| Plan Review Notes For Permit 05101193 |
| Permit Number |
05101193 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-04 00:00:00 | *** DENIED *** | | | 1)ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 2) NEED TO SHOW TRANSFER AIR GRILL SIZE | | | AND SUPPLY AIR DUCT SIZE. PLEASE NOTE | | | TRANSFER GRILL MUST BE 50 SQUARE INCHES | | | PER 100 CFM'S OF SUPPLY AIR. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | 2005-12-29 00:00:00 | NEW MECH SHEETS. |
|