Plan Review Notes
Plan Review Notes For Permit 05110205
Permit Number 05110205
Review Stop P
Sequence Number 3
Notes
Date Text
2006-02-24 00:00:00DENIED 3RD TIME
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 1) COMPLY WITH FBC-2004 SEC. 424.2
 PRIVATE SWIMMING POOLS (ADD TO NOTES)
 2) FBC-2004 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (NOTE: IN TWO PLACES ON PRINT
 IT IS INDICATED THAT AIR TESTS ARE
 APPROVED, THEY ARE NOT APPROVED AGAIN I
 ASK YOU TO PLEASE REMOVE FROM PRINT THAT
 AIR TESTS ARE APPROVED)
 3) FBC-2004 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS.
 NEED ENGINEERED TABLE FOR "VENT PIPE
 MAXIMUM LENGTH" INDICATING PUMP SIZES,
 AVERAGE FLOW, AND MAXIMUM LENGTH OF
 1-1/2" PVC VENT PIPE FROM WHERE IT
 STARTS TO WHERE IT ENDS UP TO COMPLY
 WITH 3 SECOND RELEASE.
  
 END OF COMMENTS:
  