| 2006-07-19 00:00:00 | DENIED:2004 FBC |
| | COMMENTS FROM REVIEW DATED 1-25-06 |
| | |
| | COMMENT #1:OK |
| | COMMENT #2:PLAN SHEET 9.1 ROOF CURB |
| | DETAIL INDICATES 8" FROM THE BAR JOIST |
| | FLANGE TO THE FLASHING.PER THE 2004 |
| | FBC 1509.7, ROOF CURBS SHALL EXTEND 8" |
| | ABOVE THE ROOF SURFACE NOT THE BAR |
| | JOIST. |
| | |
| | COMMENT #3:PLEASE PROVIDE A DETAIL FOR |
| | THE RELOCATED CONDENSING UNIT STANDS. |
| | PLEASE SHOW COMPLIANCE WITH 2004 FBC |
| | TABLE 1509.7. |
| | |
| | COMMENT #4:PLAN SHEET 6.2 INDICATES A |
| | SHIPS LADDER WILL BE INSTALLED ON THE |
| | WALL WHERE THE LOWER EXISTING ROOF MEETS |
| | THE NEW HIGHER ROOF.PLAN DOES NOT |
| | INDICATE ACCESS TO EXISTING ROOF. |
| | PLEASE ANNOTATE EXISTING ROOF ACCESS. |
| | |
| | COMMENT #5: PLEASE PROVIDE OUTSIDE AIR |
| | CALUCALTIONS IN ACCORDANCE WITH 2004 FMC |
| | TABLE 403.3. |
| | |
| | *****************NEW COMMENTS*********** |
| | 6.ENERGY CALCULATION FORM SUBMITTED IS |
| | NOT THE PROPER FORM.COMPLIANCE |
| | CALCULATIONS ARE THOSE UTILIZED IN THE |
| | ENERGY GAUGE FLA/COM COMPUTER PROGRAM. |
| | |
| | 7.PLEASE PROVIDE DUCT AND GRILL SIZES. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |