 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE CONDUIT AND CONDUCTOR
 SIZE AND TYPE PER 310.15&16.
  
 2} GIVE THE AIC RATING FOR THE EQUIPMENT
 BEING INSTALLED PER 110.9&10.
  
 3} SIZE THE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66, SHOW SAME ON THE
 PLAN.
  
 4} SUBMIT A FLOOR PLAN WITH LOCATION OF
 THE DEVICES AFFECTED BY THIS PERMIT,
 INDICATE THE ONES BEING ADDED AND THE
 ONES THAT ARE BEING REPLACED(IF ANY).
  
 5} THE CONTRACTOR MUST SIGN THE
 APPLICATION, AND PRINT NAME, SEE THE
 BACK OF THE FORM. IF THE CONTRACTOR
 CANNOT BE HERE PERSONNALLY, HE MAY HAVE
 THE SIGNATURE ON THE DOCUMENT NOTORIZED.
  
 IF THERE ARE ANY QUESTION SPLEASE CALL.
  