Plan Review Notes
Plan Review Notes For Permit 05110189
Permit Number 05110189
Review Stop B
Sequence Number 3
Notes
Date Text
2007-08-17 06:04:20 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 05110189
 ADD: 2025 N. DIXIE HWY
 CONT: GR CONCEPTS
 TEL: (561)743-0066
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 AT THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) OK
  
 3) OK
  
 4) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF FLOORS
 ) SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 5) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 PRODUCTS WITH STATEWIDE APPROVAL ARE
 REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE.SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG. NOTE: THE
 PRODUCT APPROVALS FOR THE DOORS AND WINDOWS ARE
 EXPIRED. SUBMIT NEW AND
 UP-DATED PRODUCT APPROVALS FOR THE
 DOORS/WINDOWS/SHUTTERS/ROOFING MATERIALS
 ETC.
 NEW*** TWO SETS OF PRODUCT APPROVALS SHALL BE SUBMITTED
 FOR EACH PRODUCT.THE PRODUCT APPROVAL FOR THE
 ROOFING.
 FBC 1609.6.2.2 THE SYSTEM SELECTED
 FROM THE SUBMITTED FLAT ROOF PRODUCT
 APPROVAL NOA HAS A MAXIMUM DESIGN
 PRESSURE OF LESS THAN -89 PSF AND CITES
 GENERAL LIMITATION #9 (SEE PAGE 12_ OF
 _41_).GENERAL LIMITATION #9 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 6) OK
  
 7) 13-103.1.2 THE BUILDING OWNER, THE OWNER'S
 ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION.
 IF, DURING THE BUILDING'S CONSTRUCTION OR RENOVATION,
 ALTERATIONS ARE MADE IN THE BUILDING?S DESIGN OR IN
 MATERIALS OR EQUIPMENT INSTALLED IN THE BUILDING WHICH
 WOULD DIMINISH ITS ENERGY PERFORMANCE, AN AMENDED COPY
 OF THE COMPLIANCE CERTIFICATION SHALL BE SUBMITTED TO
 THE BUILDING OFFICIAL ON OR BEFORE THE DATE OF FINAL
 INSPECTION BY THE BUILDING OWNER OR HIS OR HER LEGALLY
 AUTHORIZED AGENT.
 BEFORE A BUILDING PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE SIGNED BY THE
 BUILDING OWNER, THE
 OWNER?S ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.
  
 8) OK
  
 9) OK
  
 10) OK
  
 NO RESPONSE****
 11) EXPLAIN WHAT TYPE OF WORK IS CARRIED OUT IN THE
 WORKSHOP AREA. WHAT TYPE OF MATERIAL WILL BE DISPLAYED
 IN THE SHOW ROOMS? THE BUILDING OCCUPANCY MAY CHANGE
 DUE TO THE USE OF THE WORKSHOP AND OTHER AREAS IN THE
 BUILDING.
  
 12) OK
  
 13) OK
  
 14) OK
  
 NEW************
  
 A)SHEET 3.1 THE DIMENTIONS FOR F-I ON THE FOUNDATION
 LEGEND DO NOT MATCH DETAIL #3 ON SHEET 8.2. CLARIFY.
  
 B)GEOTECHNICAL TESTING LAB RECOMEND THAT THE MINIMUM
 CONTINOUS FOOTING WIDTH BE 30". THE CONTINOUS FOOTING
 ON SHEET 3.1 SHOWS A 20" WIDTH. THE TESTING LAB REPORTS
 SHALL NOT BE IGNORED.
  
 C)A FRAMING HEADDER DETAIL FOR THE NEW 3 FOOT OPENING
 CONNECTING THE BUILDINGS IS REQUIRED. SEE SHEET 4.1
  
 D)HOW CAN THE FOUNDATION /FLOOR AND ROOF PLAN HAVE
 THE SAME DETAIL? #3 SHEETS 8.1. SEE PAGES 3.1 / 4.1 AND
 6.1. FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOACTION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 E)FBC TABLE 1607.1 IF THE MEZZANINE IS USED AS OFFICE
 SPACE THE DESIGN FLOOR LOAD SHALL BE 50 PSF. INDICATE
 THE STAIRS FLOOR LOAD ON THE PLANS.
  
 F)FBC 903.2.6 IF THE BUILDING IS DECLEARED AS GROUP M
 THERE IS A POSSIBILITY IT WILL REQUIRE A SPRINKLER
 SYSTEM ACCORDING TO THIS SECTION.
  
 G)FBC. 302.3WHEN A BUILDING IS OCCUPIED BY TWO OR
 MORE USES NOT INCLUDED IN THE SAME OCCUPANCY
 CLASSIFICATION, THE BUILDING OR PORTION THEREOF SHALL
 COMPLY WITH SECTION 302.3.1 OR 302.3.2.
  
 H)FBC. 1607.7.1 HANDRAIL ASSEMBLIES AND GURADS SHALL
 BE DESIGNED TO RESIST A LOAD OF 50 PLF APPLIED IN ANY
 DIRECTION AT THE TOP AND TO TRANSFER THIS LOAD THROUGH
 THE STRUCTURE.
  
 I)FBC. 1607.7.1.1 THE GUARD RAIL SHALLBE ABLE TO
 RESIST A SINGLE CONCENTRATED LOAD OF 200 POUNDS. SHOW
 IN DETAIL HOW THESE REQUIREMENTS WILL BE MET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]