| 2006-01-25 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE |
| | |
| | 1.PLAN SHEET 9.1 GENERAL HVAC NOTE #2 |
| | INDICATES 2001 FBC.WE ARE CURRENTLY IN |
| | THE 2004 FBC. |
| | |
| | 2.PLAN SHEET 6.2, DETAIL FOR THE CURB. |
| | PLANS DO NOT INDICATE ATTACHMENT TO THE |
| | ROOF DECK.PLEASE NOTE, ROOF CURBS |
| | SHALL BE A MINIMUM OF 8" ABOVE THE ROOF |
| | SURFACE PER 2004 FBC 1509.7. |
| | |
| | 3.PLANS DO NOT PROVIDE A DETAIL FOR |
| | THE STANDS FOR THE EXISTING CONDENSING |
| | UNITS THAT WERE RELOCATED TO THE |
| | EXISTING ROOF.HEIGHT OF THE STANDS |
| | SHALL COMPLY WITH TABLE 1509.7 OF THE |
| | 2004 FBC. |
| | |
| | 4.PLEASE INDICATE HOW THE EQUIPMENT |
| | LOCATED ON THE ROOF WILL BE ACCESSED FOR |
| | SERVICE, MAINENTANCE OR REPLACEMENT. |
| | SHOW COMPLIANCE WITH 2004 FMC 306.5, |
| | EQUIPMENT LOCATED ON ROOFS WITH AN |
| | ELEVATION OF 16FT OR GREATER SHALL HAVE |
| | A PERMANENT MEANS OF ACCESS. |
| | |
| | 5.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2004 FMC |
| | TABLE 403.3. |
| | |
| | 6.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| | SHALL HAVE NOTIFICATION TO ALARM/STROBE |
| | IN NORMALLY OCCUPIED AREAS PER 2004 FMC |
| | 606.4.1 EXCEPTION #2. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |