-3 ON SHT P2-00. PLEASE CORRELATE
 RISERS FROM FLOOR LEVEL TO FLOOR LEVEL.
 SECTION 106.1.1.
 44. SHT P2-02 24 RISERS SHOWN ON THIS
 SHEET WERE NOT SHOWN ON SHT P2-01.
 PLEASE CORRELATE RISERS FROM FLOOR TO
 FLOOR. SECTION 106.1.1.
 45. SHT P2-02 RISER P-4 IS SHOWN AS
 RISER P-3 ON SHT P2-01. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 46. SHT P2-02 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SQUARE FOOOTAGE BEING
 DRAINED AT EACH PRIMARY DRAIN AND SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED IN CALCULATIONS AS WELL
 AS ANY AREAS FROM UPPER ROOFS ADDED TO
 THE DECK AREA.
 47. SHT P2-02 MANY AREA DRAINS ARE
 MISLABELED AS PLANTER DRAINS, MANY
 DRAINS ARE NOT LABELED, MANY LABELS SHOW
 NO DRAIN. PLEASE CLARIFY. SECTION
 106.1.1.
 48. SHT P2-02 RISER CV-18 HAS BEEN
 OFFSET FROM SHEET P2-01, BUT NO OFFSET
 PIPING IS SHOWN ON THE FLOOR PLAN.
 PLEASE CORRELATE PIPING FROM FLOOR TO
 FLOOR. SECTION 106.1.1.
 49. SHT P2-03 RISERS P-4 & CD-19 SHOWN
 ON THIS SHEET WERE NOT SHOWN ON SHEET
 P2-02. PLEASE CORRELATE RISERS FROM
 FLOOR TO FLOOR. SECTION 106.1.1.
 50. SHT P2-03 RISER SV-19 SHOWN AS SV-3
 ON SHEET P2-02. CORRELATE RISERS FROM
 FLOOR TO FLOOR. SECTION 106.1.1.
 51. SHT P2-03 RISER P-6 SHOWN AS P-5 ON
 SHT P2-02. CORRELATE RISERS FROM FLOOR
 TO FLOOR. SECTION 106.1.1.
 52. SHT P2-03 RISER SV-1 SHOWN AS SV-7
 ON SHT P2-02. PLEASE CORRELATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 53. SHT P2-03 RISER CD-19 IS SHOWN AS
 CD-14 ON SHT P2-02. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 54. SHT P2-03 RISER CD-4 SHOW AS CD-13
 ON SHT P2-02. PLEASE CORREATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 55. SHT P2-03 RISER CD-3 SHOWN AS CD-12
 ON SHT P2-02. PLEASE CORRELATE RISER
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 56. SHT P2-03 RISER CD-2 SHOWN AS CD-11
 ON SHT P2-02. PLEASE CORRELATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 57. SHT P2-03 RISER P-5 SHOWN AS P-6 ON
 SHT P2-02. PLEASE CORRELATE RISERS FROM
 FLOOR TO FLOOR. SECTION 106.1.1.
 58. SHT P2-03 RISER CV-13 SHOWN AS RISER
 CV-1 ON SHT P2-02. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 59. SHT P2-03 RISERS P-4, P-5, RD5,
 SV-11, AND SV-15. PLANS INDICATE THESE
 RISERS HAVE BEEN OFFSET. NO PIPING FOR
 OFFSETS HAS BEEN SHOWN ON THE FLOOR
 PLAN. PLEASE SHOW ALL OFFSET PIPING ON
 THE FLOOR PLANS. RISER DIAGRAMS SHALL
 REFLECT ALL OFFSETS. SECTION 106.1.1.
 60. SHT P2-04 RISER P-6 SHOWN AS RISER
 P-5 ON SHT PD2.03. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 61. SHT P2-04 RISERS P-9, (2 OF THEM),
 ARE NOT SHOWN ON SHT P2-03. PLEASE
 CORRELATE RISERS FROM FLOOR TO FLOOR.
 SECTION 106.1.1.
