| 2006-01-27 00:00:00 | **** THE EDGE PHASE II ** 17 STORY ** |
| | |
| | ********** UNSAT *************** |
| | |
| | ** PLEASE KNOW, PLANS ARE NOT COMPLETE |
| | AND REVIEW BELOW IS BASED ON PLANS |
| | SUBMITTED. |
| | PLEASE ALSO KNOW, SINCE PLANS ARE NOT |
| | COMPLETE, THERE MAY OR MAY NOT BE |
| | FURTHER COMMENTS ON NEXT REVIEW. |
| | |
| | |
| | 1)NOTE: PLEASE SEE ADDRESSING NEEDS TO |
| | BE ADDRESSED AS PERMIT APPLICATION |
| | MENTIONS 350 S AUST, PCN USED ON |
| | APPLICATION IS FORRR 300 S AUST. |
| | PLEASE ALSO SEE PLANS INDICATE 300 S |
| | AUSTRALIAN AVE. |
| | PLEASE BE SUREADDRESS IS CORRECTED |
| | WITH THE ADDRESSING DEPT AND ADJUST |
| | PLANS IF NEEDED. |
| | |
| | 2)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION REQUIRED ON TITLE BLOCKS FOR CONSULTING |
| | ENGINEERING FIRM AS REQUIRED |
| | UNDER FLORIDA STATUES 471.023, FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002. |
| | PLEASE SEE COMPANIES AS LISTED ARE |
| | PROVIDING ENGINEERING SERVICES" AND NO |
| | CERTIFICATE OF AUTHORIZATION NUMBER |
| | COULD BE LOCATED ON STATE WEBSITE OF |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION. |
| | (DBPR). |
| | PLEASE KNOW AS REQUIRED BY THESAID |
| | FLORIDA STATUES AND LICENSINGUNDER FS |
| | 468 FOR THIS OFFICE, ONE SET OF MEP |
| | PLANS ARE BEING RETAINED AND SHALL BE |
| | FORWARDED TO THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS FOR REVIEW OF |
| | SAID REQUIREMENTS. WE HAVE CONSULTED |
| | WITH THEFBPE'S ON THE ABOVE. PLEASE |
| | CONTACT MR. JERRY ONGLEY AND MR. DOUGLAS |
| | SUNSHINE IF THERE ARE ANY QUESTIONS. |
| | ** PLEASE KNOW, THESE REQUIREMENTS ARE |
| | ALSOFOR THE OTHER CONSULTING COMPANIES |
| | AS LISTED ON SAID TITLE BLOCKS. |
| | |
| | 3)NOTE: PLEASE SEE SPECS SUBMITTED FOR |
| | FIRE PUMP CONTAIN THE TITLE AND THE |
| | RESPONSIBLE ENGINEER AS STEVEN FELLER OF |
| | FELLER ENGINEERING. STEVEN FELLER AND |
| | FELLER ENGINEERING IS THE CONSULTING |
| | ENGINEERS OF PHASE-ONE. |
| | PLEASE CORRECT ALL SUBMITTALS FOR FIRE |
| | PUMP, FIRE PUMP CONTROLLER ETC. |
| | |
| | 4)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | ALL CURRENT CODE IN EFFECT FOR THIS |
| | PROJECT. PLEASE KNOW WE ARE CURRENTLY |
| | UNDER THE 2003 NFPA-101, 2002 NFPA-72 |
| | AND 2002 NFPA-70 ETC. |
| | |
| | 5)NOTE: PLEASE KNOW, ENTRANCE TO MAIN |
| | ELECTRICAL ROOM SHALL BE DETERMINED BY |
| | THIS OFFICE AND FIRE MARSHAL'S OFFICE |
| | FOR ACCESSIBILITY. PLANS INDICATE ACCESS |
