2005-11-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110182
 ADD: 220 SUNSET RD
 CONT: GUSTASON
 TEL: (561)732-0656
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW:
 ACTION: DENIED
  
 1) ENTEGRA VALENCIA SPANISH "S",
 INDICATE TYPE OF FASTENING DEVISE, THE
 MINIMUM REQUIRED AERODYNAMIC UPLIFT
 MOMENT MF=(FT-LBF) 26.1. HIGHLIGHT WHICH
 APPLICATION WILL BE USED.
  
 2) TARCO ROOFING UNDERLAYMENT SUBMITTED
 IS UNDER THE 2001 CODE NOT 2004. THE
 PRODUCT INFORMATION SUBMITTED DOES NOT
 HAVE THE PRESSURES TESTED FOR.
  
 3) MULE-HIDE MODIFEID UNDERLAYMENT HAS A
 LIMITATION # 9, GOOD FOR ONLY -45 LBS.
 THERE CAN BE NO ENHANCED NAILING IN ANY
 ZONE. END ZONE HAVE A MINIMUM PRESSURE
 OF -89.0.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715