| Plan Review Notes For Permit 05110191 |
| Permit Number |
05110191 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-06 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE | | | SITE DAILY. | | | | | | 3. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM REMODEL. | | | | | | 4. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | 5. COULD NOT LOCATE ANY EMERGENCY LIGHT | | | FIXTURES ON ELECTRICAL SHEETS. | | | | | | 6. PLEASE EXPLAIN PROPOSED KEY LOCK | | | HARDWARE SHOWN ON PAGE A-6. HOW DOES | | | THESE DEVICES INTERFACE WITH EXITING. | | | | | | 7. GENERAL HARDWARE NOTES ON PAGE A-2 | | | IS INCORRECT. CHAPTER 7 OF THE LIFE | | | SAFETY CODE SHALL BE REFERENCED INSTEAD | | | OF CHAPTER 5. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|