Plan Review Notes
Plan Review Notes For Permit 05110247
Permit Number 05110247
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-13 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 1.PLAN SHEET A6-70 DETAIL 5 & 8
 MECHANICAL EQUIPMENT RACK DETAIL,
 DETAILS DO NOT INDICATE THE ATTACHMENT
 TO THE STRUCTURE.PLEASE SHOW
 COMPLIANCE WITH 2001 FMC 301.13 &
 CHAPTER 16 OF THE 2001 FBC.
  
 2.PLAN SHEET A8-10 RESIDENTIAL DOOR
 SCHEDULE, THE MECHANICAL CLOSET
 REFERENCES NOTE #9 WHICH STATES THE
 INTERIOR OF THE CLOSET DOOR & FRAME WILL
 BE PAINTED WITH INTUMESCENT PAINT.IS
 THE INTENT OF THE PAINT TO CLASSIFY THE
 DOOR AS "NON-COMBUSTIBLE"?WILL THE
 DOOR BE NON-COMBUSTIBLE WITHOUT THE
 PAINT?
  
 3.PLAN SHEET M2-00 THE OUTSIDE AIR TO
 THE MAIN ELECTRICAL ROOM IS SUPPLIED
 FROM THE GARAGE & LOADING AREA?PLEASE
 CLARIFY.PLAN SHEET A9-01 INDICATES A 1
 HR SEPARATION.PER 2001 FMC 401.5.1,
 INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM HAZARDOUS OR
 NOXIOUS CONTAMINANT SUCH AS PARKING LOTS
 AND LOADING DOCKS.
  
 4.PLAN SHEET M2-00 INDICATES A 32" X
 12" LOUVER BETWEEN THE PUMP ROOM & THE
 DOMESTIC PUMP ROOM. PLAN SHEET A9-01
 INDICATES A 1 HR SEPARATION BETWEEN
 THESE ROOMS.PLEASE CLARIFY.THIS ALSO
 EFFECTS THE EXHAUST FROM THE PUMP ROOM &
 THE MAIN ELECTRICAL ROOM.
  
 5.PLAN SHEET M2-00 EXHAUST DUCT FROM
 MENS ROOM PENETRATES 1 HR SEPARATION TO
 THE FIRE COMMAND ROOM.SHOW COMPLIANCE
 WITH 2001 FMC 607.1.3 (3) ITEMS 1
 THROUGH 4.
  
 6.PLAN SHEET M2-01 AHU & CONDENSOR
 LOCATED IN THE GARAGE.PLEASE PROVIDE
 MANUFACTURERS SUBMITTAL/INSTALLATION
 DATA, FOR INSTALLATION OF THE CONDENSER
 LOCATED INDOORS.
  
 7.PLAN SHEET M3-00 THROUGH M3-02, PER
 2001 FMC 601.4 RETURN AIR REQUIRED FROM
 ROOMS SEPARATED FROM THE CENTRAL RETURN
 BY DOORS.TRANSFER GRILLES OR JUMPERS
 SHALL BE SIZED IN ACCORDANCE WITH 2001
 FMC 601.4 EXCEPTION 1 THROUGH 3.
  
 8.PLEASE INDICATE MATERIAL OF DRYER
 DUCT.SHOW COMPLIANCE WITH 2001 FMC
 504.2. & 504.4.
  
 9.PLAN SHEET M3-00 THROUGH M3-02,
 DRYER EXHAUST APPEARS TO EXCEED THE
 MANUFACTURERS REQUIREMENTS WITH THE
 OFFSETS.PLEASE CLARIFY.
  
 10.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE RESIDENTIAL A/C
 EQUIPMENT.PLEASE VERIFY MAXIMUM LENGTH
 OF REFRIGERANT LINES.INDICATE SIZING.
  
 11.REFRIGERANT LINES SHALL BE IN A
 VENTED SHAFT IN ACCORDANCE WITH ASHRAE
 15-92.
  
 12. PLAN SHEET M4-00 REFERENCES 2001 FBC
 412.5 FOR THE SMOKE CONTROL.PLEASE
 INDICATE WHICH METHOD WILL BE USED.
 412.5 HAS 3 PRESCRIPTIVE METHODS AND ONE
 ENGINEERED METHOD THAT IS REQUIRED TO
 DEMONSTRATE THE MITIGATION OR REMOVAL OF
 SMOKE.PLEASE CLARIFY.
  
 13. PLAN SHEET M5-00 APARTMENT DRYER
 DATA UNIT A3 IS INDICATED AS REQUIRING A
 BOOSTER FAN OR ARCHITECTURAL REDESIGN.
 PLEASE NOTE, BOOSTER FANS MUST BE
 SUBMITTED UNDER 103.7.1, ALTERNATE
 MATERIALS & METHODS.PLEASE PROVIDE ALL
 PERTINANT INFORMATION.PROVIDE LETTER
 FROM AN ENGINEER EMPLOYED BY THE
 MANUFACTURER STATING THE INSTALLATION OF
 A DRYER BOOSTER FAN WILL NOT VOID THE
 WARRANTY OF THE DRYER.
  
 14. ALL LIFE SAFETY ITEMS AS WELL AS THE
 GARAGE VENTILATION FANS AND CO SENSORS
 SHALL HAVE THE CAPABILITY TO OPERATE
 UNDER EMERGENCY POWER.
  
 15. PLAN SHEET M5-01 DETAIL 11 INDICATES
 DUCT SMOKE DETECTOR IN THE RETURN AIR
 PLENUM.PER 2001 FMC 606.2.1, SMOKE
 DETECTORS SHALL BE INSTALLED IN THE
 SUPPLY AIR DUCT.
  
 16. PLEASE CLARIFY CONDENSATE, PLAN
 SHEET P4-05 & P4-06 DOES NOT INDICATE
 WHERE THE CONDENSATE TERMINATES (STORM
 DRAIN OR SANITARY).PLEASE CLARIFY. PER
 CITY CODE SEC.90-125 PROHIBITIONS &
 LIMITATIONS OF DISCHARGE (5), CONDENSATE
 SHALL NOT DISCHARGE INTO SANITARY.
 CONDENSATE SHALL TERMINATEINTO THE
 STORM DRAIN SYSTEM.PLEASE NOTE,
 CONDENSATE PIPING IN THE AHU CLOSET
 SHALL BE N0N-COMBUSTIBLE (NO PVC) PER
 2001 FMC 602.2.1.
  
 17. TRASH CHUTE SHALL BE SPRINKLERED IN
 ACCORDANCE WITH 2001 FBC 705.2.4.6.
  
 18. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH TABLE
 403.3 FOR ALL AREAS (I.E. RESIDENCE &
 COMMON AREAS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.