| | GRANTED THROUGH GARAGE AREA AND TRAVEL |
| | DISTANCE IN BLDG MAY REQUIRED A MORE |
| | ACCESSIBLE MEANS TO MAIN ELECTRICAL |
| | ROOM. |
| | ** PLEASE SEE POSSIBLE FIRE REVIEW |
| | COMMENTS. |
| | |
| | 6)NOTE: PLEASE SEE 110.26 FOR MIN |
| | DOOR(S) REQUIRED FOR MAIN ELECTRICAL |
| | ROOM. PLEASE SEE ONE MAIN/EQUIPMENT |
| | LOCATED DIRECTLY IN-FRONT OF THE EGRESS |
| | PATH/DOOR. |
| | PLEASE SEE PANIC HARDWARE SHALL BE |
| | REQUIRED AND DOORS MUST OPEN IN THE |
| | DIRECTION OF TRAVEL.PLEASE PROVIDE A |
| | NOTE ON PLANS FOR THIS. |
| | A NOTE ON E4.00 STATES "DOOR NEEDS TO BE RELOCATED" , |
| | HOWEVER THIS WAS NOT DONE |
| | AND IS SHOWN THE SAME IN A-SHEETS AND |
| | E-SHEETS. |
| | PLEASE ADD NOTE(S) TO PLANS FOR ALL |
| | CLEARANCES PER 110.26 SHALL BE MET. |
| | 4.00 ETC |
| | |
| | 7)NOTE: PLEASE VERIFY WHERE LIGHTING IS |
| | FOR ELECTRICAL RMS ON FLRS |
| | 2,5,6,7,10,16? |
| | 215.5, LS1017.8,7.9 ETC |
| | |
| | 8)NOTE: PLEASE SEENFPA-72 WHICH |
| | REQUIRES BATTERY BACK UP FIXTURES IN |
| | STAIR TOWERS AND OTHER AREAS WHERE EM |
| | LTS ARE REQUIRED FOR MIN EGRESS PATHS. |
| | PLEASE SEE 7.9.2.2 WHICH STATES NO |
| | SINGLE MEANS OF OVERCURRENT PROTECTION |
| | OR SWITCHING ETC SHALL LEAVE ANY EGRESS |
| | PATHS IN TOTAL DARKNESS AS SHOWN ON |
| | PLANS. |
| | PLEASE KNOW AS REQUIRED BY THE AHJ AND |
| | THE FIRE MARSHAL'S OFFICE A BATTERY |
| | BACK-UP FIXTURE OF SOME SORT WILL BE |
| | REQUIRED FOR THESE EGRESS PATHS TO |
| | ALLEVIATE THE ABOVE. |
| | |
| | 9)NOTE: PLEASE PROVIDE COMPLETE |
| | PHOTO-METRICS FOR FOR ALL STAIR-TOWERS |
| | AND EGRESS PATHS. PLEASE SEE LS 101 |
| | 7.8.1.3 WHICH REQUIRES A MIN OF |
| | 10FT/CANDLES (108 LUX) FOR STAIR TOWERS |
| | UNDER NORMAL CONDITIONS AND A MIN OF |
| | 1FT/CD UNDER EMERGENCY CONDITIONS. |
| | 7.9.2.2 |
| | |
| | 10)NOTE: PLEASE INDICATE BY SOME MEANS |
| | THE IDENTIFICATION OF ALL LIGHTING |
| | FIXTURES ON PLANS. PLEASE SEE LIGHTING |
| | IN STAIRS, TYPE OF FIXTURE COULD NOT BE |
| | FOUND AND CORRELATION TO THE SUBMITTED |
| | FIXTURE SCHEDULE COULD NOT BE DONE. |
| | |
| | 11)NOTE: PLEASE PROVIDE A NOTE ON ROOF |
| | PLANS: |
| | " ALL PROPOSED LIGHTNING PROTECTION |
| | SYSTEMS SHALL MEET NFPA-780" OR WORDS TO |
| | THAT AFFECT. |
| | ** PLEASE KNOW, THERE ARE MANY "LIGHTING PREVENTION |
| | SYSTEMS" ON THE MARKET WHICH |
| | ARE NOT ACCEPTABLE IN THIS JURISDICTION |
| | OR BY NFPA. |
| | |
| | 12)NOTE: PLEASE SUBMIT A LETTER FROM THE |
| | FLORIDA POWER AND LIGHT REPRESENTATIVE |
