| 2005-12-24 00:00:00 | *********** UNSAT ********** |
| | |
| | ** PLEASE SEE PLANS REFERENCE THE 2001 |
| | FBC, HOWEVER AS OF OCT 1ST, 2005, THE |
| | CODE HAS CHANGED TO THE 2004 FBC. |
| | PLEASE ADJUST DESIGNS REQUIRED. |
| | THIS IS REQUIRED FOR ALL TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | ALL PLANS ARE TO DICTATE CURRENT |
| | RELEVANT CODES. |
| | |
| | 1)NOTE: PLEASE SEE TWO COMPLETELY |
| | DIFFERENT RISER DIAGRAMS WERE SUBMITTED. |
| | IT IS ASSUMED, THE RISER SHOWN ON 10.2 |
| | IS THE ONE FOR REVIEW , AS THE PREVIOUS |
| | RISER IS INCOMPLETE AND WOULD HAVE |
| | NUMEROUS COMMENTS. |
| | THIS REVIEW IS FOR THE ONE ON 10.2, |
| | |
| | A) PLEASE CONDUCTORS FROM GUTTER TO THE |
| | RELOCATED EXISTING MAINS. |
| | |
| | B)NOTE: PLEASE INCLUDE THOSE EXISTING |
| | DISCONNECTS SIZES. |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULE "D" |
| | INDICATE DEDICATED BATHROOM CIRCUIT, |
| | HOWEVER ONLY TWO BATHROOMS ARE SHOWN AND |
| | NEITHER OF THOSE CONTAIN ELECTRICAL GFI |
| | RECEPTS??? |
| | |
| | 3)NOTE: PLEASE VERIFY SIGN CIRCUIT PER |
| | 600.5. |
| | |
| | 4)NOTE: PLEASE INDICATE LOADING FOR |
| | SHYOW WINDOW CIRCUIT. 220.12A |
| | PLEAS ADJUST THE # OF CIRCUITS OF |
| | NEEDED. |
| | |
| | 5)NOTE: PLEASE SEE LOADS FOR RTU'S |
| | APPEAR TO BE ROUNDED DOWN? |
| | PLEASE SEE EACH IS SHOWN AS 10,800VA, |
| | HOWEVER THE TOTAL VA SHOWN ON LOAD CALCS |
| | DOES NOT CORRELATE. |
| | PLEASE ALSO SEE 43KW + IS MORE THAN |
| | 104A'S. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125% ALONG WITH ANY LARGEST MOTOR |
| | LOADS. |
| | 215.3,230.42 ETC. |
| | |
| | 7)NOTE: PLEASE SEE NOTE ON 10.2 MENTIONS |
| | TO SEE MEZZ PLANS FOR ELECTRICLA AND |
| | EGRESS LTS, HOWEVER THIS COULD NOT BE |
| | LOCATED ON ELECTRICAL SHEETS SUBMITTED. |
| | PLEASE SEE NFPA-101 7.8,7.9. |
| | PLEASE SEE A MIN OF 10FT CANDLES IS NOW |
| | REQUIRED FOR EGRESS STAIRS UNDER NORMAL |
| | POWER AND A MIN OF 1FT CANDLE UNDER |
| | EMERGENCY POWER. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FORM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF ANY OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THEREARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |