Plan Review Notes
Plan Review Notes For Permit 05110247
Permit Number 05110247
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-03-01 00:00:00******DENIED******
  
 1) FIRE HYDRANTS SHALL BE FULLY
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 2) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 3) PARKING GARAGE SHALL COMPLY WITH
 APPLICABLE BUILDING CODES, AND NFPA 88A.
  
  
 4) KNOX BOXES ARE REQUIRED TO BE
 INSTALLED WITH APPROPRIATE KEYS PRIOR TO
 FINAL INSPECTION.
  
 5) ARE STAIRWELLS NUMBERED CORRECTLY ON
 CD SHTS?
  
 6) NFPA 101, AND NFPA 1, 2003 EDITIONS
 SHALL BE REFERENCED AFTER JAN. 1, 2005.
  
 7) ALL REQUIREMENTS FOR HIGHRISE
 BUILDINGS SHALL BE MET, AND BE IN
 COMPLIANCE WITH NFPA 101, CHAPTER 11.
  
 8) PLEASE INDICATE ON PLANS THAT ALL
 WALKING SURFACES SHOWN ON SHT CD-03 ARE
 SLIP RESISTANT.
  
 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 10) MAXIMUM TRAVEL DISTANCE SHALL NOT
 EXCEED 250' IN ACCORDANCE WITH NFPA 101,
 SECTION 30.2.6.4.
  
 11) NFPA 72, 2002 EDITION TO BE
 REFERENCED.
  
 12) NFPA 13, 2002 EDITION SHALL BE
 REFERENCED.
  
 13) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30' IN HEIGHT.
  
 14) AT LEAST (2) FIRE DEPARTMENT
 CONNECTIONS ARE REQUIRED ON HIGHRISE
 BUILDINGS. OK ON FIRE SPRINKLER SITE
 PLAN.
  
 15) LOCKING KNOX BOX CAPS REQUIRED ON
 ALL FIRE DEPARTMENT CONNECTIONS.
  
 16) DUCT SMOKE DETECTORS REQUIRED ON
 SUPPLY SIDE OF AIR SYSTEM WITH
 CAPABILITY GREATER THAN 2000 CFM.
  
 17) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 18) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 19) UL CERTIFICATION SHALL BE PROVIDED
 PRIOR TO OR AT THE TIME OF FIRE ALARM
 FINAL INSPECTION.
  
 20) ACCESS ROADS SHALL BE A MINIMUM OF
 20' IN UNOBSTRUCTED WIDTH IN ACCORDANCE
 WITH NFPA 1, CHAPTER 18.
  
 21) AN ADDRESS IS REQUIRED ON BUILDING
 AND SHALL BE A MINIMUM OF 3" IN HEIGHT
 AND CONTRASTING WITH TO THE BACKGROUND.
  
 22) FIRE EXTINGUISHER CABINET ONLY SHOWN
 (1) LOCATION ON FL #1. PLEASE SHOW ALL
 LOCATIONS IN BUILDING.
  
 23) PLEASE INDICATE WHICH AELEVATORS ARE
 SRTETCHER ACCESSIBLE.
  
 24) TACTILE SIGNAGE IS REQUIRED AT
 STAIRWELLS, INDICATING FLOOR NUMBER,
 TOP, BOTTOM AND ROOF ACCESS.
  
 25) NO STORAGE ALLOWED IN ELECTRICAL,
 MECHANICAL OR FIRE COOMAND ROOMS.
  
 26) NO COMBUSTIBLE STORAGE ABOVE
 CEILINGS IF USED AS RETURN AIR PLENUM.
  
 27) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILINGS,
 CLASS A,B OR C.
  
 28) HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF STAIRS.
  
 29) STAIRS TO COMPLY WITH APPLICABLE
 BUILDING CODES, AND NFPA 101, CHAPTER 7.
  
  
 30) EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 31) ALL SHAFTS LARGE ENOUGH FOR PERSONS
 TO FALL INTO MUST BE MARKED SHAFTWAY
 WITH 6" HIGH LETTERS.
  
 32) THE ANTICIPATED STACK EFFECT NOTE
 WORDING SHALL BE ADDED TO THE MECHANICAL
 PLANS.
  
 33) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF THE BUREAU OF
 FIRE PREVENTION AND COMPLIANCE WITH NFPA
 51B.
  
 34) ELEVATORS TO COMPLY WITH ASME/ANSI
 17.1.
  
 35) ELEVATOR LOBBIES SHALL HAVE WARNING
 SIGNS.
  
 36) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR CO DETECTORS IN PARKING
 GARAGE.
  
 37) SMOKE DETECTORS SHALL BE LOCATED AT
 LEAST 3' FROM HVAC DIFFUSERS.
  
 38) MORE EXIT SIGNS APPEAR TO BE NEEDED
 IN LOBBY AND SURROUNDING AREA.
  
 39) EXITS SIGNS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100' AND MAKE
 EXITING CLEAR AND OBVIOUS.
  
 40) EMERGENCY LIGHTING FACILITIES ARE
 REQUIRED IN ROOMS AND AREAS WHERE
 ARTIFICIAL LIGHTING IS NOT ADEQUATE.
  
 41) ARE EXIT LIGHTS AND EMERGENCY
 LIGHTING FACILITIES MISSING IN THE
 PARKING GARAGE?
  
 42) WHERE ARE THE EXIT SIGNS LOCATED AT
 STAIRS #1&2 LEADING PERSONS I REGARDS TO
 EXITING?
  
 43) SOME CORRIDOR SMOKE DETECTORS APPEAR
 TO BE MISSING FROM ALL SHTS. PLEASE SHOW
 ALL LOCATIONS.
  
 44) FIRE ALARM SYSTEM TO MEET
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
 45) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 46) FIRE ALARM AUDIBLE DEVICE IS MISSING
 IN UNIT B1C ON SHT E.7.01.
  
 47) STANDPIPES CONNECTIONS SHALL BE 2
 1/2" TO 1 1/2" REDUCER WITH CHAINS.
  
 48) IN ADDITION TO ELECTRONIC
 SUPERVISION, CHAIN AND LOCK IS REQUIRED
 ON DOUBLE CHECK DETECTOR ASSEMBLY.
  
 49) PLEASE PROVIDE FURTHER INFORMATION,
 AND MANUFACTURER SPEC SHEETS FOR FIRE
 PUMP.
  
 50) FIRE SPRINKLERS ARE SHOWN IN
 TRANSFORMER VAULT? IS THAT INTENDED OR
 WILL THEY BE ELLIMINATED?
  
 51) PLEASE SHOW LOCATION AND DETAILS FOR
 DOUBLE CHECK DETECTOR ASSEMBLY. NOT
 SHOWN ON FIRE PROTECTION SITE PLAN.
  
 52) DO THE DOOR SWING AT THE ELECTRICAL
 ROOM AND TRASH CHUTE OBSTRUCT THE
 CORRIDOR BY GREATER THAN 1/2 THE WIDTH?
  
 53) SMOKE EVACUATION IS MENTIONED.
 PLEASE PROVIDE FURTHER INFORMATION.
  
 54) SMOKE MANAGEMENT PANELS WHERE
 PROVIDED SHALL PROVIDE A GRAPHIC
 REPRESENTATION OF THE BUILDING. HOA
 SWITCHES WITH NO OVERLAY OF THE BUILDING
 WILL NOT BE ACCEPTABLE.
  
 55) ARE THERE ANY ADA SPEAKER/STROBE
 DEVICES PLANNED FOR ANY LIVING UNITS?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  