Plan Review Notes
Plan Review Notes For Permit 05101117
Permit Number 05101117
Review Stop G
Sequence Number 2
Notes
Date Text
2006-03-13 00:00:00DENIED
 REFERENCE:FBC-2004 FUEL GAS
  
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS REVISION.
  
 1. PER TABLE 402.4(2) USING THE LONGEST
 LENGTH METHOD PER 402.4.1 THE GAS
 REVISION IS SIZED WRONG.(PLEASE CORRECT)
 2. IT APPEARS THAT ON REVISION THAT GAL-
 VANIZED PIPE IS UNDERGROUND, PER SEC.
 404.8 AND PAUL SCHMITZ CHIEF PLUMBING
 INSPECTOR GALVANIZED PIPE UNDERGROUND
 SHALL NOT BE USED.(PLEASE CORRECT OR IN-
 DICATE THAT PIPE IS NOT UNDERGROUND)
  
 END OF COMMENTS:
  