| 2006-05-03 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | THIRD REVIEW, SAME PAPERWORK SUBMITTED - |
| | CALLED CONTRACTOR AND HAD CONVERSATION |
| | IN REGARDS TO HOW TO SHOW CODE |
| | COMPLIANCE FOR PERMITTING |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | THE NOC PROVIDED IS EXPIRED, OVER 90 |
| | DAYS WITHOUT COMMENCING WORK |
| | FS713.13(2). |
| | |
| | 2.)PROVIDE BUILDING MEAN ROOF HEIGHT. |
| | DESIGN PRESSURES FOR BUILDINGS OVER |
| | 60FEET ARE REQUIRED TO BE DESIGNED USING |
| | ASCE7, FBC1609.1.1.DOCUMENTS PREPARED |
| | BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| | RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| | FAC61G15-23.002. |
| | |
| | THE SCHEDULE GIVES DESIGN PRESSURES OF |
| | -13.5 AND -14.1, BUT -45 IS CIRCLED ON |
| | SHEET 9 OF THE PRODUCT APPROVAL.DESIGN |
| | PRESSURES ARE TO BE DETERMINED BY FBC |
| | TABLE 1609.6B AND 1609.6D. |
| | |
| | 3.)ADDRESSED. |
| | |
| | 4.)COMPLETE THE ATTACHED INSTALLATION |
| | SCHEDULE, OR PROVIDE REQUIRED |
| | INFORMATION IN A SIMILAR FORMAT.SEE |
| | ATTACHED POLICY. |
| | |
| | THE FORM WAS NOT FILLED OUT CORRECTLY |
| | (ALL COLUMNS BLANKEXCEPT FOR DPS WHICH |
| | ARE INCORRECT).NO ANCHOR SPACING |
| | INDICATED ON PRODUCT APPROVAL.NOT |
| | ENOUGH INFORMATION PROVIDED TO DETERMINE |
| | CODE COMPLIANCE. |
| | |
| | |