Plan Review Notes
Plan Review Notes For Permit 05110189
Permit Number 05110189
Review Stop ENG
Sequence Number 1
Notes
Date Text
2006-01-27 00:00:00FAILED:
  
 1. PLEASE PROVIDE STORM WATER
 CALCULATION FOR THE PROPOSED IMPROVMENT
 ON THE ENTIRE SITE.
 2. SHEET C1, SHOWS TWO C.S. STRUCTURE,
 PLEASE VERIFY.
 3. SHEET C1 SHOWS A POWER POLE AT THE
 PROPOSED CURB CUT, IS THIS A FPL POLE OR
 BELONG TO THE CITY? NOTE THAT, IT SHOULD
 BE RELOCATED BY THE DEVELOPER WITH A
 PERMIT ISSUED FROM PUBLIC UTILITY
 DEPARTMENT AND FPL.
 4. ANY WORK WITHIN PUBLIC R.O.W WOULD
 REQUIRED A PERMIT FROM PUBLIC UTILITIES,
 THE PROPOSED 15 IN. STORM PIPE SHOULD BE
 RCP TYPE(IN PUBLIC R.O.W.), CONTACT
 494-1086, WINDEL PALMER.
 5. ARE THERE NEW CONNECTIONS FOR WATER
 AND SEWER OR THE EXISTING WILL BE USED?
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI