Plan Review Notes For Permit 05101187
Permit Number 05101187
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-11-21 00:00:00DENIED:
  
 1) NEW FIRE ALARM SYSTEMS SHALL BE
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL FIRE ALARM SYSTEMS THAT SUPERVISE
 FIRE SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENT ATTESTING
 TO THIS CERTIFICATION PRIOR TO FINAL
 APPROVAL OF THE FIRE ALARM SYSTEM.
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 4) THE CITY OF WEST PALM BEACH FIRE
 MARSHAL OFFICE REQUIRED DUCT DETECTORS
 TO INITIATE A GENERAL FIRE ALARM.
  
 5) PLEASE EXPLAIN WHY THERE ARE TWO (2)
 PERMIT APPLICATION FOR FIRE ALARM SYSTEM
 FOR THIS BUILDING. (05100244)
  
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754