| Plan Review Notes For Permit 05101097 |
| Permit Number |
05101097 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-15 00:00:00 | | | | PLEASE SUMBIT LOAD CALCULATIONS SHOWING | | | EXISTING LOADS AND THE ADDED POOL | | | EQUIPMENT LOADS. ALSO INDICATE IF THE | | | EXISTING SERVICE IS ADEQUITE FOR THE | | | PROPOSED LOADS. | | | | | | ALSO SUBMIT MANUFACTURER SPEC"S FOR THE | | | HEATER. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|