| Plan Review Notes For Permit 05110205 |
| Permit Number |
05110205 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-02-24 00:00:00 | DENIED 3RD TIME | | | REFERENCE: FBC-2004 424.2 SWIMMING POOLS | | | | | | 1) COMPLY WITH FBC-2004 SEC. 424.2 | | | PRIVATE SWIMMING POOLS (ADD TO NOTES) | | | 2) FBC-2004 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (NOTE: IN TWO PLACES ON PRINT | | | IT IS INDICATED THAT AIR TESTS ARE | | | APPROVED, THEY ARE NOT APPROVED AGAIN I | | | ASK YOU TO PLEASE REMOVE FROM PRINT THAT | | | AIR TESTS ARE APPROVED) | | | 3) FBC-2004 SEC 424.2.6.6 ENTRAPMENT | | | PROTECTION FOR SUCTION INLETS. | | | NEED ENGINEERED TABLE FOR "VENT PIPE | | | MAXIMUM LENGTH" INDICATING PUMP SIZES, | | | AVERAGE FLOW, AND MAXIMUM LENGTH OF | | | 1-1/2" PVC VENT PIPE FROM WHERE IT | | | STARTS TO WHERE IT ENDS UP TO COMPLY | | | WITH 3 SECOND RELEASE. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 | | | | | | |
|