| Plan Review Notes For Permit 05110194 |
| Permit Number |
05110194 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-28 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE SERVICE SIZE AND IF IT IS | | | PROPOSED OR EXISTING. | | | | | | 2} INDICATE IF THE ELECTRICAL WORK SHOWN | | | IN THE KITCHEN IS PROPOSED OR EXISTING, | | | IT IS NOT IN THE DESCRIPTION OF WORK ON | | | THE APPLICATION. | | | | | | 3} PLEASE NOTE THAT RECEPTACLES ARE NOT | | | SHOWN IN THE NEW PROPOSED BEDROOM. SEE | | | 210.12 AND 210.52. | | | | | | 4} THE WELL AND SPRINKLER PUMP MUST BE | | | ADDED TO THE LOAD CALCULATIONS PER | | | ARTICLE 220. | | | | | | AN ELECTRICAL PERMIT IS REQUIRED FOR | | | THIS WORK. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|