Plan Review Notes
Plan Review Notes For Permit 05110247
Permit Number 05110247
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED.
  
 2) INFORMATIVE:
 A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED, COUNTY IMPACT FEES PAID AND A
 SIGNED THRESHOLD INSPECTION AGREEMENT
 SUBMITTED BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.1.1.1ONLY THE
 MECHANICAL SYSTEM DESIGNER'S NAME AND
 LICENSE NUMBER ARE CURRENTLY INCLUDED ON
 SHEET 2 OF THE ENERGY CODE COMPLIANCE
 FORM.ALL OF THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING, MECHANICAL AND PLUMBING
 SYSTEMS SHALL EACH SIGN THE ENERGY CODE
 COMPLIANCE FORM, IN THE SPACE PROVIDED,
 TO CERTIFY COMPLIANCE.
 ALSO, SHEET 1 SHOULD BE COMPLETED WITH
 THE CORRECT PROJECT ADDRESS (350 S
 AUSTRALIAN AVE), ZIP CODE (33401) AND
 PERMIT NUMBER (05110247).
  
 4) 471.023 F.S.STRUCTURAL PLANS.ADD
 THE CERTIFICATE OF AUTHORIZATION NUMBER
 (EB 25930) FOR ECHELON ENGINEERING, LLC
 TO EACH SHEET.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY BE
 ADDED BY HAND.
  
 5) FBC* 104.2.1SHEET CD-02, 2ND - 5TH
 FLOORS, EXITING PLAN.THERE ARE TWO
 DOOR WIDTH NOTES BELOW THE PLAN WHICH
 POINT TO EXITING VIA THE BALCONY OF UNIT
 E2 AT THE NORTH-WEST CORNER OF THE
 BUILDING.THE NOTES ARE NOT APPLICABLE
 TO THE 2ND - 5TH CONFIGURATION.REMOVE
 THE NOTES.
  
 6) FBC* 104.2.1SHEET A1-01, GROUND
 FLOOR PLAN.THE LOCATION OF THE
 ENTRANCE DOOR TO UNIT F1 IS NOT SHOWN
  
 7) FBC* 704.1SHEETS A1-01 AND A1.01B,
 GROUND FLOOR PLAN.THERE IS NO LINE
 TYPE SHOWN ON THE PARTITION LEGEND TO
 SHOW THE FIRE RESISTANCE RATING OF THE
 TRANSFORMER VAULT.
  
 8) FBC* 704.1SHEET A1-01A, GROUND
 FLOOR PLAN.THERE IS NO LINE TYPE
 DIFFERENCE ON THE PLAN OR THE PARTITION
 LEGEND TO DIFFERENTIATE BETWEEN 1 HOUR
 AND 2 HOUR RATED WALLS.
  
 9) RECOMMENDATION:SHEETS A1-01 TO
 A1-17, FLOOR PLANS. FOR CLARITY AT THE
 FIRE RATED WALL LOCATIONS, PLEASE
 CONSIDER CONTINUING THE RELEVANT LINE
 TYPE (SEE PARTITION LEGEND) THROUGH ANY
 ASSOCIATED CONCRETE WALL, COLUMN,
 SHEARWALL ETC SHOWN ON THE PLANS. ALSO,
 THE LINE TYPE FOR THE EXPANSION JOINT,
 ACROSS THE PARKING DECK, ON SHEETS A1-02
 AND A1-04 SHOULD BE CHANGED FOR CLARITY.
  
 10) FBC* 104.2.1SHEET A1-02, 2ND, 3RD,
 5TH FLOOR PLAN.THERE APPEARS TO BE A
 SECTION OF WALL MISSING ALONG GRID A AT
 GRID 25.
  
 11) FBC* 104.2.1FLOOR PLANS.THERE
 APPEARS TO BE NO SPOT LEVELS SHOWN ON
 THE PLANS.IN PARTICULAR, ADD SPOT
 LEVELS TO SHEETS A1-06, A1-17 AND A1-18
 WHICH ARE THE 6TH FLOOR, MAIN ROOF AND
 UPPER ROOF PLANS, RESPECTIVELY.
  
 12) FBC 1608.2.2SHEETS A4-10, A6-20
 AND A7-20.THE GUARDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.ANNOTATE THE PLANS TO
 ENSURE THIS REQUIREMENT IS MET.
  