 62. SHT P2-04 RISER P-8 NOT SHOWN ON SHT
 P2-03. PLEASE CORRELATE RISERS FROM
 FLOOR TO FLOOR . SECTION 106.1.1.
 63. SHT P2-04 RISER P-? DOES NOT HAVE A
 RISER DESIGNATION NUMBER. PLEASE CLARIFY
 SECTION 106.1.1.
 64. SHT P2-04 RISERS SV-1, SV-7, SV-13,
 SV-14, & CD-2 HAVE BEEN OFFSET, BUT NO
 OFFSET PIPING IS SHOWN ON THE FLOOR
 PLAN. PLEASE SHOW ALL OFFSET PIPING ON
 THE FLOOR PLAN, AND RISER DIAGRAMS SHALL
 REFLECT THESE OFFSETS. SECTION 106.1.1.
 65. SHT P2-04 RISERS P-7, (TWO OF THEM),
 ARE NOT SHOWN ON SHT P2-03. PLEASE
 CORRELATE RISERS FROM FLOOR TO FLOOR.
 SECTION 106.1.1.
 66. SHT P2-04 RISER AND PIPING NOT SHOWN
 FOR BATHROOM GROUP IN UNIT P1. PLEASE
 SHOW RISER AND INDICATE RISER NUMBER,
 SHOW ALL PIPING. SECTION 106.1.1.
 67. SHT P2-05 RISER SV-1 SHOWN AS SV-3
 ON SHT P2-04. PLEASE CORRELEATE ALL
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 68. SHT P2-05 RISER SV-9 SHOWN AS SV-1
 ON SHT P2-04. PLEASE CORRELATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 69. SHT P2-05 RISER SV-1 SHOWN AS SV-20
 ON SHT P2-04. PLEASE CORRELATE RISERS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 70. SHT P2.05 RISER P-3 SHOWN AS P-4 ON
 SHT P2-04. PLEASE CORRELATE RISERS FROM
 FLOOR TO FLOOR. SECTION 106.1.1.
 71. SHT P2-05 RISER SV-4 IS SHOWN AS
 SV-1 ON SHT P2-04. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 72. SHT P2-05 RISER SV-2 IS SHOWN AS
 SV-7 ON SHT P2-04. PLEASE CORRELATE
 RISERS FROM FLOOR TO FLOOR. SECTION
 106.1.1.
 73. SHT P2-05 NO PIPING OR RISER SHOWN
 FOR BATHROOM FIXTURES IN UNIT P1. PLEASE
 SHOW PIPING AND RISER. INDICATE RISER
 NUMBER. SECTION 106.1.1.
 74. SHT P2-05 SHEET TITLE DOES NOT
 INCLUDE 15TH FLOOR AS INDICATED IN THE
 MIDDLE OF THE SHEET AT THE BOTTOM.
 PLEASE CORRELATE SHEET TITLE WITH
 INFORMATION SHOWN ON SHEET. SECTION
 106.1.1.
 75. SHT P2-06 OVERFLOW SCUPPERS DO NOT
 REFLECT THE OVERFLOW SCUPPERS ON THE
 ARCHITECTURAL ON SHT A1-17. PLEASE
 CORRELATE THE SCUPPER AMOUNT AND
 LOCATIONS FOR THE ARCHITECTURAL AND
 PLUMBING SHEETS. ENGINEER SHALL INDICATE
 REQUIRED NUMBER OF SCUPPERS PER THE
 CALCULATIONS REQUIRED FOR SECONDARY ROOF
 DRAINS OR SCUPPERS ACCORDING TO SECTIONS
 1101.7, 1107.3 AND TABLE 1106.7.
 76. SHT P2-06 THE VENTS THRU THE ROOF DO
 NOT REFLECT THE VENTS SHOWN ON SHT P2-05
 FOR LOCATION. PLEASE CORRELATE VENTS
 FROM FLOOR TO FLOOR. SECTION 106.1.1.
 77. SHT P3-00 PLUMBING KEYED NOTES:
 NUMBER 9 REFERENCES SHT P0-04. THIS
 SHEET HAS NOT BEEN SUMBITTED. PLEASE
 CLARIFY. SECTION 106.1.1.
