| 2006-06-15 00:00:00 | A |
| | ********* UNSAT 2ND REVIEW ******** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIUOUS |
| | REVIEW AND SOME NEW NOTES DUE TO ITEMS |
| | ON PLANS NOT ON ORIGINAL. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 |
| | MENTIONED PLANS CAME IN DESIGNED UNDER |
| | THE 2001 FBC WHERE THE DESIGNS AFTER OCT |
| | 1ST 2005 REQUIRED CHANGE TO THE 2004 |
| | FBC. |
| | PLEASE SEE ENERGY CODE COMPLIANCE FORMS |
| | ARE STILL BEING SHOWN UNDER THE 2001. |
| | PLEASE SEE THERE ARE NUMEROUS CHANGES |
| | UNDER THE 2004 FBC CHAPTER 13 AND |
| | LIGHTING DENSITIES ETC. |
| | PLEASE SEE 13-415.2.ABC.1 FOR |
| | PERFORMANCE CALCULATIONS TO BE SHOWN FOR COMPLIANCE |
| | WHICH IS NOT DONE AT THIS |
| | TIME. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 |
| | FOR LIGHTING CONTROLS, FIXTURES, |
| | SCHEDULING , OVER-RIDES, MORE THAN ONE |
| | FLR, LOCATIONS OF OVER-RIDE DEVICES AND |
| | TIME LIMITS. |
| | PLEASE SEE MIN VOLTAGE DROP INFORMATION |
| | FOR WORST CASE SHALL BE SHOWN PER |
| | 13-413.1.ABC.1 |
| | PLEASE SEE 13-415.1.ABC.3 ETC |
| | |
| | 2) NOTE: PLEASE SEE MISSING |
| | PHOTO-METRICS FOR STAIRSAS NOTED ON |
| | PREVIOUS REVIEW. PLEASE SEE THIS DETAIL |
| | CAN BE TYPICAL FOR EACH IF APPLICABLE |
| | FOR SAME TYPE OF FIXTURES ANDLAYOUT. |
| | NFPA-101 2003 7.8.1.3,7.9.2.2 |
| | ** PLEASE SHOW AND INDICATE ALL OTHER |
| | EM/EXT LTS NEW OR EXISTING ON PLANS . |
| | |
| | 3) NOTE: PLEASE SEE LOADS SHOWN ON PANEL |
| | "D" DO NOT SEEM TO CORRELATE WITH THE |
| | LOADS INDICATED ON PANEL "E". |
| | PLEASE CLARIFY. |
| | PLEASE ALSO VERIFY LOAD CALCULATION AS |
| | SERVICE IS BEING SHOWN AS 3-PHASE YET IT |
| | SEEM ONLY THE A/C LOADS ARE BEING |
| | FIGURED AT 3-PHASE. |
| | PLEASE SEE NEC 220, |
| | |
| | 4) NOTE: PLEASE SEE ARCHITECTURAL PLANS |
| | WHICH INDICATE NEW WORK IN OTHER AREAS , |
| | YET THE ELECTRICAL PLANS DO NOT |
| | CORRELATE WITH THIS. |
| | PLEASE SEE NEW LIGHTING IS MENTIONED AND |
| | AREAS TO BE REMODELED, YET NONE IS |
| | SHOWN?? |
| | PLEASE COMPLETE. |
| | |
| | 5) NOTE: PLEASE SEE NOTICE TO FS |
| | 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ** PLEASE SUBMIT ONLY ONE COPY OF THE |
| | OLD/VOIDED SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTRUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2006-06-14 00:00:00 | PLANS IN ELECTRICAL FOR REVIEW. |