| | ON THE ACCEPTANCE OF FPL VAULT AS SHOWN. |
| | |
| | 13)NOTE: PLEASE COMPLETE PLANS WITH ALL |
| | CIRCUITINGAND CORRELATE WITH SUBMITTED |
| | PANEL SCHEDULES. REVIEW FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | PLEASE BE SURE TO SEE |
| | 210.52B1,210.52D,210.11C3 ETC. |
| | |
| | 14)NOTE: PLEASE SEE 424.3B WHICH |
| | REQUIRES OCP FOR AHU/HEAT TO BE SIZED AT |
| | A MIN OF 125%. PLEASE SEE SOME OCP AS |
| | INDICATED WILL NEED TO BE ADJUSTED.** |
| | PLEASE BE SURE TO ADJUST AND CONDUCTOR |
| | SIZES AS NEEDED. PER 310.16,240.4 ETC |
| | |
| | 15)NOTE: PLEASE SEE 210.52D,210.11C3 FOR |
| | BATH RECEPTS. PLEASE SEE SOME UNITS , |
| | B2, B1 ETC. |
| | |
| | 16)NOTE: PLEASE PLACE ALL AREA AND ROOM DESIGNATIONS ON |
| | PLANS. |
| | PLEASE SEE PREVIOUS COMMENTS WITH |
| | RESPECT TO COMPLIANCE WITH CIRCUITING. |
| | |
| | 17)NOTE: PLEASE INDICATE THE KITCHEN |
| | CIRCUITS AS SMALL APPLIANCE. |
| | 210.52B |
| | |
| | 18)NOTE: PLEASE SEE NFPA-72 11.8.3.5, |
| | 11.5.1.1 FOR SMOKE DETECTORS REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPINGRMS. |
| | PLEASE SEE UNIT D1, PLEASE ALSO SEE |
| | OTHER UNITS WHERE SD'S DO NOT APPEAR TO |
| | BE "OUTSIDE" SLEEPING AREAS OR |
| | CORRIDORS. PLEASE SEE A DOOR SEPARATES |
| | BEDRM HALLWAYS FROM LIVING/COMMON AREA |
| | OF UNIT. THIS SEEMS TO SHOW NO SD |
| | COVERAGE FOR AREAS OUTSIDE BEDROOMS. |
| | PLEASE FIRE REVIEW COMMENTS. |
| | ** PLEASE PLACE NOTE ON PLANS WITH |
| | REFERENCE TO THE MIN PLACEMENT |
| | REQUIREMENTS OF ABOVE NFPA. PLEASE SEE |
| | THAT SD'S ARE LOCATED A MIN OF 3' FROM BATH,KITCHEN |
| | DOORS , 3' FROM SUPPLY |
| | REGISTERS , ETC :WITH EXCEPTIONS AS |
| | LISTED FOR LOCATIONS WITHIN 20' OF |
| | COOKING APPLIANCES. |
| | ** PLEASE SEE SPECS/LISTING FROM SD |
| | MANUFACTURE AS MANY REQUIRED SD'S TO BE |
| | FURTHER THAN LISTED ABOVE AND MOST |
| | REQUIRED SD'S TO BE 5' FROM THE RETURN |
| | AIR GRILLE. |
| | ** PLEASE KNOW, ANY CEILING HEIGHT |
| | VARIATIONS MAY CHANGE LOCATION OF SD'S, |
| | AS THEY ARE REQUIRED TO BE LOCATED |
| | WITHIN 12" OF THE HIGHEST POINT OF A |
| | FLAT CEILING. |
| | |
| | 19)NOTE: PLEASE SHOW AND LABEL ALL |
| | PANELS, ELECTRICAL AND PANELS WHICH |
| | APPEAR TO BE LOW VOLTAGE? |
| | PLEASE KNOW, ANY PLUG-IN TYPE |
| | TRANSFORMERS MAY NOT BE LOCATED IN CLOSE |
| | PROXIMITY OF EASILY IGNITABLE MATERIALS |
| | IN CLOTHES CLOSETS. |
| | PLEASE KNOWIN MANY LOCAL JURISDICTIONS |
| | AS A RESULT OF THE HEATING OF THESE TYPE TRANSFORMER A |
