Plan Review Notes
Plan Review Notes For Permit 05110189
Permit Number 05110189
Review Stop M
Sequence Number 3
Notes
Date Text
2007-08-09 12:14:25---------------DENIED-----------------
  
 FBC 2004 CODE FAMILY
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 NOTE: NO WRITTEN RESPONSE TO PREVIOUS REVIEW COMMENTS
 WAS FOUND IN THIS SUBMITTAL PACKAGE.
  
 1. OK
  
 2. OK
  
 3. RELOCATING CONDENSER STANDS: IS THIS NO LONGER PART
 OF THE SCOPE OF THIS PERMIT? NO INFORMATION WAS FOUND
 ON PLANS OR IN SUBMITTAL PACKAGE. PLEASE CLARIFY. A
 NARRATIVE OR WRITTEN RESPONSE TO PREVIOUS RVIEW
 COMMENTS WILL HELP IN EXPEDITING THE REVIEW PROCESS.
  
 4. PG 6.2: DRAWING OF "SHIP'S LADDER" SHOWS THE LATTER
 STARTING AT 6 FEET ABOVE GRADE. THE EXTENT OF THE
 LADDER SHALL BE FROM GRADE OR FLOOR LEVEL TO THE
 EQUIPMENT'S LEVEL SERVICE SPACE. SEE FBC,M 306.5.
  
 5. NO OUTDOOR AIR INFORMATION COULD BE FOUND ON PLANS.
 PROVIDE OCCUPANCY CLASSIFICATION, OCCUPANT LOAD,
 OUTDOOR AIR REQUIRED PER OCCUPANT AND THE AMOUNT OF
 OUTDOOR AIR TO BE PROVIDED IN ACCORDANCE WITH FBC,M
 TABLE 403.3. ALSO, PROVIDE INFORMATION FOR TOILET ROOM
 EXHAUST FANS SUCH AS MODEL # AND CFM.
  
 6. ENERGY CALCULATIONS:
 A) ON THE PROJECT SUMMARY PAGE, PLEASE INCLUDE ALL
 AVAILABLE INFORMATION IN THE GIVEN FIELDS. MISSING ON
 THIS FORM ARE THE OWNER NAME AND THE PERMIT NUMBER.
 B) CALCULATION PROCEDURES SHALL BE PREPARED, SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER REGISTERED IN
 FLORIDA PER FBC 13-400.3.ABC.1.
 C) THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY TO THE BUILDING OFFICIAL THAT THE
 BUILDING IS IN COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THIS CODE PRIOR TO RECEIVING THE PERMIT
 TO BEGIN CONSTRUCTION OR RENOVATION. THE PARTY
 RESPONSIBLE UNDER SUBSECTIONS 471.003 AND 481.228 AND
 CHAPTER 489, FLORIDA STATUTES, FOR THE DESIGN AND
 SPECIFICATION OF EACH BUILDING SYSTEM SHALL CERTIFY
 THAT THE PLANS AND SPECIFICATIONS FOR THAT SYSTEM
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THIS CODE
 (SEE ALSO SECTION 13-103.2).
 D) WALL TYPE ON INPUT DATA REPORT CALLS FOR 8 INCH
 LIGHTWEIGHT CONCRETE BLOCK. IF THIS TYPE OF BLOCK IS TO
 BE USED FOR AN ENERGY CREDIT IT MUST BE SPECIFIED ON
 PLANS.
 E) PG 4.1 GENERAL NOTE #22 CALLS FOR MINIMUM R-5
 INSULATION ON ALL CBS WALLS. ADJUST CALCULATIONS TO
 CORRESPOND WITH PLANS.
 F) PG 4.1 GENERAL NOTE #22 CALLS FOR R-19 BATT
 INSULATION ON CEILINGS IN ALL CONDITIONED SPACES. DOES
 THIS SPACE HAVE A CEILING? WHERE AND HOW WILL THIS
 INSULATION BE INSTALLED? ADJUST INPUT DATA REPORT TO
 CORRESPOND WITH THE ACTUAL ROOF/INSULATION TYPE TO BE
 USED. PLA DOES NOT SHOW A BUILT-UP GRAVEL ROOF.
  
 7. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]