Plan Review Notes
Plan Review Notes For Permit 05110189
Permit Number 05110189
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-24 00:00:00*********** UNSAT **********
  
 ** PLEASE SEE PLANS REFERENCE THE 2001
 FBC, HOWEVER AS OF OCT 1ST, 2005, THE
 CODE HAS CHANGED TO THE 2004 FBC.
 PLEASE ADJUST DESIGNS REQUIRED.
 THIS IS REQUIRED FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 ALL PLANS ARE TO DICTATE CURRENT
 RELEVANT CODES.
  
 1)NOTE: PLEASE SEE TWO COMPLETELY
 DIFFERENT RISER DIAGRAMS WERE SUBMITTED.
 IT IS ASSUMED, THE RISER SHOWN ON 10.2
 IS THE ONE FOR REVIEW , AS THE PREVIOUS
 RISER IS INCOMPLETE AND WOULD HAVE
 NUMEROUS COMMENTS.
 THIS REVIEW IS FOR THE ONE ON 10.2,
  
 A) PLEASE CONDUCTORS FROM GUTTER TO THE
 RELOCATED EXISTING MAINS.
  
 B)NOTE: PLEASE INCLUDE THOSE EXISTING
 DISCONNECTS SIZES.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE "D"
 INDICATE DEDICATED BATHROOM CIRCUIT,
 HOWEVER ONLY TWO BATHROOMS ARE SHOWN AND
 NEITHER OF THOSE CONTAIN ELECTRICAL GFI
 RECEPTS???
  
 3)NOTE: PLEASE VERIFY SIGN CIRCUIT PER
 600.5.
  
 4)NOTE: PLEASE INDICATE LOADING FOR
 SHYOW WINDOW CIRCUIT. 220.12A
 PLEAS ADJUST THE # OF CIRCUITS OF
 NEEDED.
  
 5)NOTE: PLEASE SEE LOADS FOR RTU'S
 APPEAR TO BE ROUNDED DOWN?
 PLEASE SEE EACH IS SHOWN AS 10,800VA,
 HOWEVER THE TOTAL VA SHOWN ON LOAD CALCS
 DOES NOT CORRELATE.
 PLEASE ALSO SEE 43KW + IS MORE THAN
 104A'S.
 215.5
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% ALONG WITH ANY LARGEST MOTOR
 LOADS.
 215.3,230.42 ETC.
  
 7)NOTE: PLEASE SEE NOTE ON 10.2 MENTIONS
 TO SEE MEZZ PLANS FOR ELECTRICLA AND
 EGRESS LTS, HOWEVER THIS COULD NOT BE
 LOCATED ON ELECTRICAL SHEETS SUBMITTED.
 PLEASE SEE NFPA-101 7.8,7.9.
 PLEASE SEE A MIN OF 10FT CANDLES IS NOW
 REQUIRED FOR EGRESS STAIRS UNDER NORMAL
 POWER AND A MIN OF 1FT CANDLE UNDER
 EMERGENCY POWER.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FORM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ANY OLD/VOIDED
 SHEETS FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  