| | FIRE HAS OCCURRED. IN THE |
| | INTEREST OF LIFE SAFETY AND PROPERTY |
| | PLEASE ADJUST LOCATIONS. |
| | 110.26,240.24D, 408.7 ETC. |
| | PLEASE ALSO SEE UNIT(S) WHICH INDICATE A |
| | PANEL OF SOME SORT "INSIDE " THE BATHTUB |
| | LOCATION. PLEASE SEE 240.24 FOR |
| | PERMITTEDLOCATIONS OF PANELS. |
| | PLEASE SEE REDLINED PLANS. |
| | PLEASE SEE UNIT "G" FOR WHAT APPEARS TO |
| | BE TWO PANELS? |
| | PLEASE SEE D2, PLEASE SEE A1, PANEL NOT |
| | LOCATED ON WALL, SEE P3, P2 MISSING |
| | PANEL. |
| | PLEASE VERIFY ALL OF THE ABOVE AS MANY |
| | OF THESE HAVE BEEN REDLINED ON ONE SET |
| | OF PLANS. |
| | |
| | 20)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS FOR 2',6'AND 12 RULE. PLEASE SEE |
| | SOME MISSING FOR 2' OF WALL SPACE. |
| | |
| | 21)NOTE: PLEASE SEE 210.52C2, 210.8A16 |
| | FOR WHAT APPEARS TO BE SHOWN AS AN |
| | ISLAND KITCHEN. B2 |
| | |
| | 22)NOTE: PLEASE SEE SEE UNIT UNIT A-2 |
| | LAYOUT OF WALLS AND DOORS.PLEASE SEE |
| | AREA WHERE THERE SEEMS TO BE A ROOM? |
| | |
| | 23)NOTE: PLEASE CORRELATE ELECTRICAL |
| | ROOMS AND RISER DIAGRAM. PLEASE SEE E4.0 |
| | SHOWS ELECTRICAL RM ON EVERY FLR, |
| | HOWEVER RISER DOES NOT. |
| | PLEASE SEE OTHER COMMENTS WITH RESPECT |
| | TO ELECTRICAL RMS. |
| | 215.5 |
| | |
| | 24)NOTE: PLEASE PROVIDE A CURB DETAIL |
| | FOR FLR PENETRATIONS OF BUS-DUCT PER |
| | 368.6 WHERE A VERTICAL RISER PENETRATES |
| | TWO OR MORE DRY FLOORS, A MINIMUM 100 MM |
| | (4 IN.) HIGH CURB SHALL BE INSTALLED |
| | AROUND ALL FLOOR OPENINGS FOR RISER |
| | BUSWAYS TO PREVENT LIQUIDS FROM ENTERING |
| | THE OPENING. THE CURB SHALL BE INSTALLED |
| | WITHIN 300 MM (12 IN.) OF THE FLOOR |
| | OPENING. ELECTRICAL EQUIPMENT SHALL BE |
| | LOCATED SO THAT IT WILL NOT BE DAMAGED |
| | BY LIQUIDS THAT ARE RETAINED BY THE |
| | CURB. |
| | |
| | 25)NOTE: PLEASE CORRELATE MAIN |
| | ELECTRICAL ROOM EQUIPMENT WITH RISER |
| | DIAGRAM. PLEASE SEE ONE SHOWS 3000A |
| | MAIN, THEOTHER 4000A, PLEASE SEE |
| | ELECTRICAL PANELSSHOWN ON 4.00 ALSO DO |
| | NOT CORRELATE WITH RISER. |
| | PLEASE SEE MANY OF THESE ITEMS/LOCATIONS |
| | WERE REDLINED ON ONE SET. |
| | |
| | 26)NOTE: PLEASE SEE METER CENTERS ON |
| | ELECTRICAL ROOMS SHOWN ON E4.00 DO NOT |
| | CORRESPOND TO THE METER CENTERS ON 5.02 |
| | 215.5 |
| | |
| | 27)NOTE: PLEASE SEE METER CENTER(S), |
| | PLEASE SEE THERE ARE MANY UNIT |
| | IDENTIFICATIONS WHICH DO NOT CORRELATE |
| | TO THE UNITS ON PLANS. |
| | PLEASE SEE UNITS TYPES ON RISER. |
| | 215.5 |
| | |
