| 2007-08-09 12:14:25 | ---------------DENIED----------------- |
| | |
| | FBC 2004 CODE FAMILY |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY. |
| | |
| | NOTE: NO WRITTEN RESPONSE TO PREVIOUS REVIEW COMMENTS |
| | WAS FOUND IN THIS SUBMITTAL PACKAGE. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. RELOCATING CONDENSER STANDS: IS THIS NO LONGER PART |
| | OF THE SCOPE OF THIS PERMIT? NO INFORMATION WAS FOUND |
| | ON PLANS OR IN SUBMITTAL PACKAGE. PLEASE CLARIFY. A |
| | NARRATIVE OR WRITTEN RESPONSE TO PREVIOUS RVIEW |
| | COMMENTS WILL HELP IN EXPEDITING THE REVIEW PROCESS. |
| | |
| | 4. PG 6.2: DRAWING OF "SHIP'S LADDER" SHOWS THE LATTER |
| | STARTING AT 6 FEET ABOVE GRADE. THE EXTENT OF THE |
| | LADDER SHALL BE FROM GRADE OR FLOOR LEVEL TO THE |
| | EQUIPMENT'S LEVEL SERVICE SPACE. SEE FBC,M 306.5. |
| | |
| | 5. NO OUTDOOR AIR INFORMATION COULD BE FOUND ON PLANS. |
| | PROVIDE OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, |
| | OUTDOOR AIR REQUIRED PER OCCUPANT AND THE AMOUNT OF |
| | OUTDOOR AIR TO BE PROVIDED IN ACCORDANCE WITH FBC,M |
| | TABLE 403.3. ALSO, PROVIDE INFORMATION FOR TOILET ROOM |
| | EXHAUST FANS SUCH AS MODEL # AND CFM. |
| | |
| | 6. ENERGY CALCULATIONS: |
| | A) ON THE PROJECT SUMMARY PAGE, PLEASE INCLUDE ALL |
| | AVAILABLE INFORMATION IN THE GIVEN FIELDS. MISSING ON |
| | THIS FORM ARE THE OWNER NAME AND THE PERMIT NUMBER. |
| | B) CALCULATION PROCEDURES SHALL BE PREPARED, SIGNED AND |
| | SEALED BY AN ARCHITECT OR ENGINEER REGISTERED IN |
| | FLORIDA PER FBC 13-400.3.ABC.1. |
| | C) THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR |
| | OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER |
| | SHALL CERTIFY TO THE BUILDING OFFICIAL THAT THE |
| | BUILDING IS IN COMPLIANCE WITH THE REQUIREMENTS OF |
| | CHAPTER 13 OF THIS CODE PRIOR TO RECEIVING THE PERMIT |
| | TO BEGIN CONSTRUCTION OR RENOVATION. THE PARTY |
| | RESPONSIBLE UNDER SUBSECTIONS 471.003 AND 481.228 AND |
| | CHAPTER 489, FLORIDA STATUTES, FOR THE DESIGN AND |
| | SPECIFICATION OF EACH BUILDING SYSTEM SHALL CERTIFY |
| | THAT THE PLANS AND SPECIFICATIONS FOR THAT SYSTEM |
| | COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THIS CODE |
| | (SEE ALSO SECTION 13-103.2). |
| | D) WALL TYPE ON INPUT DATA REPORT CALLS FOR 8 INCH |
| | LIGHTWEIGHT CONCRETE BLOCK. IF THIS TYPE OF BLOCK IS TO |
| | BE USED FOR AN ENERGY CREDIT IT MUST BE SPECIFIED ON |
| | PLANS. |
| | E) PG 4.1 GENERAL NOTE #22 CALLS FOR MINIMUM R-5 |
| | INSULATION ON ALL CBS WALLS. ADJUST CALCULATIONS TO |
| | CORRESPOND WITH PLANS. |
| | F) PG 4.1 GENERAL NOTE #22 CALLS FOR R-19 BATT |
| | INSULATION ON CEILINGS IN ALL CONDITIONED SPACES. DOES |
| | THIS SPACE HAVE A CEILING? WHERE AND HOW WILL THIS |
| | INSULATION BE INSTALLED? ADJUST INPUT DATA REPORT TO |
| | CORRESPOND WITH THE ACTUAL ROOF/INSULATION TYPE TO BE |
| | USED. PLA DOES NOT SHOW A BUILT-UP GRAVEL ROOF. |
| | |
| | 7. OK |
| | |