| Plan Review Notes For Permit 05101140 |
| Permit Number |
05101140 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-06 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)YOU HAVE SUBMITTED TWO PRODUCT | | | APPROVALS FOR PANELS.CLARIFY; ARE YOU | | | INSTALLING TWO DIFFERENT TYPES OF | | | PANELS? | | | | | | 2.)THE INSTALLATION SCHEDULE STATES | | | THAT YOU ARE INSTALLING FL#358, BUT THIS | | | IS NOT ONE OF THE PRODUCT APPROVALS | | | SUBMTITED. | | | | | | 3.)TWO COPIES OF ALL DOCUMENTS | | | REQUIRED.ONLY ONE FLOOR | | | PLAN/INSTALLATION SCHEDULE WAS | | | SUBMITTED. | | | | | | 4.)YOU HAVE SPECIFIED 1" FASTENERS, | | | BUT THERE IS A 7/8" EMBEDMENT | | | REQUIREMENT.THIS LEAVES ONLY 1/8" FOR | | | STUCCO.PLEASE ADDRESS. | | | | | | 5.)IT IS NOT CLEAR HOW YOU HAVE | | | ARRIVED AT THE DESIGN PRESSURES.FOR | | | INSTANCE, OPENING 3 IS 18SF, SHOULD BE | | | -47.3 EXPOSURE C, 19' MRF AS YOU HAVE | | | DECLARED ON THE INSTALLATION SCHEDULE. | | | SEE FBC TABLE 1609.6B, 1606.2D.PLEASE | | | CONTACT ME IF YOU NEED ASSISTANCE. | | | |
|