Plan Review Notes
Plan Review Notes For Permit 05110217
Permit Number 05110217
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-06 00:00:00DENIED
  
 1.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING; ROOFING,
 OVERHEAD DOOR, EXTERIOR DOOR, WINDOWS,
 MULLIONS AND STRAPS AND TIE-DOWNS.
  
 2.ALL APPLICATONS RECEIVED AFTER
 OCTOBER 1, 2005 SHALL BE DESIGNED TO THE
 2004 FBC.
  
 3.SHOW ROOM TYPE ADJACENT TO GARAGE.
 SHOW DOOR TYPE.R-309.2 AND R-309.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672