| 2006-05-30 00:00:00 | |
| | NONCOMLPIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE INDICATE THE LOCATION OF THE |
| | PANEL SHOWN ON THE RISER, ON THE PLAN. |
| | |
| | 2} THE FEEDER FROM THE MAIN TO THE PANEL |
| | IS INCORRECT FOR A 200 AMP SERVICE. SEE |
| | 310.15(B)(6). |
| | |
| | 3}PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 4} THE 80 AMP OCP IS TOO LARGE FOR THE |
| | CONDUCTORS FEEDONG THE AHU'S. SEE |
| | 310.16. ALSO SEE CIRCUITS 2,4 IS |
| | MISMARKED "A/C". |
| | |
| | 5} CIRCUIT #15 MARKED "FUTURE POOL PUMP" |
| | SHOWS 2500 WATTS ON A 20 AMP BREAKER, |
| | PLEASE CORRECT. |
| | |
| | 6} CIRCUIT #17 MARKED "FUTURE POOL |
| | HEATER" @ 1200 WATTS SEEMS INCORRECT. |
| | TYPICALLY THESE HEATERS ARE NO SMALLER |
| | THAN 5000 WATTS @ 240 VOLTS. |
| | |
| | 7} PLEASE CORRECT CIRCUIT #9 & 11, 30AMP |
| | OCP FOR 10000 WATTS. |
| | |
| | 8} THERE ARE RECEPTACLES MISSING FROM |
| | THE BEDROOM(#2)AND THE NEW BEDROOM. |
| | 210.52(A). |
| | |
| | 9} A RECEPTACLE PER 210.52(E) MUST BE |
| | INSTALLED AT THE FRONT OF THE BUILDING. |
| | |
| | 10} THE PERSON TAKING RESPONSIBILITY FOR |
| | THE DESIGN MUST PRINT AND SIGN THEIR |
| | NAME TO SAME PER 106.3.4.2. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |