| 2006-02-13 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE |
| | |
| | 1.PLAN SHEET A6-70 DETAIL 5 & 8 |
| | MECHANICAL EQUIPMENT RACK DETAIL, |
| | DETAILS DO NOT INDICATE THE ATTACHMENT |
| | TO THE STRUCTURE.PLEASE SHOW |
| | COMPLIANCE WITH 2001 FMC 301.13 & |
| | CHAPTER 16 OF THE 2001 FBC. |
| | |
| | 2.PLAN SHEET A8-10 RESIDENTIAL DOOR |
| | SCHEDULE, THE MECHANICAL CLOSET |
| | REFERENCES NOTE #9 WHICH STATES THE |
| | INTERIOR OF THE CLOSET DOOR & FRAME WILL |
| | BE PAINTED WITH INTUMESCENT PAINT.IS |
| | THE INTENT OF THE PAINT TO CLASSIFY THE |
| | DOOR AS "NON-COMBUSTIBLE"?WILL THE |
| | DOOR BE NON-COMBUSTIBLE WITHOUT THE |
| | PAINT? |
| | |
| | 3.PLAN SHEET M2-00 THE OUTSIDE AIR TO |
| | THE MAIN ELECTRICAL ROOM IS SUPPLIED |
| | FROM THE GARAGE & LOADING AREA?PLEASE |
| | CLARIFY.PLAN SHEET A9-01 INDICATES A 1 |
| | HR SEPARATION.PER 2001 FMC 401.5.1, |
| | INTAKE OPENINGS SHALL BE LOCATED A |
| | MINIMUM OF 10 FT FROM HAZARDOUS OR |
| | NOXIOUS CONTAMINANT SUCH AS PARKING LOTS |
| | AND LOADING DOCKS. |
| | |
| | 4.PLAN SHEET M2-00 INDICATES A 32" X |
| | 12" LOUVER BETWEEN THE PUMP ROOM & THE |
| | DOMESTIC PUMP ROOM. PLAN SHEET A9-01 |
| | INDICATES A 1 HR SEPARATION BETWEEN |
| | THESE ROOMS.PLEASE CLARIFY.THIS ALSO |
| | EFFECTS THE EXHAUST FROM THE PUMP ROOM & |
| | THE MAIN ELECTRICAL ROOM. |
| | |
| | 5.PLAN SHEET M2-00 EXHAUST DUCT FROM |
| | MENS ROOM PENETRATES 1 HR SEPARATION TO |
| | THE FIRE COMMAND ROOM.SHOW COMPLIANCE |
| | WITH 2001 FMC 607.1.3 (3) ITEMS 1 |
| | THROUGH 4. |
| | |
| | 6.PLAN SHEET M2-01 AHU & CONDENSOR |
| | LOCATED IN THE GARAGE.PLEASE PROVIDE |
| | MANUFACTURERS SUBMITTAL/INSTALLATION |
| | DATA, FOR INSTALLATION OF THE CONDENSER |
| | LOCATED INDOORS. |
| | |
| | 7.PLAN SHEET M3-00 THROUGH M3-02, PER |
| | 2001 FMC 601.4 RETURN AIR REQUIRED FROM |
| | ROOMS SEPARATED FROM THE CENTRAL RETURN |
| | BY DOORS.TRANSFER GRILLES OR JUMPERS |
| | SHALL BE SIZED IN ACCORDANCE WITH 2001 |
| | FMC 601.4 EXCEPTION 1 THROUGH 3. |
| | |
| | 8.PLEASE INDICATE MATERIAL OF DRYER |
| | DUCT.SHOW COMPLIANCE WITH 2001 FMC |
| | 504.2. & 504.4. |
| | |
| | 9.PLAN SHEET M3-00 THROUGH M3-02, |
| | DRYER EXHAUST APPEARS TO EXCEED THE |
| | MANUFACTURERS REQUIREMENTS WITH THE |
| | OFFSETS.PLEASE CLARIFY. |
| | |
| | 10.PLEASE PROVIDE MANUFACTURER |
| | SUBMITTAL DATA FOR THE RESIDENTIAL A/C |
| | EQUIPMENT.PLEASE VERIFY MAXIMUM LENGTH |
| | OF REFRIGERANT LINES.INDICATE SIZING. |
| | |
| | 11.REFRIGERANT LINES SHALL BE IN A |
| | VENTED SHAFT IN ACCORDANCE WITH ASHRAE |
| | 15-92. |
| | |
| | 12. PLAN SHEET M4-00 REFERENCES 2001 FBC |
| | 412.5 FOR THE SMOKE CONTROL.PLEASE |
| | INDICATE WHICH METHOD WILL BE USED. |
| | 412.5 HAS 3 PRESCRIPTIVE METHODS AND ONE |
| | ENGINEERED METHOD THAT IS REQUIRED TO |
| | DEMONSTRATE THE MITIGATION OR REMOVAL OF |
| | SMOKE.PLEASE CLARIFY. |
| | |
| | 13. PLAN SHEET M5-00 APARTMENT DRYER |
| | DATA UNIT A3 IS INDICATED AS REQUIRING A |
| | BOOSTER FAN OR ARCHITECTURAL REDESIGN. |
| | PLEASE NOTE, BOOSTER FANS MUST BE |
| | SUBMITTED UNDER 103.7.1, ALTERNATE |
| | MATERIALS & METHODS.PLEASE PROVIDE ALL |
| | PERTINANT INFORMATION.PROVIDE LETTER |
| | FROM AN ENGINEER EMPLOYED BY THE |
| | MANUFACTURER STATING THE INSTALLATION OF |
| | A DRYER BOOSTER FAN WILL NOT VOID THE |
| | WARRANTY OF THE DRYER. |
| | |
| | 14. ALL LIFE SAFETY ITEMS AS WELL AS THE |
| | GARAGE VENTILATION FANS AND CO SENSORS |
| | SHALL HAVE THE CAPABILITY TO OPERATE |
| | UNDER EMERGENCY POWER. |
| | |
| | 15. PLAN SHEET M5-01 DETAIL 11 INDICATES |
| | DUCT SMOKE DETECTOR IN THE RETURN AIR |
| | PLENUM.PER 2001 FMC 606.2.1, SMOKE |
| | DETECTORS SHALL BE INSTALLED IN THE |
| | SUPPLY AIR DUCT. |
| | |
| | 16. PLEASE CLARIFY CONDENSATE, PLAN |
| | SHEET P4-05 & P4-06 DOES NOT INDICATE |
| | WHERE THE CONDENSATE TERMINATES (STORM |
| | DRAIN OR SANITARY).PLEASE CLARIFY. PER |
| | CITY CODE SEC.90-125 PROHIBITIONS & |
| | LIMITATIONS OF DISCHARGE (5), CONDENSATE |
| | SHALL NOT DISCHARGE INTO SANITARY. |
| | CONDENSATE SHALL TERMINATEINTO THE |
| | STORM DRAIN SYSTEM.PLEASE NOTE, |
| | CONDENSATE PIPING IN THE AHU CLOSET |
| | SHALL BE N0N-COMBUSTIBLE (NO PVC) PER |
| | 2001 FMC 602.2.1. |
| | |
| | 17. TRASH CHUTE SHALL BE SPRINKLERED IN |
| | ACCORDANCE WITH 2001 FBC 705.2.4.6. |
| | |
| | 18. PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH TABLE |
| | 403.3 FOR ALL AREAS (I.E. RESIDENCE & |
| | COMMON AREAS). |
| | |