| | 28)NOTE: PLEASE SEE RISER WHICH |
| | INDICATES THE ELEVATOR'S ELECTRICAL |
| | EQUIPMENT LOCATED ON FIRST FLR, HOWEVER |
| | PLEASE SEE PLANS FOR ROOF AS ELEVATOR |
| | EQUIPMENT ROOM IS SHOWN AT THAT |
| | LOCATION. PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 29)NOTE: PLEASE PROVIDE OCP LOCATED AT |
| | GENERATOR WHICH IS PART OF THE PHASE 1 |
| | HIGH-RISE BLDG. |
| | PLEASE SEE EQUIPMENT SPECS INDICATE THE |
| | GEN AT 1000KW. |
| | 215.5 |
| | |
| | 30)NOTE: PLEASE PROVIDE A MEANS OF |
| | DISCONNECT FOR THE FEEDERS COMING FROM |
| | GEN.225.31-225.39 |
| | PLEASE SEE A MAIN CIRCUIT BRKR LOCATED |
| | IN EDPH2 WOULD BE ACCEPTABLE. |
| | SHALL ALSO REQUIRE SIGNAGE. |
| | 230.2E,700.8 ETC. |
| | |
| | 31)NOTE: PLEASE SEE PANEL "GH" AS SHOWN |
| | ON RISER WHICH IS SHOWN FROM ANOTHER |
| | BLDG AND ANOTHER SERVICE, MAY NOT BE |
| | LOCATED IN THIS BLDG.230.3 |
| | *****PLEASE KNOW AS CONDITION SET FORTH |
| | BY THE DESIGN TEAM ON PHASE ONE, A |
| | COMPLETE SEPARATION OF ALL ELECTRICAL |
| | SYSTEMS WILL TAKE PLACE AND A COMPLETE 4 |
| | HR SEPARATION WILL BE PROVIDED BETWEEN |
| | PARKING GARAGE AND PHASE II HIGH RISER |
| | BLDG. PLANS DO NOT SEEM TO CORRELATE |
| | WITH THIS. PLEASE KNOW, GARAGE IS NOW |
| | SHOWING ELECTRICAL DEVICES/SYSTEMS FED |
| | FROM TWO SEPARATE SERVICES WHICH WILL |
| | NOT BE PERMIT. A DEFINITIVE SEPARATION |
| | WILL BE PROVIDE AND CROSSING OVER OF |
| | SYSTEMS WILL NOT BE ACCEPTABLE. |
| | 230.2,230.3 ETC, 90.4 |
| | |
| | 32)NOTE: PLEASE PLACE NOT ON PLANS AS NO |
| | EQUIPMENT GROUNDING CONDUCTORS MAY BE |
| | ALUMINUM, AND NO FEEDERS SMALLER THAN |
| | #2. PER CITY OF WEST PALM BEACH LOCAL |
| | AMENDMENTS TO THE 2001 FBC.250.62,310.2 |
| | |
| | 33)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| | COLOR CODING OF 277/480V SYSTEMS PER |
| | LOCAL AMENDMENTS, 215.2 |
| | BROWN, PURPLE, YELLOW. |
| | ** PLEASE KNOW SPECIFIC COLOR CODING PER |
| | 277/480V IS NOT PROVIDED IN THE NEC AND |
| | ONLY A "HIGH-LEG" SHALL HAVE "ORANGE" AS |
| | THE COLOR. |
| | |
| | 34)NOTE: PLEASE PROVIDE A COMPLETE |
| | GROUNDING ELECTRODE RISER IN BLDG AND |
| | PROVIDE THIS LINE DIAGRAM ON ELECTRICAL |
| | RISER. THIS SHOULD INCLUDE ALL GROUNDING |
| | FOR TRANSFORMER(S)/SEPARATELY DERIVED SYSTEMS.250.58 |
| | |
| | 35)NOTE: PLEASE INDICATE THE ATTACHMENT |
| | FOR TRANSFORMERS AS SHOWN AS REQUIRED |
| | PER ABOVE NOTE #34 AND 250.30, 250.66 |
| | |
| | 36)NOTE: PLEASE SEE NO LOAD CALCULATIONS |
| | WERE SUBMITTED FOR MAINS, SERVICES, |
| | METER CENTERS ETC. MC1? |
| | PLEASE SEE SOME CONNECTED LOADS DO NOT |
| | INDICATE LOADS AND HOW THEY WERE |
| | DERIVED.? |
| | PLEASE KNOW VERIFICATION OF CODE |
| | COMPLIANCE FOR SERVICE SIZES, FEEDERS, |
| | SEC'S ETC CAN NOT BE VERIFIED OR |
| | REVIEWED AT THIS TIME. |
| | 310.16.240.4,220, 215.5 |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ARE |
| | SHOWN AND FIGURED AT 125%, |
| | 215.3,230.42 ETC. |
| | |
| | 37)NOTE: PLEASE VERIFY AND SUBMIT SPECS |
| | FO BUS-DUCT AS LOCAL AMENDMENT DOES NOT |
| | PERMIT ALUM AS THE EQUIPMENT GROUNDING |
| | METHOD. 250.62 SEE PREVIOUS NOTES. |
| | |
| | 38)NOTE: PLEASE SEE SPEC BOOKS SUBMITTED |
| | ARE FOR EQUIPMENT AND SPEC BOOK FOR |
| | JOB-SITE WAS NOT SUBMITTED AT THIS TIME. |
| | PLEASE SEE SOME OF THE ABOVE COMMENTS |
| | WHICH MAY AFFECT PAGES IN THE JOB-SITE |
| | SPEC BOOKS. THESE SHOULD BE REVIEWED AND |
| | MAKE ANY CHANGES AS NEEDED. |
| | |
| | 39)NOTE: PLEASE SEE 230.95,240.13 WHICH |
| | REQUIRES GROUND FAULT PROTECTION FOR |
| | SYSTEMS WITH A VOLTAGE MORE THEN 150V TO |
| | GRND AND OVER 1000A'S. |
| | PLEASE SEE "MSBH2. |
| | |
| | 40)NOTE: PLEASE VERIFY SIZING OF |
| | EMERGENCY DISTRIBUTION SYSTEM AS ONE |
| | SHEET SHOWS 800A ATS AND SPECS FOR ATS |
| | INDICATE THIS AS 1000A'S? |
| | PLEASE SEE NOTE BELOW AS PANEL |
| | SCHEDULES ALSO INDICATE 1000A'S. |
| | PLEASE KNOW, IF 1000A'S, GFP SENSING |
| | WILL BE REQUIRED ON SECONDARY SIDE,GFP |
| | WILL BE REQUIRED ON MAIN ALSO AS NOTED |
| | PER 240.13,230.95. |
| | PLEASE SEE 700.7D, 700.26, 701.9D |
| | PLEASE SEE TEXT TAKEN DIRECTLY FROM ASCO |
| | AS A 4-POLE ATS MAY BE REQUIRED FOR THE |
| | CORRECT COORDINATION OF ELECTRICAL |
| | SYSTEMS. |
| | "WHERE GROUND FAULTPROTECTION IS |
| | TRIGGERED BY THE CODE AND AN ALTERNATE |
| | POWER SUPPLY IS INCLUDED,SWITCHING OF |
| | THE NEUTRAL BECOMES NECESSARY. THE |
| | CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A CIRCUMSTANCE. |
| | THE SERVICE IS LARGER THAN |
| | 1,000 AMPS. CONSEQUENTLY, GROUNDFAULT |
| | PROTECTION IS REQUIRED AT THE MAIN |
| | SERVICE DISCONNECT AT A MINIMUM. IF IT |
| | IS INSTALLED THERE AND THE GENERATOR |
| | NEUTRAL GROUNDING WAS THROUGH A SOLID |
| | CONNECTION TO THE MAIN SERVICE NEUTRAL, |
| | A GROUND FAULT WHEN THE GENERATOR IS |
| | FEEDING THE LOAD WILL CAUSE THE MAIN |
| | SERVICE DISCONNECT TO OPEN. THIS WILL |
| | NOTDISCONNECT THE ARCING FAULT FROM |
| | THE GENERATOR. COORDINATION IS THUS |
| | LOST." |
| | PLEASE VERIFY AS SYSTEM IN EXISTING BLDG |
| | ONE MAY BE A SEPARATELY DERIVED |
| | GENERATOR AND SEEING HOW BOTH BLDGS EM |
| | POWER IS COMING FROM THE SAME GENERATOR, |
| | A 4-POLE SWITCH MAY BE REQUIRED. PLEASE |
| | ALSO KNOW, BOTH OF THESE MAIN |
| | DISTRIBUTION SYSTEMS ARE COMING FROM TWO |
| | SEPARATE FPL VAULTS AND TRANSFORMERS. |
| | |
| | 41)NOTE: PLEASE SEE MISSING FIRE PUMP |
| | AND EQUIPMENT NOT INDICATED ON RISER |
| | DIAGRAM. |
| | PLEASE SEE 695.4B1 FOR OCP REQUIRED FOR |
| | LOCKED ROTOR. PLEASE ALSO SEE NFPA-20 |
| | FOR ELECTRICAL REQUIREMENTS FOR MEANS-OF |
| | DISCONNECT, LOCATION ETC. PLEASE SEE |
| | SPECS SUBMITTED APPEAR TO SHOW THIS , |
| | HOWEVER NONE OF THESE ITEMS ARE SHOWN ON |
| | RISER. UNABLE TO VERIFY CODE COMPLIANCE |
| | FOR FIRE PUMP, FIRE PUMP CONTROLLER, |
| | FEEDERS, SEC'S ETC. |
| | ** PLEASE SEE SPECS WHICH CONTAIN THE |
| | TITLE FROM STEVEN FELLER'S OFFICE |
| | INDICATE THE PUMP AS 277/480V, 125HP. |
| | 215.5 |
| | |
| | 42)NOTE: PLEASE CORRELATE ALL |
| | TRANSFORMERS WITH SCHEDULE(S). PLEASE |
| | SEE 112.5?, 150? KVA |
| | PLEASE ALSO CONFIRM KVA AS MAX OCP FOR |
| | TRANSFORMER MAY NOT EXCEED 125% AS 450.3 |
| | TABLES. |
| | 215.5 |
| | |
| | 43)NOTE: PLEASE COMPLETE BUS-DUCT RISER |
| | AND METER CENTERS AS PLANS ONLY INDICATE |
| | THESE THOUGH FLOOR (8).?? |
| | PLEASE SEE MISSING METER CENTER / MAIN |
| | DISCONNECT ON 3RD FLR, HOWEVER ONE IS |
| | SHOWN ON 4.00 PLANS FOR ELECTRICAL RMS. |
| | ALSO NOTED ABOVE FOR CORRELATION OF ALL |
| | RMS WITH RISER. |
| | 215.5 |
| | |
| | 44)NOTE: PLEASE PROVIDE THE COMPLETE |
| | GROUNDING ELECTRODE SYSTEMS DETAIL PER |
| | 250.50, 250.104, 250.64,,, |
| | |
| | 45)NOTE: PLEASE SEE EDPH2 IS SHOWN AS |
| | 1000A'S ON PANEL SCHEDULES AND SHOWN AS |
| | 800A ON RISER ?? PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 46)NOTE: PLEASE SEE "MSBE2" AS THIS IS |
| | ALSO SHOWN AS 1000A'S ON PANEL |
| | SCHEDULE(S), HOWEVER SHOWN AS 800A'S ON |
| | RISER. PLEASE VERIFY AS 1000A'S OR MORE |
| | 277/480V WILL ALSO REQUIRE GFP ON EM |
| | MAIN. |
| | 230.95,240.13 ETC |
| | |
| | 47)NOTE: PLEASE SEE PANEL "SL" IS SHOWN |
| | AS HAVING "SITE LIGHTING" HOWEVER, SITE |
| | LIGHTING COULD NOT BE LOCATED ON |
| | ELECTRICAL PLANS? |
| | IF SITE LIGHTING CONTAINS LT POLES, |
| | PLEASE SUBMIT WIND LOAD CALCULATIONS |
| | FOR FBC 140MPH. THESE WILL BE REVIEWED |
| | BY A STRUCTURAL REVIEWER. ** PLEASE BE |
| | SHOULD POLE CONTAIN FIXTURES FOR |
| | CALCULATION PURPOSES. |
| | |
