Plan Review Notes For Permit 05110189
Permit Number 05110189
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-15 00:00:00A
 ********* UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM PREVIUOUS
 REVIEW AND SOME NEW NOTES DUE TO ITEMS
 ON PLANS NOT ON ORIGINAL.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1
 MENTIONED PLANS CAME IN DESIGNED UNDER
 THE 2001 FBC WHERE THE DESIGNS AFTER OCT
 1ST 2005 REQUIRED CHANGE TO THE 2004
 FBC.
 PLEASE SEE ENERGY CODE COMPLIANCE FORMS
 ARE STILL BEING SHOWN UNDER THE 2001.
 PLEASE SEE THERE ARE NUMEROUS CHANGES
 UNDER THE 2004 FBC CHAPTER 13 AND
 LIGHTING DENSITIES ETC.
 PLEASE SEE 13-415.2.ABC.1 FOR
 PERFORMANCE CALCULATIONS TO BE SHOWN FOR COMPLIANCE
 WHICH IS NOT DONE AT THIS
 TIME.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3
 FOR LIGHTING CONTROLS, FIXTURES,
 SCHEDULING , OVER-RIDES, MORE THAN ONE
 FLR, LOCATIONS OF OVER-RIDE DEVICES AND
 TIME LIMITS.
 PLEASE SEE MIN VOLTAGE DROP INFORMATION
 FOR WORST CASE SHALL BE SHOWN PER
 13-413.1.ABC.1
 PLEASE SEE 13-415.1.ABC.3 ETC
  
 2) NOTE: PLEASE SEE MISSING
 PHOTO-METRICS FOR STAIRSAS NOTED ON
 PREVIOUS REVIEW. PLEASE SEE THIS DETAIL
 CAN BE TYPICAL FOR EACH IF APPLICABLE
 FOR SAME TYPE OF FIXTURES ANDLAYOUT.
 NFPA-101 2003 7.8.1.3,7.9.2.2
 ** PLEASE SHOW AND INDICATE ALL OTHER
 EM/EXT LTS NEW OR EXISTING ON PLANS .
  
 3) NOTE: PLEASE SEE LOADS SHOWN ON PANEL
 "D" DO NOT SEEM TO CORRELATE WITH THE
 LOADS INDICATED ON PANEL "E".
 PLEASE CLARIFY.
 PLEASE ALSO VERIFY LOAD CALCULATION AS
 SERVICE IS BEING SHOWN AS 3-PHASE YET IT
 SEEM ONLY THE A/C LOADS ARE BEING
 FIGURED AT 3-PHASE.
 PLEASE SEE NEC 220,
  
 4) NOTE: PLEASE SEE ARCHITECTURAL PLANS
 WHICH INDICATE NEW WORK IN OTHER AREAS ,
 YET THE ELECTRICAL PLANS DO NOT
 CORRELATE WITH THIS.
 PLEASE SEE NEW LIGHTING IS MENTIONED AND
 AREAS TO BE REMODELED, YET NONE IS
 SHOWN??
 PLEASE COMPLETE.
  
 5) NOTE: PLEASE SEE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ** PLEASE SUBMIT ONLY ONE COPY OF THE
 OLD/VOIDED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  