 13) FBC 1606.1SHEET A6-20, DETAIL 9.
 THE ATTACHMENT OF THE STUCCO CORNICE
 FRAMING SHALL BE SPECIFIED ON THE DETAIL
 OR A NOTE ADDED TO STATE THAT THE
 FRAMING AND ATTACHMENT DETAILS WILL BE
 SUBMITTED ON SPECIALIST SHOP DRAWINGS
 AFTER FIRST BEING REVIEWED BY THE
 DESIGNER OF RECORD.ANNOTATE THE DETAIL
  
 14) FBC 1015.2SHEET A6-20, DETAIL 11.
 THE EFFECTIVE HEIGHT OF THE GUARDRAIL IS
 REDUCED BY THE PRESENCE OF THE CONCRETE
 UPTURNED BEAM WHICH FORMS A LEDGE ON THE
 INSIDE FACE OF THE GUARDRAIL.TO
 PREVENT BUILDING OCCUPANTS FROM STANDING
 ON THIS LEDGE, EITHER PROVIDE A 45
 DEGREE CHAMFER ON THE INSIDE EDGE OF THE
 CONCRETE UPSTAND OR PROVIDE SOME OTHER
 MEANS TO DISCOURAGE CLIMBING.
  
 15) FBC 1608.2.1SHEET A7-20,THE
 HANDRAIL SHALL BE DESIGNED AND
 CONSTRUCTED FOR A CONCENTRATED LOAD OF
 200 LB AND A LINE LOAD OF 50 PLF.THESE
 LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY BUT SHALL BE APPLIED
 INDIVIDUALLY AT ANY POINT, AND IN ANY
 DIRECTION, TO PRODUCE MAXIMUM STRESS IN
 EACH OF THE COMPONENTS OR SUPPORTS.
 AMEND/ANNOTATE THE PLANS TO ENSURE THIS
 REQUIREMENT IS MET.
  
 16) FBC 1601.1SHEET L7-04, PAVILION.
 ADD A PAVILION FOOTING DETAIL.
  
 17) FBC 1606.1PRODUCT APPROVALS
 GENERALLY.MANY OF THE SUBMITTED
 PRODUCT APPROVALS INCLUDE MORE THAN ONE
 OPTION WITH DIFFERENT DESIGN PRESSURE
 RATINGS (WIND PRESSURE IN PSF).MARK
 THE PRODUCT APPROVAL TO SHOW WHICH
 OPTION (DESIGN PRESSURE RATING) IS
 APPLICABLE.PLEASE DO NOT USE
 HIGHLIGHTER PEN BECAUSE IT DOES NOT SHOW
 UP WHEN THE DOCUMENTS ARE SCANNED FOR
 ARCHIVING AT THE END OF THE PROJECT.
  
 18) FBC 1504.1ROOF COVERING. SUBMITTAL
 OF MANUFACTURER'S PRODUCT DATA IS NOTED
 BUT NO OTHER DOCUMENTATION WAS INCLUDED.
 SUBMIT PRODUCT APPROVAL(S) FOR THE
 PROPOSED ROOF SYSTEM(S).
  
 19) FBC 1606.1TRANSFORMER VAULT DOOR
 117A.THE DOOR SCHEDULE, SHEET A8-10,
 SPECIFIES A PAIR OF 3070 HOLLOW METAL
 DOORS.NO PRODUCT APPROVAL WAS
 SUBMITTED FOR A PAIR OF 3070 HOLLOW
 METAL DOORS.THE SUBMITTED CURRIES
 COMPANY COMMERCISL STEEL DOOR PRODUCT
 APPROVAL IS FOR A SINGLE 3070 DOOR.
  
 20) FBC 1606.1SLIDING GLASS DOOR S1.
 ACCORDING TO THE SUBMITTED RWDI WIND
 LOAD STUDY REPORT, THERE ARE LOCATIONS
 ON THE NORTH AND SOUTH ELEVATION WHERE
 THIS DOOR WILL BE SUBJECT TO NEGATIVE
 WIND PRESSURE OF -115 PSF.DRAWING
 SHEET 1 OF THE SUBMITTED MIAMI WALL
 SYSTEMS INC SERIES 100 ALUMINUM SLIDING
 GLASS DOOR PRODUCT APPROVAL NOA#
 04-0908.02, STATES THAT THE MAXIMUM
 DESIGN PRESSURE RATING FOR THE WINDOW IS
 100 PSF.PROVIDE RATIONAL ANALYSIS TO
 JUSTIFY THIS OR PROVIDE AN ALTERNATIVE
 PRODUCT APPROVAL.
  
