| Plan Review Notes For Permit 05100947 |
| Permit Number |
05100947 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-07-05 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE SERVICE ENTRANCE CONDUCTORS FOR | | | 200 AMPS MUST BE A MINIMUM OF 2/0 | | | COPPER, 310.15(B)(6). | | | | | | 2} CIRCUIT #18, #12WIRE ON A 30 AMP | | | BREAKER DOES NOT COMPLY WITH 310.16. | | | | | | 3} THE COOKTOP AND THE AHU HAVE | | | INCORRECT OCP AND WIRE SIZE FOR THE | | | RESPECTIVE LOADS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|