Plan Review Notes
Plan Review Notes For Permit 05101092
Permit Number 05101092
Review Stop E
Sequence Number 1
Notes
Date Text
2005-11-18 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A RISER DIAGRAM OF THE
 PROPOSED SERVICE, INCLUDE:
 A) CONDUDIT AND CONDUCTOR SIZES.
  
 B) AIC RATING OF EQUIPMENT, 110.9.
  
 C) GROUNDING ELECTRODE SYSTEM PER250.50
  
  
 D) GEC SIZE PER 250.66.
  
 E) AMPERE AND DISCONNECT RATING OF
 MAIN.
  
 PLEASE SEE 110.26 FOR CLEARANCE
 REQUIREMENT
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  