Plan Review Notes
Plan Review Notes For Permit 05110189
Permit Number 05110189
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. APPLICATION DESCRIPTION OF PROJECT
 INDICATES "ADDITION ONTO EXISTING BLDG."
 PLANS INDICATE ALTERATION OF EXISTING
 BLDG. ALSO. PLEASE DESCRIBE PROJECT IN
 DETAIL ON APPLICATION AS REQUIRED.
 2. SHT P4.1 PER TABLE A DRINKING
 FOUNTAIN IS REQUIRED.
 3. INDICATE THE USE OF THE MEZZANINE,
 AND INDICATE THE USE OF THE WORKSHOP TO
 DETERMINE OCCUPANCY. SECTION 106.1.1.
 4. SHT 8.2 RESTROOM ELEVATIONS. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS (SHOW LENGTH OF
 GRAB BAR BEHIND THE W/C)
 D. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 FOR TOILET ROOMS:
 A. TURNING AREA TO BE UNOBSTRUCTED, W/C
 SHALL NOT BE IN TURNING AREA. SECTION
 11-4.22.3
 5. SUBMIT A DETAIL FOR THE BREAK ROOM
 SINK SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIED)
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 6. SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.4 CONTROLS
 D. 11-4.15.5 CLEARANCES/CLEAR FLOOR
 SPACE
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 7. SHOW PIPE ROUTING FOR THE SANT.
 SYSTEM, WATER PIPING, STORM, AND
 CONDENSATE. SECTIONS 106.1.1, AND
 106.3.5.1.3.
 8. SUBMIT A SANITARY RISER DIAGRAM
 ISOMETRIC SHOW ALL PIPE SIZES, TRAPS,
 VENTS REQUIRED. SECTION 106.3.5.1.3.
 9. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES AND WATER HAMMER
 ARRESTORS IF REQUIRED BY SECTION 604.9.
 (AIR CHAMBERS ARE NOT APPROVED). SECTION 106.3.5.1.3.
 10. SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES AND INDICATE THE SQUARE
 FOOTAGE DRAINED BY EACH DRAIN. SECTION 106.3.5.1.3.
 11. SUBMIT A CONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZE, TRAPS ETC. IN
 ISOMETRIC FORM.
 12. SHT 6.2 INDICATES 6" ROOF DRAINS
 WITH SCUPPERS IN PARAPET NEXT TO THE
 DRAINS. SHT 8.2 INDICATES DOWNSPOUTS
 OUTSIDE BLDG WALL. PLEASE CLARIFY. IF
 ROOF DRAINS ARE DOWNSPOUTS, DOWNSPOUTS
 SHALL DISCHARGE AT LEAST 1 FOOT AWAY
 FROM THE STRUCTURE SIDEWALL. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED.
 SECTION 1503.6.
 13. RPZV BACKFLOW REQUIRED ON THE WATER
 SERVICE TO BLDG.
 14. SEPARATE IRRIGATION PLANS AND PERMIT
 REQUIRED. SECTION 106.3.5.1.3.
 15. CODE ADOPTED IN FBC-2004 IN EFFECT
 SINCE 10-01 2005. PLEASE CHANGE
 REFERENCES TO CODE TO REFLECT THIS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 REMOVE ALL VOIDED SHEETS AND RESUBMIT
 ONE SET FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]