| Plan Review Notes For Permit 05101092 |
| Permit Number |
05101092 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-18 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE A RISER DIAGRAM OF THE | | | PROPOSED SERVICE, INCLUDE: | | | A) CONDUDIT AND CONDUCTOR SIZES. | | | | | | B) AIC RATING OF EQUIPMENT, 110.9. | | | | | | C) GROUNDING ELECTRODE SYSTEM PER250.50 | | | | | | | | | D) GEC SIZE PER 250.66. | | | | | | E) AMPERE AND DISCONNECT RATING OF | | | MAIN. | | | | | | PLEASE SEE 110.26 FOR CLEARANCE | | | REQUIREMENT | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | |
|