2007-08-12 15:05:57** DENIED 3RD REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 HAS
 STILL NOT BEEN ACHIEVED.
 PLEASE SEE MISSING TIME SCHEDULING.
 PLEASE SEE NO OVER RIDE DEVICES AS REQUIRED PER CODE.
 PLEASE SEE MISSING MAXIMUM OVER RIDE TIMES.
 PLEASE SEE MISSING CONTROLS/SYSTEM FOR EACH LEVEL AS
 ONE SYSTEM MAY NOT FEED MULTIPLE LEVELS.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOW
 UNDER THE NEW CODE WHICH WAS ADOPTED DECEMBER 8TH,
 2006. THIS PROJECT WAS APPLIED FOR IN NOVEMBER OF 05
 WHICH PLACES THE ENERGY CALCULATIONS UNDER A DIFFERENT
 VERSION. *MAY NOT USE CALCULATIONS FROM ONE ADOPTED
 CODE AND PLANS DESIGNED UNDER ANOTHER*
 PLEASE CLARIFY HOW NO EXTERIOR LIGHTING IS ENTERED INTO
 THE ENERGY CALCULATIONS WHEN THE PLANS CLEARLY SHOWS
 LIGHTING?13-415.2.ABC.1.3
 THIS HAS BEEN CONFIRMED WITH THE STATE OF FLORIDA
 BUILDING COMMISSION.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DOES NOT
 CORRELATE WITH PLANS FOR THE METHOD OF CONTROLS,
 FIXTURES, WATTAGE ETC.
 PLEASE SEE THE CALCULATIONS ARE REQUIRED TO BE SIGNED,
 DATED AND SEALED PER 13-103.1.1.1
 FS 481.221/471.025
  
 PLEASE SEE 13-415.2.ABC.1, 13-415.1.A,
 13-415.2.ABC.1.1, 13-415.2.ABC.1FOR PERFORMANCE
 CALCULATIONS/ENERGY CALCULATIONS TO BE SHOWN FOR
 COMPLIANCE WHICH IS NOT DONE AT THIS TIME.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3FOR LIGHTING
 CONTROLS, FIXTURES, SCHEDULING , OVER-RIDES, MORE THAN
 ONE FLR, LOCATIONS OF OVER-RIDE DEVICES AND TIME
 LIMITS.
  
 2) NOTE: PLEASE SUBMIT A FIXTURE LEGEND WHICH
 CORRELATES WITH THE CALCULATIONS FOR CHAPTER 13 AS
 SUBMITTED.
 FBC 106.3.5.1.2, 106.1.2
  
 3) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 PHOTO-METRICS FOR STAIRS FOR EGRESS HOWEVER THESE ARE
 STILL NOT SUBMITTED.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004 AS
 THIS IS REQUIRED AS A PART OF MINIMUM LIGHTING DESIGNS
 FOR ENGINEER.
 NFPA-101 2003 7.8.1.3,7.9.2.2
 ** PLEASE SHOW AND INDICATE ALL OTHER EM/EXT LTS NEW OR
 EXISTING ON PLANS .
  
 4) NOTE:THIS IS THE SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE LOADS SHOWN ON PANEL "D" DO NOT SEEM TO
 CORRELATE WITH THE LOADS INDICATED ON PANEL "E". PANEL
 *E* IS SHOWN BEING FED FROM PANEL *D*. PLEASE
 COORDINATE.
 PLEASE STILL CLARIFY SERVICE AS THIS IS STILL BEING
 SHOWN AS 120/240 ON PANELS AND RESPONSE AND NOTE
 MENTIONS DELTA SERVICE WITH HIGH-LEG YET THE NOTE ALSO
 MENTIONS THIS IS A 208V SERVICE. HOW IS THIS POSSIBLE?
 PLEASE ADJUST AND CLARIFY SERVICE AS SHOWN.
 PLEASE ADJUST LOAD CALCULATIONS AS NEEDED.
 NEC 220, 230, 310, 408 ETC THERE ARE MANY ITEMS TO
 REVIEW FOR COMPLIANCE, HOWEVER AS SERVICE IS NOT CLEAR
 NOT PARTICULAR REVIEW OF THIS EQUIPMENT CAN BE DONE.
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM GUTTER TO EACH DISCONNECT A, B AND C.
 250.110, 250.122 ETC.
  
 6) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS.
 FBC ADMIN SECTION 106.1
  
 7) NOTE:PLEASE SEE PREVIOUS REVIEW WHICH GAVE NOTICE
 TO FLORIDA STATUTES 553.80(2)(B) DUE TO REPEAT CODE
 COMPLIANCE COMMENTS.
 PLEASE SEE THIS FEE HAS NOW BEEN ASSESSED AS REQUIRED
 BY THE FLORIDA STATUES. THIS IS A REQUIRED STATUTE.
 THIS FEE OF $9,788.82 IS DUE BEFORE NEXT RE-SUBMITTAL
 OF PLANS. ELECTRICAL PLANS AND CALCULATIONS SUBMITTED
 ARE RETAINED AT THIS TIME.
 PLEASE SEE NOTICE TO FS553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS.
 TO DATE NO ONE HAD CONTACTED THIS OFFICE TO GO OVER
 THESE COMMENTS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  