| Date |
Text |
| 2006-02-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. APPLICATION DESCRIPTION OF PROJECT |
| | INDICATES "ADDITION ONTO EXISTING BLDG." |
| | PLANS INDICATE ALTERATION OF EXISTING |
| | BLDG. ALSO. PLEASE DESCRIBE PROJECT IN |
| | DETAIL ON APPLICATION AS REQUIRED. |
| | 2. SHT P4.1 PER TABLE A DRINKING |
| | FOUNTAIN IS REQUIRED. |
| | 3. INDICATE THE USE OF THE MEZZANINE, |
| | AND INDICATE THE USE OF THE WORKSHOP TO |
| | DETERMINE OCCUPANCY. SECTION 106.1.1. |
| | 4. SHT 8.2 RESTROOM ELEVATIONS. SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS (SHOW LENGTH OF |
| | GRAB BAR BEHIND THE W/C) |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | FOR TOILET ROOMS: |
| | A. TURNING AREA TO BE UNOBSTRUCTED, W/C |
| | SHALL NOT BE IN TURNING AREA. SECTION |
| | 11-4.22.3 |
| | 5. SUBMIT A DETAIL FOR THE BREAK ROOM |
| | SINK SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.2 HEIGHT |
| | B. 11-4.24.3 KNEE CLEARANCE |
| | C. 11-4.24.4 SINK DEPTH |
| | D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD |
| | APPROACH REQUIED) |
| | E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | F. 11-4.24.7 FAUCETS |
| | 6. SUBMIT A DETAIL FOR THE DRINKING |
| | FOUNTAIN SHOWING THE FOLLOWING: |
| | A. 11-4.15.2 SPOUT HEIGHT |
| | B. 11-4.15.3 SPOUT LOCATION |
| | C. 11-4.15.4 CONTROLS |
| | D. 11-4.15.5 CLEARANCES/CLEAR FLOOR |
| | SPACE |
| | E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | 7. SHOW PIPE ROUTING FOR THE SANT. |
| | SYSTEM, WATER PIPING, STORM, AND |
| | CONDENSATE. SECTIONS 106.1.1, AND |
| | 106.3.5.1.3. |
| | 8. SUBMIT A SANITARY RISER DIAGRAM |
| | ISOMETRIC SHOW ALL PIPE SIZES, TRAPS, |
| | VENTS REQUIRED. SECTION 106.3.5.1.3. |
| | 9. SUBMIT A WATER RISER DIAGRAM SHOWING |
| | ALL PIPE SIZES, VALVES AND WATER HAMMER |
| | ARRESTORS IF REQUIRED BY SECTION 604.9. |
| | (AIR CHAMBERS ARE NOT APPROVED). SECTION 106.3.5.1.3. |
| | 10. SUBMIT A STORM RISER DIAGRAM SHOWING |
| | ALL PIPE SIZES AND INDICATE THE SQUARE |
| | FOOTAGE DRAINED BY EACH DRAIN. SECTION 106.3.5.1.3. |
| | 11. SUBMIT A CONDENSATE RISER DIAGRAM |
| | SHOWING ALL PIPE SIZE, TRAPS ETC. IN |
| | ISOMETRIC FORM. |
| | 12. SHT 6.2 INDICATES 6" ROOF DRAINS |
| | WITH SCUPPERS IN PARAPET NEXT TO THE |
| | DRAINS. SHT 8.2 INDICATES DOWNSPOUTS |
| | OUTSIDE BLDG WALL. PLEASE CLARIFY. IF |
| | ROOF DRAINS ARE DOWNSPOUTS, DOWNSPOUTS |
| | SHALL DISCHARGE AT LEAST 1 FOOT AWAY |
| | FROM THE STRUCTURE SIDEWALL. PLEASE |
| | INDICATE HOW THIS WILL BE ACCOMPLISHED. |
| | SECTION 1503.6. |
| | 13. RPZV BACKFLOW REQUIRED ON THE WATER |
| | SERVICE TO BLDG. |
| | 14. SEPARATE IRRIGATION PLANS AND PERMIT |
| | REQUIRED. SECTION 106.3.5.1.3. |
| | 15. CODE ADOPTED IN FBC-2004 IN EFFECT |
| | SINCE 10-01 2005. PLEASE CHANGE |
| | REFERENCES TO CODE TO REFLECT THIS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | REMOVE ALL VOIDED SHEETS AND RESUBMIT |
| | ONE SET FOR COMPARISON. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |