| 2006-04-04 00:00:00 | BUILDING REVIEW PROVISO: |
| | *1- SHEET A-3: A) REVISE TYPE OF |
| | CONSTRUCTION. SEE FBC 2004. THERE IS NOT |
| | CONSTRUCTION TYPE VI ON 2004 FBC. |
| | B) MEAN ROOF HEIGHT IS +/-21'-3", NOT |
| | 15'-0. REVISE AS REQUIRED. |
| | C) REVISE BUILDING HEIGHT. SEE |
| | DEFINITION ON SEC. 502 FBC 2004. |
| | D) REVISE/CLARIFY REFERENCE TABLE USED |
| | FOR WIND ANALYSIS. WHICH ONE IS TABLE |
| | R301.2?. SEE TABLES AND REVISE AS REQ'D. |
| | *2- TRUSS DESIGN PACKAGE: A) ENGINEER TO |
| | USE CURRENT APPROVED SEAL THAT SAYS |
| | "LICENSE" INSTEAD OF "CERTIFICATE" AS |
| | REQUIRED BY FLORIDA ADMINISTRATIVE CODE. |
| | B) ALL GENERAL DETAILS SUBMITTED WITH |
| | TRUSS PACKAGE NEED TO HAVE ENGINEER'S |
| | ORIGINAL SEAL, SIGNATURE AND DATE AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE |
| | AND FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002. |
| | *3- CONNECTOR SPECIFIED FOR GIRDER TRUSS |
| | N1G DOESN'T RESIST THE CALCULATED UPLIFT |
| | LOADS. ARCHITECT TO REVISE CONNECTOR. |
| | *4- RE-SUBMIT COMPLETE PRODUCT APPROVAL |
| | PACKAGE. NEED TO PROVIDE 2004 FLORIDA |
| | PRODUCT APPROVAL VERSION, NOT 2001. |
| | *5- PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS UNDER A SEPARATE PERMIT. |
| | *6- NEED SURVEY WITH ORIGINAL SIGNATURE |
| | AS REQUIRED BY CHAPTER 472 FL. STATUTE. |
| | *7- ARCHITECT'S REVIEW STAMP USED TO |
| | APPROVE PRODUCT APPROVALS DOESN'T HAVE |
| | THE ARCHITECT'S NAME OR COMPANY'S NAME |
| | ON IT. NEED STAMP THAT IDENTIFIES |
| | COMPANY OR ARCHITECT REVIEWING THE |
| | PRODUCTS. |