 78. SHT P3-00 DETAIL #4 REFERENCES UNIT
 B2B. THIS IS NOT SHOWN IN THE SHEET
 TITLE. PLEASE CORRELATE SHEET TITLE WITH
 INFORMATION ON DETAILS. SECTION 106.1.1.
 79. SHT P3-01 PLUMBING KEYED NOTES:
 NUMBER 9 REFERENCES SHT P0-04. THIS
 SHEET HAS NOT BEEN SUBMITTED. PLEASE
 CLARIFY. SECTION 106.1.1.
 80. SHT P3-01 DETAIL #4 PLEASE INDICATE
 THE KEYED NOTES NUMBERS FOR WATER DROPS
 AT THE TUB/SHOWER, LAV/WATER CLOSET
 PIPING. SECTION 106.1.1.
 81. SHT P3-02 PLUMBING KEYED NOTES:
 NUMBER 9 REFERENCES SHT P0-04. THIS
 SHEET HAS NOT BEEN SUBMITTED. PLEASE
 CLARIFY. SECTION 106.1.1.
 82. SHT P3-02 DETAIL #1 NO WATER RISER,
 (#8), IS SHOWN. PLEASE CLARIFY. SECTION
 106.1.1.
 83. SHT P3-02 DETAIL #2 HOT & COLD DROPS
 TO THE SHOWER HAVE BEEN MISLABLED.
 SECTION 106.1.1.
 84. SHT P3-03 PLUMBING KEYED NOTES:
 NUMBER 9 REFERENCES SHT P0-04. THIS
 SHEET HAS NOT BEEN SUBMITTED. PLEASE
 CLARIFY. SECTION 106.1.1.
 85. SHT P3-03 DETAIL #2 BOTH THE DROPS
 TO THE WATER HEATER AND TO THE TUB HAVE
 BEEN MISLABELED. PLEASE CLARIFY. SECTION
 106.1.1.
 86. SHT P4-00 ALL SV RISERS DO NOT
 REFLECT THE FLOOR PLANS FOR THE FIRST
 FLOOR PIPING. SECTION 106.1.1.
 87. SHT P4-00 ALL SV RISERS DO NOT
 REFLECT THE FLOOR PLANS FOR THE 16TH
 FLOORS. NO VENT PIPING SHOWN FOR THE
 REVENTS SHOWN ON THE 16TH FLOOR. SECTION
 106.1.1.
 88. SHT P4-00 SV-4 DOES NOT REFLECT THE
 FLOOR PLANS 2ND THRU 15TH FLOORS. THIS
 RISEER IS NOT SHOWN ON THE FIRST FLOOR.
 PLEASE CLARIFY. SECTION 106.1.1.
 89. SHT P4-00 16TH FLOOR SHALL BE
 DIFFERENT FROM OTHE FLOOR ON ALL RISERS
 AS THE VENTING/REVENTING IS ONLY ON THIS
 FLOOR. SHOW ALL VENTING/REVENTING ON
 RISERS. (THIS IS REQUIRED FOR ALL VENTS
 INCLUDING SOVENT SYSTEM IF VENTS FROM
 OTHER STACKS ARE TYING INTO THEM.
 SECTION 106.1.1.
 90. SHT P4-00 SV-5 DOES NOT REFLECT THE
 FLOOR PLANS FROM THE 2ND FLOOR THRU THE
 15TH FLOOR. OFFSET ON THE 11TH FLOOR IS
 NOT SHOWN ON THE 11TH FLOOR FLOOR PLAN.
 SECTION 106.1.1.
 91. SHT P4-00 SV-6 DOES NOT REFLECT THE
 FLOOR PLAN ON THE 11TH FLOOR. SECTION
 106.1.1.
 92. SHT P4-00 SV-7 DOES NOT REFLECT THE
 FLOOR PLAN ON THE 2ND FLOOR THRU THE
 11TH FLOOR. SECTION 106.1.1.
 93. SHT P4-00 SUBMIT A RISER DIAGRAM FOR
 EACH SANTITARY RISER DIAGRAM AND EACH
 SOVENT RISER DIAGRAM. COMMON RISERS WITH
 DIFFERENT FLOOR PLANS ARE NOT
 ACCEPTABLE. IF THE TUB AND LAV ARE ON
 THE OPPOSITE SIDE OF THE WATER CLOSET
 FROM ONE FLOOR PLAN TO THE OTHER, OR
 OFFSETS ARE DIFFERENT, OR ON DIFFERENT
 FLOOR PLANS, THEN SEPARATE RISER
 DIAGRAMS ARE REQUIRED. RISER DIAGRAMS
 SHALL REFLECT THE FLOOR PLAN FROM THEIR
 CONNECTION TO THE BUILDING DRAIN UP THRU
 THE ROOF FOR VENTING. BECAUSE THIS IS AN
 ENGINEERED SYSTEM, SEPARATE RISERS ARE
 REQUIRED, AND SEPARATE RISER
 DESIGNATIONS ARE REQUIRED. SOME RISERS
 CHANGE RISER NUMBERS FROM FLOOR TO FLOOR
 PLEASE CLARIFY. FLOOR PLANS SHOW REVENTS
 FROM OTHER RISERS TYING TOGETHER PRIOR
 TO VENTING THRU THE ROOF. THIS IS NOT
 REFLECTED ON ANY OF THE RISER DIAGRAMS.
 94. SUBMIT AN APPROVED DESIGN MANUAL FOR
 THE SOVENT SYSTEM. SUBMIT MANUFACTURE
 SPECIFICATIONS FOR AERATORS AND
 DEAERATORS FOR PRODUCT APPROVAL PER
 SECTIONS 303.1 & 303.4.
 95. PLANS APPEAR TO BE INCOMPLETE AT
 THIS TIME, AS ALL THE SV RISERS ARE NOT
 SUBMITTED AS WELL AS THE BLDG DRAIN FOR
 OTHER SYSTEMS. OTHER COMMENTS MAY OR MAY
 NOT FOLLOW UPON SUBMITTAL OF REQUIRED
 INFORMATION AND INFORMATION NOT
 SUBMITTED AT THIS TIME. SECTIONS 106.1.1
 AND 106.3.5.1.3.
 96. SHT P4-01 ALL STACKS, RELIEF VENTS
 ARE REQUIRED PER SECTION 914.1 AND SHALL
 BE PROVIDED AT EACH 10TH INTERVAL
 BEGINNING WITH THE TOP FLOOR. SECTION
 914.1.
 97. SHT P4-01 ALL STACKS, EVERY VENT
 STACK SHALL CONNECT TO THE BASE OF THE
 DRAINAGE STACK. PLEASE SHOW VENT STACK
 CONNECTION TO STACK. SECTION 903.4.
 98. SHT P4-01 ALL STACKS, NO 11TH FLOOR
 FIXTURES SHOWN ON THE RISER DIAGRAMS.
 CLARIFY. SECTION 106.1.1
 99. SHT P4-01 ALL STACKS, DRAINAGE STACK
 CAN NOT TERMINATE ABOVE THE 10TH FLOOR
 AND THEN START UP AGAIN BELOW THE 12TH
 FLOOR AS SHOWN ON THE RISER DIAGRAM.
 SECTION 106.1.1.
 100. SHT P4-02 RISERS W1, W2, W6, W8, &
 W10 FULL OPEN VALVES SHALL BE INSTALLED
 ON THE BASE OF EVERY WATER RISER PIPE.
 SECTION 606.1(3).
 101. SHT P4-04 SUBMIT THE BUILDING STORM
 DRAIN IN AN ISOMETRIC RISER DIAGRAM THAT
 REFLECTS THE PIPING SHOWN ON THE
 UNDERGROUND PLUMBING PLAN SHT P2-00.
 SECTION 106.3.5.1.3. SHOW ALL PIPE SIZES
 AND SQUARE FOOTAGE AS IT ACCUMULATES IN
 THE SYSTEM. IDENTIFY ALL RISERS AS THEY
 CONNECT TO THE BUILDING DRAIN IN THE
 ISOMETRIC DIAGRAM OF THE BUILDING DRAIN.
 SHOW ALL OFFSETS IN THE STORM RISERS,
 AND INDICATE ALL PIPE SIZES.
 102. SHTS P4-05 & P4-06 INDICATE
 MATERIAL FOR CONDENSATE SYSTEM. NO
 FLAMABLE MATERIAL IN THE AIR CONDITION
 ROOM IF IT IS USED AS A PLENUM. INDICATE
 METHOD OF VENTING THE CONDENSATE RISERS.
 VENTS CAN NOT TERMINATE IN THE WALLS OR
 IN A PLENUM.
 103. SHTS P4-05 & P4-06 SUBMIT A
 BUILDING DRAIN CONDENSATE ISOMETRIC
 RISER DIAGRAM THAT REFLECTS THE
 UNDERGROUND PIPING ON SHT P2-00. SECTION
 106.3.5.1.3.
 104. SHT P5-00 DETAIL 05 WASHER BOX
 CONNECTION WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASHER BOX PER 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING. PKI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 105. SHT P5-00 DETAIL 04 WATER HEATER
 CONNECTION DETAIL: A FULL OPEN VALVE IS
 REQUIRED ON THE SUPPLY PIPE TO EVERY
 WATER HEATER. SECTION 606.1(7).
 106. SHT P5-00 DETAIL 04 WATER HEATER:
 SUBMIT P&T RELIEF VALVE DISCHARGE PIPING
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 AND TERMINATION POINT. SECTION
 106.3.5.1.3. THE RELIEF VALVE DISCHARGE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVEA VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. INDICATE MATERIAL FOR P/T
 DISCHARGE PIPING.
 107. SHT P5-00 DETAIL 04 WATER HEATER
 SUBMIT EMERGENCY PAN DRAIN ISOMETRIC
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 MATERIAL, AND TERMINATION POINT. SECTION
 106.3.5.1.3.
 108. SHT P5-00 DETAIL 04 WATER HEATER:
 THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.13.2. PLEASE INDICATE
 METHOD FOR COMPLIANCE.
 109. SHT P5-00 DETAIL 07 DOMESTIC WATER
 BOOSTER PUMP DETAIL: SUBMIT MANUF.
 SPECIFICATION SHEETS FOR PUMP. PUMP
 SHALL BE LISTED. SECTION 303.4.
 110. SHT P6-00 SHOWS TWO RISER NUMBER 1
 AND TWO RISER NUMBER 11, AND NO RISERS
 NUMBER 9 & 12. PLEASE CLARIFY. SECTION
 106.1.1.
 111. SHT P6-01 NO RISER NUMBER 2. PLEASE
 CLARIFY. SECTION 106.1.1.
 112. SHT P6-03 RISER NUMBER 20
 MISLABELED AS RISER 19. PLEASE CORRELATE
 RISERS. SECTION 106.1.1.
 113. ALL SETS OF PLANS AND ALL SHEETS IN
 EACH SET OF PLANS: IF THE DESIGN
 PROFESSIONAL IS AN ENGINEER, THEN HE OR
 SHE SHALL AFFIX HIS OR HER OFFICIAL
 SEAL, SIGNATURE AND DATE TO SAID
 DRAWINGS AS REQUIRED BY FLORIDA
 STATUTES. NO INITIALS. LEAGAL
 SIGNATURE REQUIRED.
 114. SUBMIT WATER ISOMETRIC RISER
 DIAGRAMS FOR EACH UNIT SHOWING ALL PIPE
 SIZES, VALVES, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9.
 SECTION 106.3.5.1.3.
 115. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS APPLICATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2004
 FUEL GAS.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF
 2 PSI INDICATE LOCATION OF REGULATORS
 AND SUBMIT MANUF. SPECIFICATION SHEETS
 FOR REGULATORS INDICATING MODEL. IF
 VENTED REGULATORS, INDICATE MATERIAL FOR
 VENTS AND SHOW ROUTING OF PIPING.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RESUBMIT RED LINED SET OF
 PLUMBING PLANS FROM FIRST REVIEW TO HELP
 TO EXPEDITE THE SECOND REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]