| Plan Review Notes For Permit 05101117 |
| Permit Number |
05101117 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-13 00:00:00 | DENIED | | | REFERENCE:FBC-2004 FUEL GAS | | | | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS REVISION. | | | | | | 1. PER TABLE 402.4(2) USING THE LONGEST | | | LENGTH METHOD PER 402.4.1 THE GAS | | | REVISION IS SIZED WRONG.(PLEASE CORRECT) | | | 2. IT APPEARS THAT ON REVISION THAT GAL- | | | VANIZED PIPE IS UNDERGROUND, PER SEC. | | | 404.8 AND PAUL SCHMITZ CHIEF PLUMBING | | | INSPECTOR GALVANIZED PIPE UNDERGROUND | | | SHALL NOT BE USED.(PLEASE CORRECT OR IN- | | | DICATE THAT PIPE IS NOT UNDERGROUND) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)806-6721 |
|