| Plan Review Notes For Permit 05110205 |
| Permit Number |
05110205 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-13 00:00:00 | DENIED; | | | 1) FBC-2004424.2.6.6.5 WHERE PROVIDED, | | | THE VACUUM OR PRESSURE CLEANER FITTING | | | SHALL BE LOCATED AT LEAST 6" AND NOT | | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | | THE SKIMMER. | | | 15) FBC-2004 424.2.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | | SHEETS REQUIRED. (SUBMITTAL) PLAN CALLS | | | FOR A GAS HEATER, SUBMITAL SHEET IS FOR | | | A HEAT PUMP. PLEASE REVISE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|