 21) FBC 1606.1HORIZONTAL SLIDER WINDOW
 W2, W4, W6, W6.1.ACCORDING TO THE
 SUBMITTED RWDI WIND LOAD STUDY REPORT,
 THERE ARE LOCATIONS WHERE THESE WINDOWS
 WILL BE SUBJECT TO A POSITIVE AND/OR
 NEGATIVE WIND PRESSURE OF 95 PSF.
 DRAWING SHEET 1 OF THE SUBMITTED MIAMI
 WALL SYSTEMS INC SERIES 106 ALUMINUM
 HORIZONTAL SLIDER WINDOW PRODUCT
 APPROVAL NOA# 04-1122.02, STATES THAT
 THE MAXIMUM DESIGN PRESSURE RATING FOR
 THE WINDOW IS 90 PSF.PROVIDE RATIONAL
 ANALYSIS TO JUSTIFY THIS OR PROVIDE AN
 ALTERNATIVE PRODUCT APPROVAL.
  
 22) INFORMATIVE:
 FBC 1606.1PRODUCT APPROVAL SUBMITTAL.
 ALL THREE COPIES OF THE SUBMITTED
 DOCUMENT BINDERS INCLUDE SOME INCOMPLETE
 PRODUCT APPROVAL DOCUMENTS.PLEASE
 REVIEW THE BINDERS TO ENSURE THAT A
 PRODUCT APPROVAL HAS BEEN SUBMITTED FOR
 EACH TYPE OF PRODUCT THAT IS TO BE
 INSTALLED.PLAN REVIEW WILL ONLY ENSURE
 THAT THE BINDERS INCLUDE PRODUCT
 APPROVALS TO COVER THE WORST CASE.FOR,
 EXAMPLE IF ONLY A LARGE MISSILE IMPACT
 PRODUCT APPROVAL IS SUBMITTED, THAT
 WOULD MEET PLAN REVIEW REQUIREMENTS BUT
 IT WOULD MEAN THAT PRODUCT WOULD HAVE TO
 BE USED EVEN WHERE LARGE MISSILE IMPACT
 RATING IS NOT REQUIRED.
  
 23) -PROVISO-
 WINDOW WALLS: THE WINDOW SHOP DRAWING
 SUBMITTAL SHALL INCLUDE A STRUCTURAL
 MULLION.THE MULLION MUST BE CAPABLE OF
 SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING FOR THOSE WINDOWS
 THAT EXCEED THE MAXIMUM HEIGHT STATED IN
 THE SUBMITTED MIAMI WALL SYSTEMS INC.
 FIXED WINDOW LARGE MISSILE IMPACT SERIES
 101 AND SMALL MISSILE IMPACT SERIES 101
 PRODUCT APPROVAL NOA'S 03-0415.18 AND
 05-0420.01.
  
 24) -PROVISO-
 SLIDING GLASS DOORS:THE WINDOW/DOOR
 SUBCONTRACTOR SHALL PROVIDE RATIONAL
 ANALYSIS FROM A FLORIDA REGISTERED
 ENGINEER TO JUSTIFY THE USE OF THE
 PROPOSED SLIDING GLASS DOOR IN SIZES
 THAT EXCEED THE MAXIMUM IN THE SUBMITTED
 MIAMI WALL SYSTEMS INC. SERIES 100
 SLIDING GLASS DOOR PRODUCT APPROVAL
 NOA'S 04-0908.02 AND 01-1108.03.
 NOTE: MISSILE IMPACT RATING FOR THESE
 LARGER SIZES CANNOT BE JUSTIFIED BY
 RATIONAL ANALYSIS.MISSILE IMPACT TEST
 RESULTS MUST BE SUBMITTED.
  
 25) -PROVISO-
 HORIZONTAL SLIDER WINDOWS: IT IS NOTED
 THAT 'CUT-DOWN' SLIDING GLASS DOORS WILL
 BE USED FOR THOSE HORIZONTAL SLIDER
 WINDOWS WHICH EXCEED 6'-6" WIDE X 6'-0"
 HIGH (FOR EXAMPLE W2, W2.1, W3, W3.1,
 W3.2(SLIDER?), W3.P, W4, W4.1, W5, W5.1,
 W5.P, W6, W6.1).
  
 26) -PROVISO-
 FIXED WINDOWS:THE WINDOW SHOP DRAWING
 SUBMITTAL SHALL INCLUDE A STRUCTURAL
 MULLION.THE MULLION MUST BE CAPABLE OF
 SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING FOR THOSE WINDOWS
 THAT EXCEED THE 6'-0" MAXIMUM HEIGHT
 STATED IN THE SUBMITTED MIAMI WALL
 SYSTEMS INC. SERIES 122 ALUMINUM FIXED
 WINDOW PRODUCT APPROVAL NOA 04-0322.09.
  
 27) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]