| Plan Review Notes For Permit 05110210 |
| Permit Number |
05110210 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-17 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE CONDUIT AND CONDUCTOR | | | SIZE AND TYPE PER 310.15&16. | | | | | | 2} GIVE THE AIC RATING FOR THE EQUIPMENT | | | BEING INSTALLED PER 110.9&10. | | | | | | 3} SIZE THE GROUNDING ELECTRODE | | | CONDUCTOR PER 250.66, SHOW SAME ON THE | | | PLAN. | | | | | | 4} SUBMIT A FLOOR PLAN WITH LOCATION OF | | | THE DEVICES AFFECTED BY THIS PERMIT, | | | INDICATE THE ONES BEING ADDED AND THE | | | ONES THAT ARE BEING REPLACED(IF ANY). | | | | | | 5} THE CONTRACTOR MUST SIGN THE | | | APPLICATION, AND PRINT NAME, SEE THE | | | BACK OF THE FORM. IF THE CONTRACTOR | | | CANNOT BE HERE PERSONNALLY, HE MAY HAVE | | | THE SIGNATURE ON THE DOCUMENT NOTORIZED. | | | | | | IF THERE ARE ANY QUESTION SPLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|