| | 48)NOTE: PLEASE VERIFY OCP FOR LARGER |
| | A/C SYSTEMS SHOWN ON PANEL SCHEDULES, |
| | PLEASE SEE 424.3B AS NOTED ABOVE FOR MIN |
| | OCP OF 125%.ADJUST WHERE NEEDED. |
| | RTU#1, #2, #3. PLEASE ALSO ADJUST AWG AS |
| | NEEDED.310.16,240.4 |
| | |
| | 49)NOTE: PLEASE LABEL ALL TRANSFORMERS |
| | ON RISER AS INDICATED ON PANEL |
| | SCHEDULES. |
| | 215.5 |
| | |
| | 50)NOTE: PLEASE VERIFY THE USE OF WHAT |
| | APPEARS TO BE TANDEM BRKRS IN PANELS IN |
| | THIS NEW CONSTRUCTION PROJECT?? |
| | THIS IS ONLY A NOTE. |
| | |
| | 51)NOTE: PLEASE PROVIDE A DISCONNECT |
| | DETAIL INCLUDING SIZE ETC FOR ROOF TOP |
| | UNITS. THIS MAY BE A "TYPICAL" DETAIL |
| | FOR EACH SIZE IF NOT ALL THE SAME. |
| | 215.5,440.11 |
| | |
| | 52)NOTE: PLEASE SEE A BATTERY BACK UP LT |
| | FIXTURE WILL BE REQUIRED IN THE MAIN |
| | ELECTRICAL RM(S), PUMP RMS, FIRE COMMAND |
| | RM, ELEVATOR EQUIPMENT RMS. |
| | 700.16,700.12E, |
| | |
| | 53)NOTE: PLEASE SEE FAIR HOUSING ACT |
| | REGULATIONS, 24 CFR 100.205 WITH RESPECT |
| | TO THE LOCATIONS OF "ALL" ELECTRICAL |
| | DEVICES, CONTROLS. |
| | A NOTE IS LOCATED ON "GEN NOTES" WHICH |
| | MENTIONS THE HEIGHTS FO RECEPTS AND |
| | SWITCHES, HOWEVER THIS SHOULD REFLECT |
| | FHAR ETC AS NOTED ABOVE. |
| | |
| | 54)NOTE: PLEASE SEE THE AMENITY DECK |
| | DETAILS COULD NOT BE LOCATED IN SETS. |
| | PLEASE SEE E2.06 WHICH ONLY SEEMS TO |
| | INDICATE A PARTIAL AREA SHOWN. |
| | PLEASE SEE NO ELECTRICAL SHOWN FOR |
| | LIGHTING ETC? |
| | PLEASE SEE LS 101 7.8 AND 7.9 WHICH |
| | REQUIRES MEANS OF EGRESS LIGHTING TO THE |
| | PUBLIC RIGHT OF WAY.; THIS WOULD INCLUDE |
| | EMERGENCY LIGHTING AS REQUIRED. |
| | PLANS NOW SHOW A SEPARATE PHASE LINE, AS |
| | GARAGE WAS TO BE BUILT WITH PHASE ONE |
| | BLDG AND DID NOT SHOW GARAGE WITH PHASE |
| | LINE DOWN THE CENTER OF THE GARAGE. |
| | |
| | ** NOTE: PLEASE SEE MANY OF THE ABOVE |
| | ITEMS WERE REDLINED ON ONE SET FOR AREAS |
| | OF NOTES ABOVE. |
| | |
| | ** NOTE: PLEASE SEE POSSIBLE NOTES FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS AND DESIGN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW ONCE ALL REVIEWS ARE COMPLETED. |
| | IF THERE ARE NAY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| 2006-01-26 00:00:00 | IN PROGRESS |
| 2006-01-25 00:00:00 | REVIEW STARTED, IN PROGRESS. |
| | PLANS REVIEW STOPPED. NOTES TO FOLLOW, |
| | AS REVIEW IS NOT COMPLETE. |
| 2006-01-24 00:00:00 | |
| | |
| | I ROLL OF MEP'S AND I SUBMITTAL BOOK IN |
| | ELECTRICAL FOR REVIEW. |