Plan Review Notes
Plan Review Notes For Permit 05100947
Permit Number 05100947
Review Stop E
Sequence Number 3
Notes
Date Text
2006-05-30 00:00:00 
 NONCOMLPIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 PANEL SHOWN ON THE RISER, ON THE PLAN.
  
 2} THE FEEDER FROM THE MAIN TO THE PANEL
 IS INCORRECT FOR A 200 AMP SERVICE. SEE
 310.15(B)(6).
  
 3}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} THE 80 AMP OCP IS TOO LARGE FOR THE
 CONDUCTORS FEEDONG THE AHU'S. SEE
 310.16. ALSO SEE CIRCUITS 2,4 IS
 MISMARKED "A/C".
  
 5} CIRCUIT #15 MARKED "FUTURE POOL PUMP"
 SHOWS 2500 WATTS ON A 20 AMP BREAKER,
 PLEASE CORRECT.
  
 6} CIRCUIT #17 MARKED "FUTURE POOL
 HEATER" @ 1200 WATTS SEEMS INCORRECT.
 TYPICALLY THESE HEATERS ARE NO SMALLER
 THAN 5000 WATTS @ 240 VOLTS.
  
 7} PLEASE CORRECT CIRCUIT #9 & 11, 30AMP
 OCP FOR 10000 WATTS.
  
 8} THERE ARE RECEPTACLES MISSING FROM
 THE BEDROOM(#2)AND THE NEW BEDROOM.
 210.52(A).
  
 9} A RECEPTACLE PER 210.52(E) MUST BE
 INSTALLED AT THE FRONT OF THE BUILDING.
  
 10} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW