| Plan Review Notes For Permit 05101187 |
| Permit Number |
05101187 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-21 00:00:00 | DENIED: | | | | | | 1) NEW FIRE ALARM SYSTEMS SHALL BE | | | LISTED FOR CENTRAL STATION SERVICE. | | | | | | 2) ALL FIRE ALARM SYSTEMS THAT SUPERVISE | | | FIRE SPRINKLER SYSTEMS SHALL BE UL | | | CERTIFICATED AND HAVE DOCUMENT ATTESTING | | | TO THIS CERTIFICATION PRIOR TO FINAL | | | APPROVAL OF THE FIRE ALARM SYSTEM. | | | | | | 3) THE FIRE ALARM SYSTEM SHALL BE CLASS | | | "A" OR FULLY ADDRESSABLE. | | | | | | 4) THE CITY OF WEST PALM BEACH FIRE | | | MARSHAL OFFICE REQUIRED DUCT DETECTORS | | | TO INITIATE A GENERAL FIRE ALARM. | | | | | | 5) PLEASE EXPLAIN WHY THERE ARE TWO (2) | | | PERMIT APPLICATION FOR FIRE ALARM SYSTEM | | | FOR THIS BUILDING. (05100244) | | | | | | | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|